Safety
Meets the requirements of EN61010-1 Cat III 300 V phase to earth.
IEC61557
Complies with the following parts of EN61557, Electrical safety in low
voltage systems up to 1000 V a.c. and 1500 V d.c. - Equipment for
testing, measuring or monitoring of protective measures:
Part1 - General Requirements
Part4 - Residual current devices
Power supply
Batteries:
8 x 1,5 V cells IEC LR6 type (AA alkaline).
Rechargeable:
8 x 1.2 V NiCd or NiMH cells may be used.
Battery condition is constantly shown on the display as a four-section
bar graph.
Battery Life:
1000 consecutive tests
Weight
All units 980gms
Dimensions
All units 203 x 148 x 78 mm
E.M.C
In accordance with IEC61326 including amendment No.1
17
SPECIFICATION
RCD Test Ranges (to EN61557-6)
Test Current Accuracy:
No Trip Test:
(
∆
I) –8% to –2%
Trip Test:
(I, 5I) +2% to +8%
Trip Time:
±1% ±1ms
Voltage measurement (All Models)
Range ac:
0 V - 300 V 25Hz to 450Hz
Accuracy:
±2% ±2 digits
Frequency measurement
(RCDT320 only)
Range:
25Hz to 450Hz
Accuracy:
25.0Hz to 199.9Hz ±0.1Hz
200Hz to 450Hz ±1Hz
Fault (Touch) Voltage
Displayed range:
0 V to 50 V (displayed on the analogue bar graph)
Error:
+5%/+15% ±0.5 V
Temperature and humidity
Operating Range:
-5°C to +40°C
Operating Humidity:
93% R.H. at +40°C max.
Storage Range:
-25°C to +70°C
Maximum altitude:
2000m
Environmental Protection:
Weather proof to IP54
RCDT300_UG_en_V01 07/05/2004 12:07 pm Page 17
Содержание RCDT300 Series
Страница 20: ...20 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 20...
Страница 21: ...21 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 21...
Страница 22: ...22 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 22...
Страница 23: ...23 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 23...