4.1
Voltage Fuses
The DTS SMX is fitted with three in-line fuses. See section 4.1.2 for the replacement procedure.
4.1.1
Voltage Fuse Specifications
The voltage inputs are fitted with fusing appropriate for the model of meter ordered (represented by F1-F3 in the
diagrams below) and are rated at 2A 600Vac for 480V systems or 2A 250V for 208V systems.
4.1.2
Fuse Location and Replacement
•
Remove the plastic safety cover from the fuses by
unscrewing the plastic nuts located in figure 4.1a
•
Remove the blown fuse from its holding clip and replace with
the new fuse.
•
DO NOT
wedge a flat head screwdriver or other type of
device into the clip to remove the fuse. This can damage
the fuse clip.
•
Replace the plastic safety cover and nuts
Description:
1
3/8” or 1 1/2” Long 2A Fast
-acting
type fuse
Manufacturer:
Littlefuse or equivalent
Manufacturer Part
Number:
BLS 2 or equivalent
Nominal Voltage (V):
250Vac or 600Vac (Service
Dependent)
Current Rating (A):
2
Figure 4.1a