www.megger.com
AVO®830 and AVO®835
24
Measurements
To Measure Conductance
1. Make sure that:
•
The circuit power is disconnected
•
All high-voltage capacitors are discharged
Note:
If a live circuit is detected the instrument will sound a pulsed audible beep and
V OL
(flashing) shows on
the display.
2. Set-up the instrument as shown in Fig 5.
•
Set the Function Dial to
Ω
•
Press
MODE
twice to select
n S
•
Red test lead: V terminal
•
Black test lead: COM terminal
3. Connect the test probe tips to the circuit under test.
The display shows
0.00 nS
until the circuit is detected and shows the appropriate conductance when the circuit is
detected.
Capacitance Measurement
Hz
CAT III 1000V
CAT IV 600V
COM
FUSED
100mA
V
10A
Ω
AVO835
RANGE
MODE
MIN MAX
AVG
REL %
REL
Low Z
HOLD/Auto
ac+dc
APO
Lo
Hz
Hz
°F
Hz
V
Hi
A
mA
OFF
OFF
Ω
°C
+
+
+
+
+
+
+
+
+
Fig 6: Capacitance Measurement Set-up
Caution:
To avoid possible damage to the instrument or to the equipment under test, make sure that
the circuit power is disconnected and all high-voltage capacitors are discharged before capacitance is
measured. Use the DC voltage function to confirm that the capacitor is discharged.
To Measure Capacitance
1. Make sure that:
•
The circuit power is disconnected
Содержание AVO 830
Страница 1: ...AVO 830 and AVO 835 True RMS Digital Multi Meter User Guide ...
Страница 2: ......
Страница 44: ...www megger com AVO 830 and AVO 835 44 ...
Страница 45: ...www megger com AVO 830 and AVO 835 45 ...
Страница 46: ...www megger com AVO 830 and AVO 835 46 ...
Страница 47: ...www megger com AVO 830 and AVO 835 47 ...