OPERATION

Measurements - General
Live - Earth 
loop impedance measurement can be made via installation
sockets using the plug terminated test lead, or at any other convenient
point on the installation using the optional  dual lead test set. The optional
dual lead test can also be used to carry out Live - Neutral loop impedance
measurement. 

Switching ‘On’and testing
Turning the rotary switch will activate the instrument. Alternatively, pressing
the  Retest button will re-activate the instrument after ‘Auto shut off’. The
activated instrument will momentarily display all screen segments, followed
by the  software version number. When connected to mains voltage of the
correct polarity the L - PE ‘neon’indicator activates  and supply voltage
is  displayed. If out of voltage range, VOL flashes alternately with the actual
measured voltage.The word ‘ null’ is then displayed as an  11 second self
calibration check (‘Auto’ range only) is completed. The instrument then
proceeds to automatically take a measurement. Two pin plug terminated
test leads should be reversed if only the N - PE voltage indicator is
activated. Repeat  measurements can be made either by disconnecting
and then reconnecting the instrument (e.g. when using test probes) or by
pressing the Retest button. When operational, the 

LT7

will carry out a self

calibration every 5 minutes. 

Circuit condition Indication

Testing is inhibited if:
1 )

Phase and Neutral supply connections are reversed. (N - PE ‘ n e o n ’ activated). 

2)

Neutral - Earth voltage >50 V when performing a 3 wire test (L-PE
and N - PE ‘neons’activated).

3)

Electrical ‘noise’exceeds rejection level on low current range. 

(

displayed).

4)

Voltage is out of range. Flashing ‘VOL’ and actual Voltage
displayed.

5)

Supply frequency out of limits (flashing ‘HZ’ displayed).

6 )

Thermal protection device operates on h i g h current range ( and 
d i s p l a y e d ) .

Low Current (Auto) measurement (0,1   or 1   resolution)
This mode measures Live to Earth loop impedance via installation
sockets. Live to Earth or Live to Neutral loop impedance can also be
measured  using  the  optional  dual  lead  test  set.  The  measurement
sequence takes  11 seconds. Residual Current Devices (R.C.D.s) 

30mA

will not trip.

LT7

is supplied as standard with a display resolution of 0,1 

. In areas of

exceptional electrical noise, and where improved repeatability may be
desired, it is possible to change the display resolution to 1 

 in the

following manner:-
1)

Turn rotary switch to the ‘ OFF’ position.

2)

Press and hold the Retest push button whilst turning the rotary
selector switch to any other position.

3)

Still holding the Retest button, the display will cycle between 1 

 and

0,1 

 resolution.

4)

Release the Retest button when the desired resolution is displayed. 

To operate 

LT7

:-

1) 

Turn rotary switch to ‘Auto’.

2)

Connect 

LT7

by mains cord, or using the dual test lead firmly 

connect red test probe to  Live and the black test probe to Neutral 
or to Protective Earth (ground). Mains (line) voltage is displayed.

3)

Test progress is indicated by a sequential display of vertical bars. 

Refer to Safety Warnings before using the instrument

Содержание LT7

Страница 1: ...fied before carrying out an earth fault loop impedance test Exposed metalwork of an installation or equipment under test must not be touched LT7 must not be connected across two phases of a 3 phase su...

Страница 2: ...short circuit current A special range is provided to carry out loop measurement on installations protected by Residual Current Devices 30mAwithout causing the breaker to trip out The resolution in thi...

Страница 3: ...s are reversed N PE neon activated 2 Neutral Earth voltage 50 V when performing a 3 wire test L PE and N PE neons activated 3 Electrical noise exceeds rejection level on low current range displayed 4...

Страница 4: ...t probe to Protective Earth ground or to Neutral Mains line voltage is displayed 3 Test progress is indicated by a sequential display of vertical bars 4 PSCC value displayed directly in kA 20kA displa...

Страница 5: ...ted instrument with a clean cloth dampened with soapy water or Isopropyl Alcohol IPA ACCESSORIES Supplied Part number User Guide 6172 087 Power cord test lead with 3 pin plug to BS1363 A 6231 601 or P...

Страница 6: ...8579 Fax 44 0 1304 207342 Fax 1 610 676 8625 or an approved repair company Returning an Instrument for Repair If returning an instrument to the manufacturer for repair it should be sent freight pre p...

Страница 7: ...indicateur de tension N PE Neutre Terre est activ Des mesures r p t es peuvent tre effectu es soit en d connectant puis en reconnectant l instrument par exemple lors de l utilisation de sondes de tes...

Страница 8: ...e l interrupteur rotatif sur 20 2 Brancher le LT7 ou connecter fermementle capteur de test rouge sur Phase et le capteur de test noir sur Neutre ou sur Terre de Protection terre La tension du secteur...

Страница 9: ...smessungen k nnen entweder durch Abnehmen und Wiederanschlie en des Instruments an die Installation z B wenn Pr fsonden verwendet werden oder durch Bet tigen des Wiederholungspr fknopfes Retest durchg...

Страница 10: ...7 ein oder schlie en die rote Pr fsonde fest an Spannungsf hrend und die schwarze Pr fsonde an die Schutzerdung Erde oder Neutral an Netzspannung Leitung wird angezeigt 3 Der Pr fverlauf wird durch di...

Страница 11: ...camente una medici n Los cables de prueba terminados en un enchufe de dos patillas deber n invertirse si s lo se activa el indicador de tensi n N PE Pueden realizarse mediciones repetidas bien sea des...

Страница 12: ...o conectar firmemente la sonda de prueba roja al Conductor con corriente y la sonda de prueba negra al Neutro o a Tierra Protectora masa Se visualiza la tensi n de la red l nea 3 La marcha de la prue...

Отзывы: