AVTMMPQSIM Rev 1 May 2017
43
ADDENDUM C
SAMPLE POWER QUALITY TRAINING
This Addendum is meant to offer a possible sample training to illustrate power quality
phenomenon.
1.
Initial PQ Simulator configuration
Configure the PQ Simulator as shown in
Section 7 Initial Settings
of this manual.
2.
Program the MPQ Analyzer
Programming the MPQ Analyzer for 115V input from simulator.
Voltage sag / dip limit
108.00
Voltage swell limit
132.00
Fast transient limit
400.00
THD limit
5.0
RMS storage interval
3 Seconds
See
Addendum 4 Complete 115V MPQ Setup File
for full setup file.
Programming the MPQ Analyzer for 230V input from simulator.
Voltage sag / dip limit
207.00
Voltage swell limit
262.00
Fast transient limit
600.00
THD limit
5.0
RMS storage interval
3 Seconds
See
Addendum 5 Complete 230V MPQ Setup File
for full setup file.
Connect the unit to the simulator as shown in Section 6
Product Installation
of this
manual.
Содержание MPQSIM