97
off and restart 30s later, if protection happened
3 times when fan motor restarts continuously,
the unit will stop and the LED will display the
failure.
When outdoor fan speed keeps too low (lower
than 100RPM) or too high (higher than
1500RPM) for 60s, the unit will stop and the
LED will display the failure. Malfunction is
cleared 30s later.
For A6 Duct& HESP Duct:
If a fault occurs on the air volume regulator or
the regulator enters protection mode, it sends
the error message CF and an instruction to
reduce fan speed to the master. The message
and the instruction can be inquired with the
remote controller or the wired controller. (Fault
and protection information are displayed for
one minute). After a fault occurs, the master
unit shows the error code E3 and the fault count
for one minute. If the fault occurs three times,
then the fan is unable to resolve the problem
independently. External shutdown by a remote
controller, wired controller, or central controller
must be used to clear the fan fault and fault
count. The fan runs normally for 5 minutes
while clearing fault count.
0:
No malfunction
1:P0 Overcurrent
2:Overpressure
3:
Overload
4:Overspeed
5:Startup malfunction
6:Lack of phase
7:DC voltage too low
8:Communication fault
9:Parameter fault
10:L3 Current limited
11:L5 Voltage limited
12:Target speed cannot be met during the
static pressure calculation process.
14.3.5 Inverter module protection
The Inverter module has a protection function
about current, voltage and temperature. If these
protections happen, the corresponding code
will display on indoor unit and the unit will stop
working.
14.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active
immediately and the indoor fan will open 7s
later.
If the unit runs in heating mode, the indoor fan
will be also controlled by anti-cold wind
function.
14.3.7 Compressor preheating functions
Preheating permitting condition:
If T4
<
3
℃
(37.4°F) and the machine connects
to power supply newly within 5 seconds or if T4
<
3
℃
(37.4°F) and compressor has stopped for
over 3 hours, the compressor heating cable will
work.
Preheating mode:
A weak current flow through the coil of
compressor from the wiring terminal of the
compressor, then the compressor is heated
without operation.
Preheating release condition:
If T4
≥5
℃
(41°F) or the compressor starts
running, the preheating function will stop.
14.3.9 Condenser high temperature T3
protection
---55°C(131°F)<T3<60°C(140°F),
the
compressor frequency will decrease to the
lower level until to F1 and then runs at F1.If
T3<54°C(129.2°F), the compressor will keep
running at the current frequency.
---T3<52°C(125.6°F), the compressor will not
limit the frequency and resume to the former
frequency.
---T3>60°C(140°F)
for
5
seconds,
the
compressor will stop until T3<52°C(125.6°F).
14.3.10 Evaporator low temperature T2
protection
---T2<0°C(32°F), the compressor will stop and
restart when T2
≧
5°C(41°F).
---0°C(32°F)
≦
T2<4°C(39.2°F), the compressor
frequency will be limited and decreased to the
lower level
Содержание CCA3U-09HRFN1-MC
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Cassette Units ...
Страница 9: ...6 A5 Duct Units A6 Duct Units ...
Страница 10: ...7 Console Units ...
Страница 11: ...8 Ceiling floor Units ...
Страница 12: ...9 HESP DUCT Units ...
Страница 31: ...28 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 38: ...35 Console Units Ceiling floor Units ...
Страница 43: ...40 CFAU 09HRFN1 M C CFAU 12HRFN1 M C MCD 36HRFN1 M C MCD 48HRFN1 M D ...
Страница 44: ...41 CTBU 36HWFN1 M C CTBU 48HWFN1 M C ...
Страница 45: ...42 MUEU 18HRFN1 M C MUEU 24HRFN1 M C MUE 36HRFN1 M C ...
Страница 46: ...43 MUE 48HRFN1 M C MUE 60HRFN1 MW ...
Страница 47: ...44 MUE 36HRFN1 M C MUE 48HRFN1 M C ...
Страница 48: ...45 MUE 60HRFN1 MW MTI 18HWFN1 MT0W MTIU 24HWFN1 MW ...
Страница 49: ...46 MTIU 36HWFN1 MW MTIU 48HWFN1 MW MHG 60HWFN1 MW ...
Страница 51: ...48 MOBA30 09HFN1 MT0W MOB30 12HFN1 MT0W ...
Страница 52: ...49 MOD30 24HFN1 MT0W MOD01 23HFN1 MT0W ...
Страница 53: ...50 MOD30U 36HFN1 M ...
Страница 59: ...56 CTBU 09HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 60: ...57 CTBU 12HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 61: ...58 CTBU 18HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 62: ...59 CTBU 24HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 63: ...60 CTB 36HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 64: ...61 CTB 48HWFN1 M C Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 74: ...71 12 Field Wiring 36K 48K 60K ...
Страница 123: ...120 P U P V ...
Страница 124: ...121 P W P N ...
Страница 141: ...138 ...
Страница 151: ...148 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw ...
Страница 187: ...184 5 Remove the four fixing screws of the fan motor then remove the motor 5 ...
Страница 200: ...197 6 Remove the grounding screw 7 Remove the Wires 1 2 3 or L1 L2 S Then remove the electronic control box 7 ...