AVTMPFL22M Rev 1 April 2011
19
4
PREPARING FOR TEST
IMPORTANT SAFETY WARNINGS
F
WARNING
The surge return is isolated from chassis ground by a 2000ohm
resistor. This limits current in the case of a failed concentric neutral.
The surge return cannot be used as a substitute system ground.
Failure to follow this procedure can result in serious injury
or in the extreme, death of the operator and/or the destruction of the
equipment.
F
WARNING
The operator is isolated from transient voltages along the surge
return by the insulation system in the PFL and by the insulated
jacket of the high voltage output cable. Tears or breaks in the
insulating jacket of the High-Voltage output cable expose the Surge
Return to the operator and poses a safety hazard and the cable
should be replaced.
F
WARNING
DO NOT EXTEND the Surge Return lead of the HV Output Cable
because this introduces excessive impedance in the Surge Return
and could result in exposed hazardous voltages.
Содержание PFL22M1500 Series
Страница 2: ......
Страница 16: ...M AVTMPFL22M Rev 1 April 2011 6 M...
Страница 28: ...M AVTMPFL22M Rev 1 April 2011 18 M...
Страница 40: ...M AVTMPFL22M Rev 1 April 2011 30 M...
Страница 43: ...AVTMPFL22M Rev 1 April 2011 33 Addendum 1 MTDR100 User Guide...
Страница 44: ...M AVTMPFL22M Rev 1 April 2011 34 M...
Страница 61: ...AVTMPFL22M Rev 1 April 2011 51 Addendum 2 PFL22M1500INV XX PFL22M1500INV Inverter Option only...
Страница 62: ...M AVTMPFL22M Rev 1 April 2011 52 M...
Страница 68: ...M AVTMPFL22M Rev 1 April 2011 58 M...
Страница 69: ...AVTMPFL22M Rev 1 April 2011 59 Addendum 3 Cable Fault Location Applications Guide...
Страница 70: ...M AVTMPFL22M Rev 1 April 2011 60...
Страница 77: ...AVTMPFL22M Rev 1 April 2011 67 Megger Quality System Certificate...
Страница 78: ...M AVTMPFL22M Rev 1 April 2011 68...