42
MOM2
ZP-BD03E
BD0333JE
8 SPECIFICATIONS
8
S
pecifications
SPECIFICATIONS
Specifications are valid at fully charged batteries and an ambient
temperature of +25°C, (77°F). Specifications are subject to change
without notice.
Environment
Application field
For use in high-voltage substations
and industrial environments.
Temperature
Operation
-20ºC to +50°C (-4°F to +122°F) *
)
Storage
-40ºC to +70ºC (-40°F to +158°F)
Relative humidity %RH
5%-95%, non condensing
Pollution degree
2
Shock
IEC 60068-2-27
Vibration
IEC 60068-2-6
Transport
ISTA 2A
Flammability class
V0
*) Battery operation temperature 0ºC to +50° (32°F to +122°F)
Battery charging tempe10ºC to +40° (50°F to +104°F)
CE-marking
EMC
2014/30/EU
LVD
2014/35/EU
RoHS
2011/65/EU
General
Battery power
Five AA (HR6) 2700 mAh NiMH cells
Recharge time
< 12 h
Typical recharge time
at 25
°C
3 h
Battery charger
Mains voltage
100 - 250 V AC, 50 / 60 Hz
Power consumption
24 W
Protection
Against wrong battery type, low/high
temperature.
Real time clock battery
life
≥10 years
Audible feedback
Different buzzer sounds
User presets
3
Field calibration
yes
Encapsulation
IP54
Dimensions
Instrument (excl.
binding posts)
217 x 104 x 72 mm
8.5 x 4.1 x 2.8 in.
Carrying case
395 x 300 x 190 mm
15.6 x 11.8 x 7.5 in.
Weight
1.0 kg (2.2 lbs) instrument only
5.0 kg (11 lbs) with accessories and
carrying case
Measurement section
Minimum current
guarantee
Selectable 50 A / 100 A
Valid at resistance ≤2mΩ
Pass / Fail
Settable from 1 µΩ to 1999 mΩ
Number of
measurements on fully
charged batteries
typ. 2200 at I min = 50 A and 0.1 s
typ. 800 at I min = 100 A and 0.1 s
Interference
suppression
yes
Range
0 - 1000 mΩ
Range selection
Auto
Resolution
0 – 999 µΩ
1 µΩ
1.0 – 9.99 mΩ
0.01 mΩ
10.0 – 99.9 mΩ
0.1 mΩ
100 – 1000 mΩ
1 mΩ
Inaccuracy
0 – 1999 µΩ
±1 % of reading ±1 digit
2 – 500 mΩ
±2 % of reading ±1 digit
500 – 1000 mΩ
±4 % of reading ±1 digit
O / –
Range
> 100 A DC (R < 2 mΩ)
Output voltage (max)
2.5 V DC
Generation duration
Selectable: 0.1 s, 0.6 s, 3 s
Recovery time at I min set to 100 A
and load 100 μΩ
Generation time
Max
Typ
0.1 s
10 s
8 s
0.6 s
20 s
16 s
3 s
130 s
100 s
Inputs
SENSE + / –
Connector
4 mm banana jack
Voltage
±3 V DC
Trigger input
Threshold 8 V DC
DC IN
12 – 24 V DC, 2 A max
Logger
Logger, Data
Label. Timestamp, I max, I min, I Limit,
Resistance, Meas.time, P/F limit
Labeling schemes
Circuit breaker oriented or running
numbers
Capacity
104 measurements
Wireless communication
PC communication
Bluetooth
www.
.com
1.800.561.8187