SAFETY
AVTMPFL22M Rev 1 April 2011
17
Safety in Using the PFL
Never assume that either the PFL22M1500 High Voltage Output Cable or
the Cable Specimen is de-energized. Always treat exposed conductors and
connections as potential electric shock hazards.
The PFL22M1500 and the Cable under test are both sources of
instantaneously lethal levels of electrical energy.
Do not use this equipment to locate faults on any cable that may be close
enough to an energized cable to allow a burn-through of the insulation of
the energized cable.
Do not operate the PFL if it has not first been stabilized and in an upright
position.
Remain a safe distance from all parts of the High-Voltage circuit, including
all connections, unless the equipment is de-energised and all parts of the test
circuit are earthed/grounded. Be aware that any voltage applied to the Cable
Specimen will be present at the remote end(s) and at any other exposed part
of the cable, often out of sight of the operator.
Use the grounding and connection procedures. If other manufacturers'
equipment is used with the PFL, the user is responsible for verifying that the
grounding and interconnections between the systems comply with each
Manufacturer's Instructions.
Use Industry Accepted practices for making reliable, low-impedance
connections, capable of carrying large surge currents.
Maintain adequate air clearances between the exposed High-Voltage
conductor and any adjacent grounds to prevent spark-over. An uncontrolled
spark-over can create a safety hazard.
Megger recommends the use of appropriately rated rubber gloves when
connecting and disconnecting to the High-Voltage terminals.
An Interlock circuit is provided (and its use is highly recommended) to
enable the operator to safely control access to the complete high-voltage
circuit.
Содержание PFL22M1500 Series
Страница 2: ......
Страница 16: ...M AVTMPFL22M Rev 1 April 2011 6 M...
Страница 28: ...M AVTMPFL22M Rev 1 April 2011 18 M...
Страница 40: ...M AVTMPFL22M Rev 1 April 2011 30 M...
Страница 43: ...AVTMPFL22M Rev 1 April 2011 33 Addendum 1 MTDR100 User Guide...
Страница 44: ...M AVTMPFL22M Rev 1 April 2011 34 M...
Страница 61: ...AVTMPFL22M Rev 1 April 2011 51 Addendum 2 PFL22M1500INV XX PFL22M1500INV Inverter Option only...
Страница 62: ...M AVTMPFL22M Rev 1 April 2011 52 M...
Страница 68: ...M AVTMPFL22M Rev 1 April 2011 58 M...
Страница 69: ...AVTMPFL22M Rev 1 April 2011 59 Addendum 3 Cable Fault Location Applications Guide...
Страница 70: ...M AVTMPFL22M Rev 1 April 2011 60...
Страница 77: ...AVTMPFL22M Rev 1 April 2011 67 Megger Quality System Certificate...
Страница 78: ...M AVTMPFL22M Rev 1 April 2011 68...