Standard test probes and crocodile clips are supplied for connection to the
circuit under test.

Application

This instrument may be connected live to earth or between live
conductors of systems that have a rated voltage of 600 V a.c. rms to earth
and an installation (overvoltage) Category III or lower.

This means that the instrument may be connected to any fixed wiring of a
building installation, but not to primary supply circuits such as overhead
cables. To maintain user safety and ensure accurate measurements, only
use the test leads supplied by Megger Limited.

The display shows the fault voltage limit, ‘25 V’ or ‘50 V’. 

If the fault-voltage display is active, a bar-graph display will also appear.    

5. Press the [0º/180º] button to change the limit setting from 25V to 50V

and back.

6. Press the [TYPE] button to turn bar-graph display ON or OFF.

7. Press the [TEST] button to exit from the set-up menu.

Test leads

All test leads form part of the measuring circuit of the instrument and
must not be modified or changed in any way, or be used with any other
electrical instrument or appliance. 

The power cord supplied with the Megger testers is a test lead that forms
part of the measuring circuit of the instrument. The overall length of this
lead must not be altered. If the power cord plug is not suitable for your
type of socket outlets, do not use an adapter. You may change the plug
once only by cutting the cord as close to the plug as possible and fitting a
suitable plug.

The colour code of the cord is: 

Earth (Ground) Yellow/Green

Neutral Blue

Phase (Line) Brown

NOTE:

A plug severed from the power cord must be destroyed, as a plug

with bare conductors is hazardous in a live socket outlet.

Test lead connection

The supplied test leads should be connected to the appropriate sockets
on the rear of the instrument marked L0 and L1, or to the 3 way test
socket.

RCDT300_UG_en_V01  07/05/2004  12:07 pm  Page 10

Содержание RCDT300 Series

Страница 1: ...M RCDT300 Series Residual Current Device testers USER MANUAL RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 1...

Страница 2: ...ged Test leads probes and crocodile clips must be in good order clean and with no broken or cracked insulation The battery cover must be in place whilst conducting tests Voltage indicator LED s cannot...

Страница 3: ...the carton 5 LCD Display 6 Top panel 6 Lid open closure 17 Preparations for use 8 Batteries 8 Preliminary test lead check 8 General operating instructions 8 Display warning symbols 9 Setup procedure...

Страница 4: ...ent test RAMP 0 180 polarity selection Selective breakers INTRODUCTION GENERAL DESCRIPTION 4 Thank you for purchasing the Megger RCD Tester For your own safety and to get the maximum benefit from your...

Страница 5: ...RCDT320 1 x RCDT300 series RCD tester 1 x 3 wire test lead with prods with clips 8 x AA LR6 batteries fitted in instrument 1 x Test lead case 1 x Warranty card 1 x Calibration certificate 1 x Owners C...

Страница 6: ...0mA RCDT320 only 30mA 100mA 300mA 500mA 1000mA RCDT320 only Neck strap slots Test selector x I RCD trip time 1 x I RCD trip time 5 x I RCD trip time AUTO RCDT320 only Ramp RCDT320 only V AC DC volts R...

Страница 7: ...taining slot 4 Connection Panel RCDT300 Series test lead connections 7 Mains plug test lead connector Single or 3Phase connection Neutral or 2nd phase connection Warning Refer to User Guide Maximum 30...

Страница 8: ...ator will be displayed Default voltmeter The default voltmeter automatically operates in all test modes indicating connection to a live system Auto Power down To extend battery life the instrument wil...

Страница 9: ...ble on the instruments as per the relevant tables in the specification section of this document Reverse polarity detection Touch voltage setting To select Polarity reversal acceptance or rejection 1 W...

Страница 10: ...the TEST button to exit from the set up menu Test leads All test leads form part of the measuring circuit of the instrument and must not be modified or changed in any way or be used with any other ele...

Страница 11: ...ING 11 Method of measurement The plug ended test lead or two wire lead should be used for this measurement A constant current source is connected across the supply and the time taken for the supply to...

Страница 12: ...p 12 NOTE If the RCD should trip while performing a 1 2I test the error message trP will be displayed instead of the time display 1xI RCD trip time measurement To test the 1xI trip time of the install...

Страница 13: ...RCDs these should be tested at 0 and 180 or in the case of DC sensitive RCD s positive or negative Possible sources of error Measurement results can be affected by the following 1 Significant operatin...

Страница 14: ...a lower charge than Alkaline batteries and my not give much warning before becoming exhausted To replace batteries Warning Do not switch the instrument on with the battery cover removed 1 Switch off t...

Страница 15: ...hould not be left in an instrument which may remain unused for extended periods Fuse Blown indication The fuse blown symbol f indicates that an internal fuse has failed This instrument is fitted with...

Страница 16: ...indicates which Megger RCD300 series testers feature the Touch voltage inhibit feature RCD Testers Line reversal detection Inhibit available Y N Y N English language RCDT310 EN AU No No RCDT320 EN AU...

Страница 17: ...All units 980gms Dimensions All units 203 x 148 x 78 mm E M C In accordance with IEC61326 including amendment No 1 17 SPECIFICATION RCD Test Ranges to EN61557 6 Test Current Accuracy No Trip Test I 8...

Страница 18: ...y voltage temperature interference and system voltage and frequency where applicable 18 BASIC AND SERVICE ERRORS ACCESSORIES AND EQUIPMENT Item Order Code 2 wire test lead set and crocodile clips 6220...

Страница 19: ...Archcliffe Road Valley Forge Corporate Centre Dover 2621 Van Buren Avenue Kent CT17 9EN Norristown PA 19403 England U S A Tel 44 0 1304 502 243 Tel 1 610 676 8579 Fax 44 0 1304 207 342 Fax 1 610 676...

Страница 20: ...20 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 20...

Страница 21: ...21 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 21...

Страница 22: ...22 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 22...

Страница 23: ...23 RCDT300_UG_en_V01 07 05 2004 12 07 pm Page 23...

Страница 24: ...0 1 30 16 08 90 F 33 0 1 34 61 23 77 OTHER TECHNICAL SALES OFFICES Toronto CANADA Sydney AUSTRALIA Mumbai INDIA Madrid SPAIN and the Kingdom of BAHRAIN Megger products are distributed in 146 countrie...

Отзывы: