Technical

 

Manual

 

Switch

 

Actuators

 

AMI/AMS

 

 

 

MDT technologies GmbH  •  

51766 Engelskirchen  •  Papiermühle 1

 

 

Tel.: +49-2263-880  •  Fax: +49-2263-4588  • [email protected]  •  www.mdt.de 

7

 

 

2.4

 

Functions

 

 

All

 

of

 

the

 

channels

 

have

 

identical

 

functions

 

(have

 

a

 

look

 

at

 

the

 

functional

 

overview).

 

The

 

numbers

 

of

 

channels

 

depends

 

to

 

the

 

hardware

 

design,

 

which

 

can

 

have

 

2,

 

4,

 

8,

 

12

 

or

 

16

 

channels.

 

The

 

identification

 

is

 

standardly

 

in

 

consecutive

 

alphabetic

 

order.

  

There

 

are

 

3

 

different

 

states

 

for

 

every

 

channel

 

possible:

 

 

not

 

active

 

The

 

channel

 

has

 

no

 

function.

 

So

 

there

 

are

 

no

 

communication

 

objects

 

for

 

this

 

channel

 

shown.

 

 

Switch

 

If

 

the

 

channel

 

is

 

chosen

 

as

 

switch,

 

there

 

will

 

be

 

different

 

parameterization

 

options

 

for

 

configuring

 

the

 

switching

 

process.

 

 

Staircase

 

Now,

 

the

 

channel

 

can

 

become

 

a

 

staircase

 

light

 

function.

 

This

 

function

 

causes

 

an

 

automatic

 

switch

 

off

 

of

 

the

 

channel

 

after

 

an

 

adjusted

 

time.

 

 

2.4.1

 

Overview

 

functions

 

 

Group

 

of

 

functions

 

Functions

 

Reset

 

behavior

 

behavior

 

at

 

bus

 

power

 

breakdown

 

behavior

 

at

 

bus

 

power

 

up

 

startup

 

timeout

 

Relay

 

mode

 

normally

 

closed/

 

normally

 

opened

 

Switch

 

functions

 

switching

 

central

 

switching

 

function

 

Time

 

functions

 

on

delay

 

off

delay

 

Staircase

 

light

 

functions

 

time

 

for

 

staircase

 

pre

warning

 

(with

 

adjustable

 

warning

 

and

 

pre

warning

 

time)

  

manual

 

off

 

retriggerable

 

on/off

 

Superior

 

functions

 

blocking

 

function

 

logic

 

functions

 

(AND/

 

OR)

 

Scenes

 

scene

 

function

 

for

 

up

 

to

 

8

 

scenes

 

per

 

channel

 

Status

 

functions

 

feedback

 

function

 

cyclic

 

send

 

able

 

“operating

state”

 

telegram

 

group

 

state

 

of

 

all

 

channels

 

Current

 

measurement

 

single

 

current

 

measurement

 

of

 

each

 

channel

 

warning

 

and

 

error

 

messages

 

adjustable

 

total

 

current

 

measurement

 

of

 

the

 

whole

 

device

 

Electric

 

meter

 

functions

 

counting

 

of

 

the

 

current

 

consumption

 

of

 

every

 

channel

 

counting

 

of

 

the

 

current

 

consumption

 

of

 

the

 

whole

 

actuator

 

Operating

 

hours

 

counter

 

forward

 

counter

 

of

 

the

 

operating

 

hours

 

back

 

counter

 

to

 

next

 

service

 

time

 

Table

 

1:

 

Overview

 

functions

 

 

 

Содержание AMI series

Страница 1: ...nologies GmbH 51766 Engelskirchen Papiermühle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 1 6 2014 Technical Manual MDT Switch Actuators with current measurement AMI AMS R2 x 2nd Hardware Revision ...

Страница 2: ...t 10 3 3 Communication Objects current measurement 11 3 4 Default settings of the communication objects 12 4 Reference ETS Parameter 13 4 1 General Settings 13 4 2 Channel selection 14 4 3 Identical parameter 15 4 3 1 Relay operating mode 15 4 3 2 Central function 16 4 3 3 Behavior at block unblock 16 4 3 4 Behavior at bus power up down 18 4 3 5 Manual control and cyclic send of the current state ...

