background image

RKP-CMU1 / RKP-1U-CMU1

Instruction Manual

Содержание RKP-1U-CMU1

Страница 1: ...RKP CMU1 RKP 1U CMU1 Instruction Manual...

Страница 2: ...ors and LCD User Interface 4 2 LCD Display 4 1 Description of RKP CMU1 Front Panel 5 1 IP settings of PC 5 2 Description of RKP CUM1 Built in Web Page 5 3 Event Log page 5 4 Data Log page 5 5 TCP IP C...

Страница 3: ...Method 7 1 Installation and Settings 7 2 Test of Sending a Short Message 7 3 AT Command List for RKP CMU1 8 3 EMI Suppression Arrangement 8 4 Warranty 6 RKP CMU1 Monitoring Software 28 28 29 29 6 1 I...

Страница 4: ...stems servers etc It can be stand alone operated or integrated into a 19 inch rack Control and monitor rack power units Front panel LCD and buttons for on site service without PC USB RS 232 or Etherne...

Страница 5: ...OFF USB RS 232 Ethernet 20 90 RH non condensing 40 85 10 95 RH non condensing 10 500Hz 2G 10min 1cycle 60min each along X Y Z axes 486 6 350 8 44mm L W H 110 5K hrs min MIL HDBK 217F 25 4 4Kg 3pcs 14...

Страница 6: ...Mechanism of Single Unit Figure 2 1 41 147 5 JK1 DC IN 1 2 2 1 3 4 5 6 7 8 RY1 RY2 RY3 RY4 RS 232 Ethernet 127 CN502 TB4 SK100 CN503 JK500 Fig1 40 9 18 23 78 2 M3 L 6mm 2 M3 L 6mm 2 M3 L 6mm 40 9 78 4...

Страница 7: ...3 4 4 5 5 6 6 7 7 8 8 Ethernet Ethernet RS 232 RS 232 RY1 RY1 RY2 RY2 RY3 RY3 RY4 RY4 1 1 14 14 13 13 25 25 A A B B _ _ 8 1 1 8 JK500 JK500 TB4 TB4 SK100 SK100 CN500 CN500 CN502 CN502 CN503 CN503 2 1...

Страница 8: ...ary voltage output 4 3 5 5V referenced to GND AUX pin 15 The maximum load current is 0 3A This output has the built in Oring diodes and is not controlled by the remote ON OFF control Positive output v...

Страница 9: ...ND for D IN This signal connects to FG and isolated from V and GND AUX Data transmitting pin of RS 232 interface Not used Common for NO NC contact RS 232 common GND This signal connects to FG and isol...

Страница 10: ...operations for selection The operating conditions of the relays are shown in Table 3 3 operating data of the rack power system It has 1000 records and the interval of log is programmable from 1 to 60...

Страница 11: ...ition Table 3 5 The RKP CMU1 is equipped with all the PMBus commands that Rack Power needs This makes it easy for users to monitor manage and control their Rack Power systems by means of the LCD user...

Страница 12: ...wer user s manual READ_TEMPERATURE_1 R Word All of the PMBus data are fully digitalized The RKP CMU1 uses the data read from Rack Power units to display their operating values and control these units...

Страница 13: ...RKP CMU1 unit the restarted Rack Power will be loaded the previous set parameters by the RKP CMU1 automatically you have set will return to the initial default values alarm Take RCP 2000 48 as an exa...

Страница 14: ...Please refer to the user s manual of RCP 2000 RKP 1U and Figure 3 3 for notes on parallel operation of RKP 1Us length is 1m But if there is a need for extending the cables the maximum length should n...

Страница 15: ...tput Current 100 0A Number of PSU 10 Units PSU Current Press ENT key PSU Temperature Press ENT key Serial Number Press ENT key Manufacture Date Press ENT key Firmware Version Press ENT key Digital Inp...

Страница 16: ...een below L L x x C C D s u B V D B C a o S E S I N V 0 8 4 A M c M M M M l o n k E E E E t t l N N N N a r T T N E A T T T i U U U U g a U N N O T I E W g s S G S A R N K C E h e t t 4 3 Status Menu...

Страница 17: ...ons xx indicates PSU s number When N A is displayed on the screen it means that the number of unit is offline Once you entered this page you can choose one of the PSU s output currents to be displayed...

Страница 18: ...tal input signals H indicates a high voltage level while L indicates a low voltage level Once you enter this page you can choose one of the PSU s firmware versions to be displayed on the screen throug...

Страница 19: ...ogrammable relays x indicates that the relay is inactive In the RKP CMU1 Info section there are the serial number the manufacture date the firmware version country of Serial number of RKP CMU1 and its...

Страница 20: ...decimal separator In the Set PSU Current section you can enter PSU current setting by pressing the ENT button when this option is on the screen Increment of current adjustment is defined on the basis...

