AVTMMPQSIM Rev 1 May 2017
65
ADDENDUM E
COMPLETE 230V MPQ SETUP FILE
DESCRIPTION
SETUP
COMMENTS
Power Wiring Connection
4 Wire Wye 3 Wattmeter
Enable Power
Calculations
Enabled
Demand Interval
5 Minute
This is not a normal interval
used in the real world. This
is just a short interval to
accumulate data quickly for
demonstration.
Enable RMS Recording
Enabled
Record
MIN, MAX, RMS
RMS Storage Interval
3 Seconds
This is not a normal interval
used in the real world. This
is just a short interval to
accumulate data quickly for
demonstration.
Enable IEC Unbalance
Recording
Enabled
Clock Hour Orientation
Enabled
Enable IEC Flicker
Recording
Not Enabled
This test takes some time to
perform and is not suitable
for a short demonstration.
Enable Frequency
Recording
Enabled
Enable Instant Flicker
Recording
Disabled
This is a special test used
for troubleshooting of flicker
failures and factory testing.
Hysteresis Value
2%
Standard value
Enable Sub-cycle event
capture
Enabled
Enable Phase Events
Enabled
Enable RVC Events
Disabled
Rotation
ACB
Voltage Sag / Dip Limits
207.00
Содержание MPQSIM
Страница 2: ......
Страница 3: ...MPQSIM User Manual...
Страница 8: ...M AVTMMPQSIM Rev 1 May 2017 2 M...
Страница 10: ...M AVTMMPQSIM Rev 1 May 2017 4 M...
Страница 20: ...M AVTMMPQSIM Rev 1 May 2017 14 M...
Страница 36: ...M AVTMMPQSIM Rev 1 May 2017 30 M...
Страница 37: ...AVTMMPQSIM Rev 1 May 2017 31 9 SPARE PARTS PART NO DESCRIPTION 2008 124 Current Cable 90017 548 AC Adapter...
Страница 38: ...M AVTMMPQSIM Rev 1 May 2017 32 M...