Страница 3: ...ion 37 4 6 3 Total current measurement 38 4 6 4 Total power meter function 39 4 6 5 Monitoring exceedance deviation of load 40 4 6 6 Fault current Load failure 42 4 7 Operating hours 43 4 7 1 Operating hours counter 43 4 7 2 Reverse counter 44 5 Index 46 5 1 Register of illustrations 46 5 2 List of tables 47 6 Attachment 48 6 1 Statutory requirements 48 6 2 Routine disposal 48 6 3 Assemblage 48 6 ...

Страница 4: ...surement AMS 0816 01 Switching actuator 8 fold 8TE 230V AC 16 A C Load 100µF standard design o 8 TE REG 230VAC 16A C Load 100uF with current measurement AMS 1216 01 Switching actuator 12 fold 4TE 230V AC 16 A C Load 100µF standard design o 12 TE REG 230VAC 16A C Load 100uF with current measurement AMI 0416 01 Switching actuator 4 fold 4TE 230V AC 16 A C Load 200µF industrial design o 4 TE REG 230V...

Страница 5: ...MS MDT technologies GmbH 51766 Engelskirchen Papiermühle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 5 2 2 Exemplary circuit diagrams Figure 1 Exemplary circuit diagram AMS 0816 01 Figure 2 Exemplary circuit diagram AMI 1216 01 ...

Страница 6: ...n contrast the line of the AKK has only four buttons independent to the number of channels Two buttons are for choosing the channel whereby the chosen channel is indicated by a flashing status LED The buttons up and down are for switching the channel on and off The programming button activates the programming function An activated programing function is indicated by a lit programming LED Figure 3 ...

Страница 7: ...d time 2 4 1 Overview functions Group of functions Functions Reset behavior behavior at bus power breakdown behavior at bus power up startup timeout Relay mode normally closed normally opened Switch functions switching central switching function Time functions on delay off delay Staircase light functions time for staircase pre warning with adjustable warning and pre warning time manual off retrigg...

Страница 8: ...ed to the used type e g AKI 0816 01 2 6 Starting up After wiring the allocation of the physical address and the parameterization of every channel follow 1 Connect the interface with the bus e g MDT USB interface 2 Switching the power supply 3 Set bus power up 4 Press the programming button at the device red programming LED lights 5 Loading of the physical address out of the ETS Software by using t...

Страница 9: ...ation shows the communication objects for the channels A and B Channel A is selected as switch Logic functions blocking object and scenes are activated Channel B is selected as staircase Only the blocking function is activated Figure 4 Communication objects per channel Channel A switch Channel B staircase The following communication objects can be shown for a channel selected as switch Nr Function...

Страница 10: ...s are always shown also if they are not used in any of the channels The communication objects for the central functions are at the bottom of the communication objects They have always the first number after the communication objects for the channels Every channel can be parameterized whether it shall be effected of the central functions or not The following communication object exists only once an...

Страница 11: ...PT 1 001 Out Read 14 Fault current reports a fault current DPT 1 001 Out Read 14 Load faulty reports a fault of the load DPT 1 001 Out Read 14 Fault current Load faulty reports a fault current and a fault of the load DPT 1 001 Out Read 15 Reset power meter resets the calculated energy of the channel DPT 1 001 In Write 16 Active energy sends the calculated energy of the channel DPT 13 010 DPT 13 01...

Страница 12: ...el A Lower deviation of load 1 Bit Low X X X 13 Channel A Fault current 1 Bit Low X X X 14 Channel A Load faulty 1 Bit Low X X X 14 Channel A Fault current Load faulty 1 Bit Low X X X 14 Channel A Reset service 1 Bit Low X X X 15 Channel A Reset power meter 1 Bit Low X X 16 Channel A Active energy 4 Byte Low X X X 8 next channel 72 144 Central function Operating 1 Bit Low X X X 73 145 Central func...

Страница 13: ...the state of all channels as 4 Byte telegram which can be used for visualizations The following chart shows the dynamic range of this parameter ETS text Dynamic range default value comment Startup timeout 1 60s 1s Time between an upload and the functional start of the device Cyclic send of Operating Telegram no send 10min 30min 1h 3h 6h 12h 24h activates the cyclic sending of the Operating telegra...

Страница 14: ...n There are 3 possible states for every channel which can be adjusted at the menu channel preselection The following parameterization accords to the chosen state of a channel But if you chosse a channel as not active there will be no further parameterization options available The chart shows the setting options for everey channel ETS text Dynamic range default value comment Channel A O not active ...

