M
AVTMMPQSIM Rev 1 May 2017
66
DESCRIPTION
SETUP
COMMENTS
Voltage Swell Limits
262.00
Current Limits
Disabled
Sub-cycle Limit
400.00
Ratio
1.0
CT Full Scale
6000.0
Nominal Angle
0, 120, 240
Angle Deviation
2.0
Fast Transient
600.00
THD Limit
5.00
Timed Waveform Capture
Enabled at 1 Minute
This is not a normal interval
used in the real world. This
is just a short interval to
accumulate data quickly for
demonstration.
Timed Capture Duration
6 Cycles
Exceedance Capture Pre-
Triggers
9
Exceedance Capture Post
Triggers
20
THD / Harmonics
Enabled
THD / Harmonic Interval
3 Seconds
This is not a normal interval
used in the real world. This
is just a short interval to
accumulate data quickly for
demonstration.
Voltage for RVC and
Mains Signaling
Auto
Declared Voltage
NA
Memory Mode
Stop When Full
Default Frequency
50
Mains Signaling
Disabled
99 Washington Street
Melrose, MA 02176
Phone 781-665-1400
Toll Free 1-800-517-8431
Visit us at www.TestEquipmentDepot.com