90
2.2 Power on and let the air conditioner
operate for cooling. Check operation status
of drainage pump, and then connect the
plug of water level switch, check the
operation sound of water pump and
observe whether the water can discharge
through the transparent hard pipe at
drainage outlet. (In light of the length of
drainage pipe, water shall be discharged
about 1 minute delayed)
2.3 Stop the operation of air conditioner, power
off the power supply and put the cover of
water test hole back to the original place.
a. After stopped the air conditioner 3 minutes,
check whether there is anything abnormal.
If drainage pipes have not been distributed
properly, over back-flow water shall cause
the
flashing
of
alarm
indicator
at
remote-controlled receiving board and
even water shall run over the water
collector.
b. Continuously infusing water until water
level alarmed, check whether the drainage
pump could discharge water at once. If
water level does not decline under warning
water level 3 minutes later, it shall cause
shutdown of unit. When this situation
happens, the normal startup only can be
recovered by turning down power supply
and eliminating accumulated water.
Note:
Drain plug at the main water-containing
plate is used for eliminating accumulated water
in water-containing plate when maintaining air
conditioner fault. During normal operation, the
plug shall be filled in to prevent leakage.
12.5.4
Insulation work of drainage pipe
Refer the introduction to the insulation
engineering parts.
Vacuum Drying and Leakage Checking
12.6.1
Purpose of vacuum drying
Eliminating moisture in system to prevent
the phenomena of ice-blockage and copper
oxidation.
Ice-blockage
shall
cause
abnormal
operation of system, while copper oxide
shall damage compressor.
Eliminating the non-condensable gas (air)
in system to prevent the components
oxidizing, pressure fluctuation and bad heat
exchange during the operation of system.
12.6.2
Selection of vacuum pump
The ultimate vacuum degree of vacuum
pump shall be -756mmHg or above.
Precision of vacuum pump shall reach
0.02mmHg or above.
12.6.3
Operation procedure for vacuum
drying
Due to different construction environment, two
kinds of vacuum drying ways could be chosen,
Содержание CCA3U-09HRFN1-MC
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Units ...
Страница 9: ...6 A5 Duct Units A6 Duct Units ...
Страница 10: ...7 Console Units ...
Страница 11: ...8 Ceiling floor Units ...
Страница 12: ...9 HESP DUCT Units ...
Страница 31: ...28 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 38: ...35 Console Units Ceiling floor Units ...
Страница 43: ...40 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D ...
Страница 44: ...41 CTBU 36HWFN1 M C CTBU 48HWFN1 M C ...
Страница 45: ...42 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C ...
Страница 46: ...43 MUE 48HRFN1 M C MUE 60HRFN1 MW ...
Страница 47: ...44 MUE 36HRFN1 M C MUE 48HRFN1 M C ...
Страница 48: ...45 MUE 60HRFN1 MW MTI 18HWFN1 MT0W MTIU 24HWFN1 MW ...
Страница 49: ...46 MTIU 36HWFN1 MW MTIU 48HWFN1 MW MHG 60HWFN1 MW ...
Страница 51: ...48 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W ...
Страница 52: ...49 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W ...
Страница 53: ...50 MOD30U 36HFN1 M ...
Страница 59: ...56 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 60: ...57 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 61: ...58 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 62: ...59 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 63: ...60 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 64: ...61 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 74: ...71 12 Field Wiring 36K 48K 60K ...
Страница 123: ...120 P U P V ...
Страница 124: ...121 P W P N ...
Страница 141: ...138 ...
Страница 151: ...148 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw ...
Страница 187: ...184 5 Remove the four fixing screws of the fan motor then remove the motor 5 ...
Страница 200: ...197 6 Remove the grounding screw 7 Remove the Wires 1 2 3 or L1 L2 S Then remove the electronic control box 7 ...