Страница 15: ...ircase 4 3 1 Relay operating mode The following illustration shows the setting options for this parameter Figure 7 Operating mode The following chart shows the dynamic range for this parameter ETS text Dynamic range default value comment Mode normally opened normally closed Relay operating mode of the channel Table 10 Operating mode The following diagram shows the behavior of the relay operating m...

Страница 16: ...bject all channels with an activated central function are switched on with their current parameterization So switch on delays or staircase functions are still kept The central function can make programming much more easier and your project can become more clear The following chart shows the associated communication object Number Name Length Usage Central function 1 Bit central switching of the cha...

Страница 17: ...lable for the Behavior when unlocked This action is called when the blocking function is deactivated again The following chart shows the corresponding communication object Number Name Length Usage 2 Block 1 Bit blocks the channel Table 14 Communication object blocking function The following diagram describes the blocking process For the Behavior when locked the action on was parameterized and for ...

Страница 18: ...value comment Behavior at bus power up Behavior at bus power down On Off no change Adjustment how the channel shall react in case of a bus power breakdown return Table 15 Behavior at bus power up down Every channel can occupy a certain state as well in case of a bus power breakdown as in case of a bus power return The channel can be switched off or on but also stay in its current state by choosing...

Страница 19: ...he current value If activated the current state will be send cyclic at the adjusted time steps via the object Channel X state Table 16 Manual control and cyclic send The manual control can be activated or deactivated permanent for each channel by the settings active or not active Additional the manual control can be blocked or enabled via the central object manual control There is only one central...

Страница 20: ...0 4 4 Switching output The following parameters which are described at the headings 4 4 x are only available at channels selected as switch 4 4 1 Overview By choosing a channel as switch a sub menu called Channel A Switching appears for this channel at the left drop down menu The sub menu is shown at the following illustration Figure 12 Switching output ...

Страница 21: ...central function for this channel Behavior when locked Off On no change Action for activating the blocking process Behavior when unlocked Off On no change Action for deactivating the blocking process Behavior at bus power down Off On no change Action for a bus power breakdown Behavior at bus power up Off On no change Action for a bus power return Logic function not active with one object with two ...

Страница 22: ...a delayed switch of the channel At sending an on signal to the channel first the adjusted on delay time expires and afterwards the channel will be switched on The off delay works on the same principle At sending an off signal first the adjusted off delay time expires and afterwards the channel will be switched off Both functions work as well alone as combined By adjusting 0 seconds for a delay the...

Страница 23: ... AND function and an OR function The following figure shows an overview of the basic logic function with two objects Figure 15 Overview Logic function The logic function consists of the activated input objects and the switching object for each channel The output of the logic is the respective relay output of the channel so the physical switching of the channel The following chart shows the relevan...

Страница 24: ...e following table illustrates the two logic functions AND Connection OR Connection Switch On Off Logic 1 Logic 2 Channel switched Switch On Off Logic 1 Logic 2 Channel switched 0 0 0 Nein 0 0 0 Nein 0 0 1 Nein 0 0 1 Ja 0 1 0 Nein 0 1 0 Ja 0 1 1 Nein 0 1 1 Ja 1 0 0 Nein 1 0 0 Ja 1 0 1 Nein 1 0 1 Ja 1 1 0 Nein 1 1 0 Ja 1 1 1 Ja 1 1 1 Ja Table 20 Logic function ...

Страница 25: ...sub menu for the scenes appears at the left drop down menu There are settings to activate single scenes set values and scene numbers and switch the memory function on off at this sub menu Scenes are activated by receiving their scene numbers at the communication object for the scenes If the memory function of the scenes is activated the current value of the channel will be saved at the called scen...

Страница 26: ...s GmbH 51766 Engelskirchen Papiermühle 1 Tel 49 2263 880 Fax 49 2263 4588 knx mdt de www mdt de 26 There are up to 8 storage options for scenes at every channel These 8 storage options can get any of the possible 64 scene numbers Figure 17 Sub function scene ...

Страница 27: ...g value 1 less than the adjusted scene number Scene C Off On Activation of the scene C Scene number C 1 64 1 Scene number Calling value 1 less than the adjusted scene number Scene D Off On Activation of the scene D Scene number D 1 64 1 Scene number Calling value 1 less than the adjusted scene number Scene E Off On Activation of the scene E Scene number E 1 64 1 Scene number Calling value 1 less t...

