ETS
‐
Text
Dynamic
range
[Default
value]
Comment
Settings
standby/orientation
light
Standby/Orientationlight
not
used
used
Setting
if
the
light
shall
stay
on
after
switching
off
Standby
setpoint
100
– 750
Lux
[100
Lux]
Value
for
the
standby
mode
Standby
time
1s
–
60min
[15s]
Length
of
standby
mode
Settings
lock
object
Force
control
active
Yes
No
activates
the
force
control
Lock
object
value
=
1
off
on
(100%)
no
change
(hold
value)
select
value
Adjustment
of
the
action
at
activation
Value
set
(nur
bei
„Wert
einstellbar“)
0
‐
100%
[0%]
defines
the
value
for
active
force
control
Lock
object
value
=
0
off
on
(100%)
no
change
(hold
value)
restore
previous
state
Adjustment
of
the
action
at
deactivation
Table
17:
Settings
Constant
light
control
‐
2
The
parameters
are
described
below:
Adjustment
switching
behavior/Regulation
The
general
settings
for
the
constant
level
light
regulation
can
be
done
here.
The
parameter
“Constant
light
controlled
by”
defines
whethter
the
constant
light
shall
be
switched
via
presence
or
an
external
object,
which
could
be
connected
to
push
button,
etc.
The
parameter
“Use
switch
on
dimming
value”
defines
the
start
‐
up
value
of
the
regulation.
It
can
be
calculated
directly
by
the
internal
calculating
routine
or
power
up
with
a
fixed
value.
Also
the
time
between
powering
up
and
starting
calculation
can
be
defined.
The
parameter
“Brightness
value
[Lux]
for
switch
on”
defines
if
the
regulation
shall
work
with
the
parameterized
value
or
the
last
setpoint,
which
can
be
set
by
a
relative
or
absolute
dimming
value
or
via
the
scene
function.
Further
more
the
regulation
can
be
parameterized
with
different
values
for
day
and
night
via
the
parameter
“Use
day/night
object”.