1.2
Document Conventions
SYMBOLS
ATTENTION
–
PLEASE CONSULT THE
INSTALLATION MANUAL
WARNING
–
RISK OF ELECTRICAL
SHOCK
1.3
Product Specification
WARNING
Verify that the model of DTS SMX that was shipped is used
for the correct installation. Failure to use the correct
CT’s
or connecting too high a voltage can result in permanent
damage to the DTS Meter.
DTS SMX -
A
x-xx-x-
F
-xx
1.3.1
Current Inputs
Current
Inputs
Value
Description
Notes
A
3
333mV CT
Any 333mV CT is acceptable
5
1 Amp or 5 Amp CT
User supplied shorting blocks
are
r
equired with these CT’s
9
Unburdened CT
Only use the CT’s that came with the unit
Note:
Make sure that the DIP Switch settings on the DTS SMX are set to the correct CT
Primary. See section 5.3.1 on page 20. If all Dip Switch se
ttings on the DTS SMX are “off”
please contact Measurlogic.
1.3.2
Service Type
Service Type
Value Description
Neutral Required
Neutral Optional
F
N
(1P 2W, 1P 3W, 3P 4W) 120
–
277Vac L
–
N
●
2
(3P 3/4W) 208
–
240 Vac L
–
L
●
4
(3P 3/4W) 480 Vac L
–
L
●
6
(3P 4W) 600Vac L
–
L
●