PYROCON19
Owner’s manual & Technician Settings
Pg. 11
Technician settings (Cont’)
P06 – Heaters cycle and splitting time
Press the [SELECT] and [+] buttons simultaneously.
“P06”, “SP” and the splitting time will appear on display.
The minutes will blink.
The heaters cycle / splitting time parameter defines the working time of the
heaters when working in sequence.
Example: the splitting time is set to 120 minutes and 4 heaters work in
sequence, each heater will be ON for 30 minutes (120/4=30).
Use the [+] and [-] buttons to adjust the splitting time.
Range: 1...600 minutes
Default: 120 minutes.
Splitting time
Cont’