©Measurlogic

 

Page 3

 

MQ0051-20F 

 

7334 S. Alton Way, Centennial CO 80112 

Tel: 877-777-6567 Tel: 303-805-5252 Fax: 425-799-4780 

e-mail[email protected] 

web: www.measurlogic.com

 

 

 

1

 

PRODUCT OVERVIEW 

 

 

The one revenue grade meter for all applications.

 

 

Your new DTS SMX energy sub-meter is one of the most versatile meters available on the market. The DTS SMX 
can operate in any environment, requires no external power source to operate, and works with all UL or ETL 
listed 333mV and 1A/5A current transformers (model dependent).  

 
For ease of installation, the DTS SMX is designed to mount on any surface and comes standard with a bright 

backlit LCD display.  
 
Some of the exciting features provided with the DTS SMX are  
 

 

field user-configurable CT ranges 
 

 

Fused Voltage Terminals 

 

 

Auto-topology Phase Detection and on-board CT Algorithms for automatic correction of reversed field 
mounted CTs 

 
For remote configurability, your DTS SMX comes with our freely downloadable 

DTS Config

  software tool 

 

The DTS SMX provides you very accurate data acquisition and is certified to ANSI C12.20 Class 0.5 Revenue 
Grade. Whether communicating via an RS-485 or Ethernet connection, the DTS SMX supports most accepted 

protocols, including Modbus RTU, Modbus TCP, BACnet MS/TP, BACnet/IP, SNMP, DNP 3.00 or LonWorks.  
 
Also, if in the future, you decide to integrate renewable energy sources, the DTS SMX will conveniently operate 

as a Bi-Directional 

NET

 meter. Easily integrates with Building Automation Systems and Energy Monitoring 

Software.  

 
Designed and Manufactured in the USA and complies with the Buy American Provisions of ARRA Section 1605.  

 
 

Thank you for choosing Measurlogic and a meter from the DTS Family. 

 
 

1.1

 

Supplied Items 

 

Check that the meter and equipment matches your order specifications and has not been damaged during 
shipping.  Verify that the following item(s) match with the corresponding model from the data sheet: 
 

 

Installation Guide  

 

 

DTS SMX power & energy meter 

 

 

3x Pre-installed fuses for line voltage inputs 
 

 

6-Pin green pluggable screw terminal connector for digital inputs and/or outputs (

if applicable

 

 

3-Pin green pluggable screw terminal connector for serial communications wiring (

if applicable

 

 

3-Pin green pluggable screw terminal connector for DC auxiliary power input wiring (

if applicable

)

Содержание DTS SMX

Страница 1: ...Q0051 20F 7334 S Alton Way Centennial CO 80112 Tel 877 777 6567 Tel 303 805 5252 Fax 425 799 4780 e mail info measurlogic com web www measurlogic com DTS SMX Surface mounting outdoor rated Revenue grade electrical sub meter ...

Страница 2: ... the CTs from Multiple Loads to the 333mV CT Daughter Board 13 3 4 5 AMP SECONDARY CT DAUGHTER BOARD 14 3 5 DTS SMX DIGITAL I O CIRCUIT OPTIONAL 15 3 5 1 Digital Outputs 15 3 5 2 Digital Inputs 15 4 MAINTENANCE AND SERVICE 15 4 1 VOLTAGE FUSES 16 4 1 1 Voltage Fuse Specifications 16 4 1 2 Fuse Location and Replacement 16 4 2 BATTERY 17 4 2 1 Battery Specifications 17 4 2 2 Battery Location and Pla...

Страница 3: ...d is certified to ANSI C12 20 Class 0 5 Revenue Grade Whether communicating via an RS 485 or Ethernet connection the DTS SMX supports most accepted protocols including Modbus RTU Modbus TCP BACnet MS TP BACnet IP SNMP DNP 3 00 or LonWorks Also if in the future you decide to integrate renewable energy sources the DTS SMX will conveniently operate as a Bi Directional NET meter Easily integrates with...

Страница 4: ...t in permanent damage to the DTS Meter DTS SMX Ax xx x F xx 1 3 1 Current Inputs Current Inputs Value Description Notes A 3 333mV CT Any 333mV CT is acceptable 5 1 Amp or 5 Amp CT User supplied shorting blocks are required with these CT s 9 Unburdened CT Only use the CT s that came with the unit Note Make sure that the DIP Switch settings on the DTS SMX are set to the correct CT Primary See sectio...

Страница 5: ...scribe how to interact with each of the features of the DTS SMX Note that not all features listed here are included with every DTS SMX Please refer to the model number to determine which features are included Voltage and CT connection Section 3 2 Page 10 Digital I O Section 3 5 Page 15 Serial Communications Section 5 1 Page 19 Ethernet Communications Section 5 2 Page 20 DIP Switch Setting Section ...