Страница 21: ...3 2 2 f o r G S M u i n R R R t S S S e 2 2 2 r 3 3 3 v 2 2 2 a l t e s S S 0 2 0 A n 0 e e 1 t t P P A r S l A y A l a r m o g U a r C m R u e r l r a e y n t 4 4 4 Programmable Relay Setting When th...

Страница 22: ...me yy indicates year mm dd indicates month day and HH MM indicates hour minute Press the ENT button to select year month day hour or minute Then use the UP DOWN buttons to choose a number Under Buzzer...

Страница 23: ...MAC Address The Clear Data Log function is used to clear all the data that Data log has stored The Change Password function is used to change a password for entering the Maintenance Menu The Load Def...

Страница 24: ...Connections option Then click the Local Area Connection Select Internet Protocol TCP IP and then click the Properties button If there are Internet Protocol Version 4 TCP IPv4 and Internet Protocol Ver...

Страница 25: ...r RJ 45 cable is not properly connected or the IP address you have set is incorrect 4 Check if it is working correctly by clicking the Support If the addresses presented as you typed it is successfull...

Страница 26: ...ble relays the information of RKP CMU1 PSU status and numbers of online units 5 2 Description of RKP CUM1 Built in Web Page 5 2 1 How to open the website Connect your PC to the RKP CMU1 then open a bl...

Страница 27: ...meanwell small letters in both the User name and Password boxes to enter this page as shown below This user name and password cannot be changed 5 2 3 PSU Status Page The PSU Status page displays the o...

Страница 28: ...he Bus voltage PSU current you set is not within the adjustable range it will become invalid Make sure the parameters that you type in are not over or less than the range as below Adjustable range of...

Страница 29: ...tus bar under its number Green indicates PSU ON Red indicates PUS OFF and N A indicates unconnected If you double click a status bar displayed green it will shift to red whereas if the status bar you...

Страница 30: ...dition condition of digital input signal output voltage total output current each PSU s currents and time The DataLog page displays 10 groups of data in one page and pages can be selected by the scrol...

Страница 31: ...ss parameters System requirements 6 1 Installation 1 Windows XP Windows Vista or Windows 7 operating system 2 AMD or Intel Pentium 133MHz or better based computer 3 USB 1 1 or higher 4 RKP CMU1 monito...

Страница 32: ...ered on and ready 3 Verify your interface settings are correct Refer to the LCD user interface section 4 4 6 6 3 1 Comm Setup Page Once this software is running there are some settings that must be do...

Страница 33: ...ssful Connection failed Make sure the interface cable is properly connected between your PC and the RKP CMU1 and make sure the parameters you set are correct 6 3 2 CMU Status Page The CMU Status page...

Страница 34: ...If the Bus voltage PSU current you set is not within the adjustable range it will become invalid Make sure the parameters that you type in are not over or less than the range as below After settings...

Страница 35: ...one by selecting the scroll down list ON green indicates PSU ON OFF red indicates PSU OFF and N A orange indicates unconnected Once you have chosen a PSU you can click the ON or OFF buttons to turn it...

Страница 36: ...ored data is over its capacity it will overwrite the previous data from the first record The contents that Event Log stores include time type of alarm and which PSU it is If you would like to check th...

Страница 37: ...previous data from the first record The contents that Data Log stores include AC voltage relay condition condition of digital input signal output voltage total output current each PSU s currents and t...

Страница 38: ...AC input can be selected by the scroll down list 6 3 7 TCP IP GSM Page This page can be split into 2 parts One is for displaying the information of TCP IP including MAC address IP address subnet mask...

Страница 39: ...TM Sierra Wireless AirLink Programmable Modems http www sierrawireless com productsandservices AirLink Programmable_Modems aspx your GSM modem and the RKP CMU1 Also make sure the baud rate of the GSM...

Страница 40: ...Set Text Mode Parameters AT CMGF Preferred Message Format AT CMGS Send Message 2 Unplug the power of the RCP 2000 3 In this case there is a PMBus Error alarm that will occur Then you should receive a...

Страница 41: ...units Refer to Figure 3 3 Wire up your interface cable USB RS232 programmable relays and digital input signals depending on your application Apply a 12 15 VDC to the SK100 port on the rear of the RKP...

Страница 42: ...t signals depending on your application Apply a 12 15 VDC to the SK100 port on the rear of the RKP CMU1 in order to power on RKP CMU1 Figure 8 1 System assembly diagram of RCP series 8 2 8 2 Mounting...

Страница 43: ...as close as possible to the Ethernet connector JK1 to reduce EMI radiation interference There are TDK ZCAT2032 0930 NEC ESD SR 160 and EROCORE FH 28 9 16 available for that purpose to the AC inlet to...

Отзывы: