2)
On a separate white sticker on the display PCB or inside the door of the enclosure (MLB0010-B).
The
4 switch positions
SW2.3, SW2.4, SW2.5 and SW2.6 are used to set the CT Primary (16 options).
Remember that if present, the CT Table shown on a printed white sticker ALWAYS take precedence.
Switch 2.3-2.6 - CT Primary Selection
SW
2.3
SW
2.4
SW
2.5
SW
2.6
CT Primary
OFF
OFF
OFF
OFF
CONFIGURABLE
OFF
OFF
OFF
ON
100
OFF
OFF
ON
OFF
150
OFF
OFF
ON
ON
200
OFF
ON
OFF
OFF
300
OFF
ON
OFF
ON
400
OFF
ON
ON
OFF
450
OFF
ON
ON
ON
500
ON
OFF
OFF
OFF
600
ON
OFF
OFF
ON
750
ON
OFF
ON
OFF
800
ON
OFF
ON
ON
900
ON
ON
OFF
OFF
1000
ON
ON
OFF
ON
1200
ON
ON
ON
OFF
1500
ON
ON
ON
ON
1600
ATTENTION
If Rogowski Coil CTs are being used with the meter then
All the CT Primary switches MUST be left in the OFF position.
DO NOT change the
“CT Primary”
settings on Switch 2.