10
11
Setting voltage
point back to
battery mode when
selecting “SBU
priority” or “Solar
first” in program 07
Available options in
IVR-2400MPPT
model:
Battery fully
charged
24V
24.5V
25V
25.5V
26V
26.5V
27V (default)
27.5V
28V
12
Charger source
priority:
To configure
charger source
priority
If this inverter/charger is working in Line, Standby or Fault mode, charger
source can be programmed as below:
Utility first
Utility will charge battery as first priority.
Solar energy will charge battery only when utility power
is not available.
Solar first
Solar energy will charge battery as first priority.
Utility will charge battery only when solar energy is not
available.
Solar and utility
Solar energy and utility will charge battery at the same
time.
Only Solar
Solar energy will be the only charger source no matter
utility is available or not.
If this inverter/charger is working in Battery mode, only solar energy can
charge battery. Solar energy will charge battery if it's available and sufficient.
13
Auto return to
default display
screen
Return to default
display screen
(default)
If selected, no matter how users switch display screen,
it will automatically return to default display screen
(Input voltage /output voltage) after no button is
pressed for 1 minute.
Stay at latest screen
If selected, the display screen will stay at latest screen
user finally switches.
14
Beeps while primary
source is
interrupted
Alarm on(default)
Alarm off