66
Description of Voltage Decay
Voltage Decay is probably only used around 8% of the time, but it is especially
useful when a fault breaks down and then reseals itself. This can be termed a
“flashing or pecking” fault. Voltage decay can also be used where the voltage
required to breakdown the fault cannot be achieved with the surge generator.
In Voltage Decay we typically use a High Voltage d.c. source, a voltage divider
and the MTDR100 which is operating as a transient recorder.
HV DC is applied and the voltage increased until the fault breaks down, and a
flashover occurs. During this flashover (the point of fault) the resultant
transients are reflected back and forward between the fault and the dc source.
These transients are detected by the voltage divider and fed to the MTDR where
they are subsequently displayed.
Typical Trace
Distance / 2 = Fault Distance
Содержание PFL22M1500 Series
Страница 2: ......
Страница 16: ...M AVTMPFL22M Rev 1 April 2011 6 M...
Страница 28: ...M AVTMPFL22M Rev 1 April 2011 18 M...
Страница 40: ...M AVTMPFL22M Rev 1 April 2011 30 M...
Страница 43: ...AVTMPFL22M Rev 1 April 2011 33 Addendum 1 MTDR100 User Guide...
Страница 44: ...M AVTMPFL22M Rev 1 April 2011 34 M...
Страница 61: ...AVTMPFL22M Rev 1 April 2011 51 Addendum 2 PFL22M1500INV XX PFL22M1500INV Inverter Option only...
Страница 62: ...M AVTMPFL22M Rev 1 April 2011 52 M...
Страница 68: ...M AVTMPFL22M Rev 1 April 2011 58 M...
Страница 69: ...AVTMPFL22M Rev 1 April 2011 59 Addendum 3 Cable Fault Location Applications Guide...
Страница 70: ...M AVTMPFL22M Rev 1 April 2011 60...
Страница 77: ...AVTMPFL22M Rev 1 April 2011 67 Megger Quality System Certificate...
Страница 78: ...M AVTMPFL22M Rev 1 April 2011 68...