Страница 28: ...03 3 0x83 131 5 0x04 4 0x84 132 6 0x05 5 0x85 133 7 0x06 6 0x86 134 8 0x07 7 0x87 135 9 0x08 8 0x88 136 10 0x09 9 0x89 137 11 0x0A 10 0x8A 138 12 0x0B 11 0x8B 139 13 0x0C 12 0x8C 140 14 0x0D 13 0x8D 141 15 0x0E 14 0x8E 142 16 0x0F 15 0x8F 143 17 0x10 16 0x90 144 18 0x11 17 0x91 145 19 0x12 18 0x92 146 20 0x13 19 0x93 147 21 0x14 20 0x94 148 22 0x15 21 0x95 149 23 0x16 22 0x96 150 24 0x17 23 0x97 1...

Страница 29: ...set the both communication objects for the scenes to the same group address By sending the calling value both scenes are called Your programming can become much clearer if you divide your group addresses by scene numbers If now one channel shall react to 8 scenes you will have to connect the communication object for the scenes to 8 group addresses The following illustrations shall make the divisio...

Страница 30: ...de 30 4 5 Staircase The following parameters which are described at the headings 4 5 x are only available at channels selected as staircase 4 5 1 Overview By choosing a channel as staircase a sub menu called Channel A Staircase appears for this channel at the left drop down menu The sub menu is shown at the following illustration Figure 19 Staircase ...

Страница 31: ...stment how long the light shall be switched on after the warning Whole duration of the warning process is the sum of the 3 times Staircase time warning and prewarning Only available when warning is activated Manual switching off not active active Activation of the manual turn off of the staircase Extend staircase time not active active Activation of the extension of the staircase Central function ...

Страница 32: ...ff of the channel after an adjusted time called time for staircase The time for staircase can be parameterized freely By sending an on signal at the communication object the channel is switched on and the time runs out After the time is ran out the channel is switched off automatically There are a lot of further functions to adjust the staircase function These functions are described at the follow...

Страница 33: ...time ran almost out and the lights are switched off soon This warning happens trough a short turn off the lights The duration of the turn off is indicated by the warning time A value of 1 3s is advisable for this parameter When the warning time runs out the lights will be switched on again for the adjusted prewarning time Now you have the opportunities to extend the staircase time when this parame...

Страница 34: ...communication object for switching the staircase function have a look at chart 20 page 27 When this function is not activated the channel switches only off after the staircase time runs out 4 5 5 Extend staircase time The following illustration shows the setting options at the ETS Software Figure 23 Extend staircase time By activating this function the staircase time is retriggerable That means wh...

Страница 35: ...l settings current measurement The following general settings can be done for the current measurement ETS text Dynamic range default value comment Object selection for the current measurement Whole value in mA Floating value in mA Value in A Value in kW Selection of the sending object for the current measurement Add the channel to total current measurement not active active adjusts whether the cha...

Страница 36: ...the calculation of the electric power of the channel For this setting additional the used voltage multiplied with the active power factor must be entered Figure 26 Calculation of the theoretical power The power of the channel is approximated calculated afterwards by a multiplication Furthermore can be set whether the channel shall be integrated to the total current measurement of the actuator have...

Страница 37: ...4h defines the sending condition for the calculated power Figure 28 Settings power meter function The power meter counts the active energy of the channel according to the adjusted voltage and the measured current The intern count is continuous but the output rises only up every 10Wh Via the object Reset power meter the power meter can be set to zero again So the power meter function offers an effe...

Страница 38: ...ollowing settings can be made for the total current measurement ETS text Dynamic range default value comment Object selection for the current measurement Floating value in mA Value in A Value in kW Selection of the sending object for the current measurement Send actual value after changes value not active 1 75 not active Activation and adjustment of the sending of the current value at determined c...

Страница 39: ...r the total current measurement is shown at the following chart Number Name Length Usage 78 148 Value of total current 2 4 Byte sends the actual current of the whole actuator 79 149 Exceedance of total current 1 Bit reports an exceedance of the total current Table 30 Communication object total current 4 6 4 Total power meter function The following illustration shows the available settings for the ...

Страница 40: ...eter has in contrast to the power meter for the single channels no reset object The total power meter function calculates always the sum of all single channels So a reset of all single channels causes automatically a reset of the total power meter The communication object for the total power meter function is shown at the following chart Number Name Length Usage Total active energy 4 Byte sends th...

