2
INSTALLATION
2.1
Safety Guidelines
WARNING
The following installation instructions are intended for qualified personnel only. To avoid
the risk of electrical shock and personal injury, do not perform additional tasks not stated
in this procedure unless you are qualified to do so.
Always adhere to the following safety guidelines:
•
Only qualified personnel or
licensed electricians
should handle the installation. Input voltages to
the DTS SMX can be hazardous.
•
Follow all applicable local and national electric codes.
•
Verify input voltage and current are within thresholds for the specific DTS SMX model. (See Product
Specification on page 4)
•
Use only UL or ETL listed current transformers.
ONLY USE CURRENT TRANSFORMERS THAT
ARE SPECIFIED BY THE MODEL OF DTS SMX. USE OF ANY OTHER CURRENT
TRANSFORMER OTHER THAN THE ONE SPECIFIED BY THE DTS MODEL CAN RESULT IN
PERMANENT DAMAGE TO THE DTS SMX.
•
Ensure that the in-line fuses located on the main board of the DTS SMX are fitted and securely
fastened.
•
Avoid any electrostatic discharge while dealing with any of the internal components of the DTS SMX
by first touching a grounded structure prior to handling internal components.
•
Before applying power make sure that all current transformer and voltage connections are securely
connected to the main board of the DTS SMX.
•
If the DTS SMX is installed incorrectly any built in safety features may no longer be functional.
•
Before opening the DTS SMX ensure that all power running to the DTS SMX is removed.
•
Under normal operation the DTS SMX should be secured with a
user supplied lock
to ensure there
is no unauthorized access to the live connections in the enclosure.