Technical
Manual
Switch
Actuators
AMI/AMS
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
13
4
Reference
ETS
‐
Parameter
4.1
General
Settings
The
following
parameter
exists
only
once
and
affects
to
all
channels:
Figure
5:
General
settings
The
parameter
startup
timeout
adjusts
the
time
between
an
upload
and
the
functional
start
of
the
device.
The
used
hardware
reacts
only
after
expiration
of
the
adjusted
time.
All
input
commands
before
the
startup
timeout
expire.
Furthermore
an
“Operating”
telegram
and
a
telegram
for
the
group
state
can
be
activated.
The
“Operating”
telegram
sends
cyclic
whether
the
actuator
answers
at
the
bus
or
not,
so
the
debugging
of
greater
objects
become
much
easier.
The
group
state
sends
the
state
of
all
channels
as
4
Byte
telegram,
which
can
be
used
for
visualizations.
The
following
chart
shows
the
dynamic
range
of
this
parameter:
ETS
‐
text
Dynamic
range
[default
value]
comment
Startup
timeout
1
‐
60s
[1s]
Time
between
an
upload
and
the
functional
start
of
the
device
Cyclic
send
of
“Operating”
‐
Telegram
no
send
,
10min,
30min,
1h,
3h,
6h,
12h,
24h
activates
the
cyclic
sending
of
the
“Operating”
telegram
if
the
actuator
answers
at
the
bus
Send
group
state
not
active
,
on
request,
on
changes,
on
changes
and
cyclic
5min/
19min/
30min/
1h/
2h/
4h
sends
the
states
of
all
channels
as
4
Byte
telegram
Total
current
active
not
active
activates
the
total
current
measurement,
have
a
look
at
chapter
4.6.2
total
current
Table
7:
General
settings
The
following
chart
shows
the
relevant
communication
objects:
Number
Name
Length
Usage
Operating
1
Bit
sends
cyclic,
if
the
actuator
is
at
the
bus
Group
state
4
Byte
sends
the
state
of
all
channels
Table
8:
Communication
objects
general
functions