Страница 41: ... 100mA so the value can be adjusted in the range of 0 1A to 20A with 100mA steps The hysteresis which is indicated in of the reference value can avoid a too fast switching At the monitoring exceedance of load the hysteresis is subtracted from reference value At the monitoring lower deviation of load the hysteresis is added to the reference value But the switch on value is always the same as the re...

Страница 42: ... message a fault current or and a load failure can be shown The fault current is calculated when the channel has not been switched so the contact is opened The load failure is calculated when the channel has been switched so the contact is closed If the error message is active a 1 signal is sent by the communication object Via the setting switching threshold the sensitivity of the error message ca...

Страница 43: ...rent 500mA Current 1A Current 2A Current 5A Adjustment of the counting condition Send status of operating hours every hours 0 100 0h Adjustment when a message shall be sent Table 37 Operating hours counter The operating hours counter can count the operating hours at which the channel is active These can be count as well when the channel is switched on as when a determined current value is exceeded...

Страница 44: ... 0h Adjustment when a message shall be sent Send signal of service at x10h intervals 0 250 0h Adjustment when a service is required Table 39 Reverse counter to next service The reverse counter to the next service can count the operating hours in which the channel is active These can be counted back as well when the channel is switched on as when a determined current value is exceeded The value whe...

Страница 45: ...wing chart shows the relevant communication objects for this parameter Number Name Length Usage 8 Time to the next service 2 Byte sends the remaining time to the next service 9 Reset service 1 Bit resets service time back to the adjusted value 10 Service required 1 Bit reports that a service is required Table 40 Communication object reverse counter to next service ...

Страница 46: ...trol and cyclic send 19 Figure 12 Switching output 20 Figure 13 On Off delay 22 Figure 14 Logical functions 23 Figure 15 Overview Logic function 23 Figure 16 Scene function 25 Figure 17 Sub function scene 26 Figure 18 Programming of scenes 29 Figure 19 Staircase 30 Figure 20 Staircase time 32 Figure 21 Warning timer prewarning time 33 Figure 22 Manual switch off 34 Figure 23 Extend staircase time ...

Страница 47: ...tion objects manual control and cyclic send 19 Table 18 Switching output 21 Table 19 Communication objects logic 23 Table 20 Logic function 24 Table 21 Communication object scene 25 Table 22 Parameter scene 27 Table 23 Calling and saving scenes 28 Table 24 Parameter staircase 31 Table 25 Communication object staircase 32 Table 26 General settings current measurement 35 Table 27 Communication objec...

Страница 48: ...e can occur danger for humans animals or material assets Do not let the packaging lying around careless plastic foil bags etc can be a dangerous toy for kids 6 2 Routine disposal Do not throw the waste equipment in the household rubbish The device contains electrical devices which must be disposed as electronic scrap The casing contains of recyclable synthetic material 6 3 Assemblage Risk for life...

Страница 49: ...it 7 0 Channel I Bit 24 1 Bit 24 0 Bit 8 1 Bit 8 0 Channel J Bit 25 1 Bit 25 0 Bit 9 1 Bit 9 0 Channel K Bit 26 1 Bit 26 0 Bit 10 1 Bit 10 0 Channel L Bit 27 1 Bit 27 0 Bit 11 1 Bit 11 0 The following chart shows exemplary the emitted group state for some cases Channel Case 1 Case 2 Case 3 Case 4 active ON active ON active ON active ON Channel A X X X X X X Channel B X X X Channel C X X X X X Chan...

Страница 50: ...nter allows to capture the power consumption easily The active power is calculated by the voltage and the factor cos phi If the mains voltage fails all outputs hold their current position After bus voltage failure or recovery the relay position is selected in dependence on the parameterization The MDT Switch Actuator is a modular installation device for fixed installation in dry rooms It fits on D...

Страница 51: ...scent lamps parallel comp 1000W 2500W Max number of electronic transformers 14 28 Output life expectancy mechanical 1 000 000 1 000 000 Permitted wire gauge Screw terminal 0 5 4 0mm solid core 0 5 2 5mm finely stranded 0 5 4 0mm solid core 0 5 2 5mm finely stranded KNX busconnection terminal 0 8mm Ø solid core 0 8mm Ø solid core Power supply KNX bus KNX bus Power consumption KNX bus typ 0 3W 0 4W ...

Отзывы: