Technical
Manual
Switch
Actuators
AMI/AMS
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
49
6.4
Group
state
The
following
chart
shows
the
assignment
of
the
4
Byte
‐
object:
Channel
active
not
active
ON
OFF
Channel
A
Bit
16
=
1
Bit
16
=
0
Bit
0
=
1
Bit
0
=
0
Channel
B
Bit
17
=
1
Bit
17
=
0
Bit
1
=
1
Bit
1
=
0
Channel
C
Bit
18
=
1
Bit
18
=
0
Bit
2
=
1
Bit
2
=
0
Channel
D
Bit
19
=
1
Bit
19
=
0
Bit
3
=
1
Bit
3
=
0
Channel
E
Bit
20
=
1
Bit
20
=
0
Bit
4
=
1
Bit
4
=
0
Channel
F
Bit
21
=
1
Bit
21
=
0
Bit
5
=
1
Bit
5
=
0
Channel
G
Bit
22
=
1
Bit
22
=
0
Bit
6
=
1
Bit
6
=
0
Channel
H
Bit
23
=
1
Bit
23
=
0
Bit
7
=
1
Bit
7
=
0
Channel
I
Bit
24
=
1
Bit
24
=
0
Bit
8
=
1
Bit
8
=
0
Channel
J
Bit
25
=
1
Bit
25
=
0
Bit
9
=
1
Bit
9
=
0
Channel
K
Bit
26
=
1
Bit
26
=
0
Bit
10
=
1
Bit
10
=
0
Channel
L
Bit
27
=
1
Bit
27
=
0
Bit
11
=
1
Bit
11
=
0
The
following
chart
shows
exemplary
the
emitted
group
state
for
some
cases:
Channel
Case
1
Case
2
Case
3
Case
4
active
ON
active
ON
active
ON
active
ON
Channel
A
X
X
X
X
X
X
Channel
B
X
X
X
Channel
C
X
X
X
X
X
Channel
D
X
X
X
X
Channel
E
X
X
X
X
Channel
F
X
X
X
Channel
G
X
X
X
X
Channel
H
X
X
X
X
X
X
Channel
I
X
X
Channel
J
X
X
X
X
Channel
K
X
X
Channel
L
X
X
Bit
‐
code
active/inactive
ON/OFF
0000
0000
0000
0000
0000
0000
0000
0000
0000
1111
1111
1111
0000
1111
1111
1111
0000
0101
0000
0101
0000
0101
0000
0001
0000
0000
1111
1111
0000
0000
1101
1101
Output
of
the
group
state
00
00
00
00
0F
FF
0F
FF
05
05
05
01
00
FF
00
DD