Страница 6: ...e only UL or ETL listed current transformers ONLY USE CURRENT TRANSFORMERS THAT ARE SPECIFIED BY THE MODEL OF DTS SMX USE OF ANY OTHER CURRENT TRANSFORMER OTHER THAN THE ONE SPECIFIED BY THE DTS MODEL CAN RESULT IN PERMANENT DAMAGE TO THE DTS SMX Ensure that the in line fuses located on the main board of the DTS SMX are fitted and securely fastened Avoid any electrostatic discharge while dealing w...

Страница 7: ...ENTION Make sure to follow the following mounting requirements and guidelines when mounting the DTS SMX When mounting the DTS SMX make sure to follow these guidelines Mount the DTS SMX as close as possible to the electrical panel being monitored Make sure there is at least 4 of space between the latch of the lid and any obstruction Make sure that the lid can fully open and close without any interf...

Страница 8: ...ical panel Only UL or ETL rated conduits and glands should be used Only UL or ETL Current Transformers should be used A spade or ring lug termination is recommended for optimally secure voltage and current connections A UL or ETL certified circuit breaker or fused disconnect must be installed within easy reach of the DTS SMX The circuit breaker or fused disconnect must be marked as the disconnecti...

Страница 9: ... easy to use voltage connection points and in line fuse connections ATTENTION Voltage connections should come from the same lines that the CT s will be connected to In line fuse clips See section 4 1 for fuse details Load Source A N B C Use appropriate breaker and wire for voltage connections See section 2 3 for reference If present terminate GROUND here If present terminate NEUTRAL here Silver Vo...

Страница 10: ... two PTs WARNING Extreme care should be exercised with medium voltage applications The connection diagram shown below is a simplified connection diagram only Connect the PTs strictly according to national code and as recommended by the PT manufacturer In line fuse clips See section 4 1 for fuse details Load Source A N B C Primary fusing shown is illustrative only Actual fusing is normally an integ...

Страница 11: ...CT ATTENTION Make sure that your model of DTS SMX is approved for the following wiring guidelines Note CTs should be connected to the same panel as the voltage connections 3 3 1 Single Phase 2 3 Wire Example 3 3 2 3 Phase with Optional Neutral Model Dependent Breaker Load A N B C Source Make sure CT arrows point TOWARDS the LOAD Load Source Breaker A N B C Make sure CT arrows point TOWARDS the LOA...

Страница 12: ...V output Rogowski CTs cannot be connected in parallel All CT sensors must be of the same manufacturer model number and current rating A full set of CT sensors must be used for each load The pair of wires from the CT sensor to the screw terminal must be twisted All CT sensors must be terminated at the screw terminal A maximum of 3 loads can be monitored at once Contact Measurlogic if more than 3 lo...

Страница 13: ...an easier way to connect up to three 3 CTs per phase to the DTS SMX meter The technical details in Section 3 3 3 also apply to this section ATTENTION Do NOT connect to the silver screws Terminate on the GREEN shorting connectors ONLY The silver screws must NOT be removed See Section 3 3 3 for CT Primary Settings Note CTs should be connected to the same panel as the voltage connections A B C A B C ...

Страница 14: ...n board pre installed as seen in the diagram below ATTENTION Do NOT connect to the silver screws Terminate on the GREEN shorting connectors ONLY The silver screws must NOT be removed Note CTs should be connected to the same panel as the voltage connections Feed WHITE Wire through CTs on Main Board Terminate BLACK and WHITE wires on GREEN connectors Do NOT remove or connect wires to SILVER screws L...

Страница 15: ...utputs if fitted may be used for pulsing or threshold triggers Suitable wire gauge for digital outputs is 18 22 AWG For longer distances 100ft use 18 AWG 3 5 2 Digital Inputs The DTS digital inputs on Ch1 and Ch2 marked DIGITAL I O on the silkscreen accept dry contacts or NPN open collector inputs and can be configured using DTS Config as level status inputs and or linked to a General Counter for ...

Страница 16: ...d at 2A 600Vac for 480V systems or 2A 250V for 208V systems 4 1 2 Fuse Location and Replacement Remove the plastic safety cover from the fuses by unscrewing the plastic nuts located in figure 4 1a Remove the blown fuse from its holding clip and replace with the new fuse DO NOT wedge a flat head screwdriver or other type of device into the clip to remove the fuse This can damage the fuse clip Repla...

Страница 17: ...iption Lithium Battery Non Rechargeable Primary 3V Coin 20 0mm Manufacturer Panasonic or equivalent Manufacturer Part Number CR2032 Nominal Voltage V 3 Nominal Capacity mAH 225 Continuous Standard Load mA 0 2 Operating Temperature C 30 60 4 2 2 Battery Location and Placement Figure 4 2b Battery Orientation The coin cell battery is located in the upper left on the main board of the DTS SMX as shown...

Страница 18: ...ardous material and hazardous waste transportation and disposal requirements Please check your local and state regulations on how to properly dispose of your lithium coin cell batteries 4 2 4 First Aid If you get electrolyte in your eyes flush with water for 15 minutes without rubbing and immediately contact a physician If you get electrolyte on your skin wash the area immediately with soap and wa...

Страница 19: ... RS 485 communications bus the meters should be daisy chained together Do not connect the meters in a STAR RING or other wiring topology that is not a daisy chained BUS Modbus RTU Default Communications Settings Unless otherwise stated through correspondence or specified on the label of the DTS SMX unit default communications parameters for Modbus RTU over RS 485 2 wire communications are Modbus A...

Страница 20: ...its Quick Start Guide specific protocol documentation or MIB files for SNMP devices 5 3 Configuring the DIP Switches Communications Settings CT Ratings and Other Options The DTS SMX has two 8 way DIP switches that provide the user a simple and flexible interface for configuration The right hand side block of DIP switches SW1 are used to set up the device s address and baud rate for RS 485 interfac...

Страница 21: ...terface instead Switch 2 1 2 2 Digital Output Mapping SW 2 1 SW 2 2 Mapping OFF OFF CONFIGURABLE OFF ON 1 pulse 0 1kWh ON OFF 1 pulse 0 5kWh ON ON 1 pulse 1 0kWh Default Positions 1 2 dictate the mappings for Digital Output 3 The table below represents the different settings If the switches are both set to the OFF position the digital output will be configurable through the communications interfac...

Страница 22: ...play PCB itself MLB0010 C 1 Table printed on the silkscreen on the display PCB itself MLB0010 B The 4 switch positions SW2 3 SW2 4 SW2 5 and SW2 6 are used to set the CT Primary 16 options Switch 2 3 2 6 CT Primary Selection SW 2 3 SW 2 4 SW 2 5 SW 2 6 CT Primary OFF OFF OFF OFF CONFIGURABLE OFF OFF OFF ON 5 OFF OFF ON OFF 20 OFF OFF ON ON 50 OFF ON OFF OFF 100 OFF ON OFF ON 200 OFF ON ON OFF 400 ...

Страница 23: ...n on a printed white sticker ALWAYS take precedence Switch 2 3 2 6 CT Primary Selection SW 2 3 SW 2 4 SW 2 5 SW 2 6 CT Primary OFF OFF OFF OFF CONFIGURABLE OFF OFF OFF ON 100 OFF OFF ON OFF 150 OFF OFF ON ON 200 OFF ON OFF OFF 300 OFF ON OFF ON 400 OFF ON ON OFF 450 OFF ON ON ON 500 ON OFF OFF OFF 600 ON OFF OFF ON 750 ON OFF ON OFF 800 ON OFF ON ON 900 ON ON OFF OFF 1000 ON ON OFF ON 1200 ON ON O...

Страница 24: ... 50 OFF OFF ON ON OFF 75 OFF OFF ON ON ON 100 OFF ON OFF OFF OFF 125 OFF ON OFF OFF ON 150 OFF ON OFF ON OFF 200 OFF ON OFF ON ON 250 OFF ON ON OFF OFF 300 OFF ON ON OFF ON 400 OFF ON ON ON OFF 450 OFF ON ON ON ON 500 ON OFF OFF OFF OFF 600 ON OFF OFF OFF ON 750 ON OFF OFF ON OFF 800 ON OFF OFF ON ON 900 ON OFF ON OFF OFF 1000 ON OFF ON OFF ON 1200 ON OFF ON ON OFF 1500 ON OFF ON ON ON 1600 ON ON ...

Страница 25: ...fig is a program used to easily monitor and configure meters from the DTS family from your local PC or across the LAN Download the latest version of DTS Config from http www measurlogic com software drivers Alternatively an e mail can be sent to info measurlogic com to request the latest version of DTS Config Access the DTSConfigSetup file to begin the installation process Follow the instructions ...

Страница 26: ...ogic com web www measurlogic com The following is a typical diagram showing connections of one or more DTS SMX meters to a Master Application 7 2 DTS SMX to Server Unit 1 Unit 2 Unit X Red Wire Green Wire Gnd or Shield Black Wire 18 24 AWG 2 wire shielded cable Serial to Ethernet Converter Unit 1 Unit 2 Unit X 1 or more Server Applications ...

Отзывы: