Technical Manual Presence Detector SCN-P360XX.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
17
The
following
chart
shows
the
avalibale
settings
for
these
parameters:
ETS
‐
Text
Dynamic
range
[Default
value]
Comment
Operating
mode
of
detector
fully
automatic
semi
automatic
Adjustment
oft
he
operating
mode
LED
green
(only
at
light
group
1&2)
Off
show
movement
show
movement
on
day
only
Definition
oft
he
switching
behavior
oft
he
green
LED
Follow
‐
up
time
1s
– 4h
[5
min]
Definition
of
the
On
‐
period
Lower
active
brightness
treshold
(only
at
light
groups)
0
‐
2000
Lux
[400
Lux]
Adjustment
below
the
detctor
shall
work;
the
sensor
is
not
active
at
greater
brightness
values
Upper
disable
brightness
treshold
(only
at
light
groups)
not
used
,
10
‐
2000
Lux
Adjustment
at
which
upper
value
the
detector
is
disabled
Number
of
monitoring
time
slots
(only
at
HCV)
0
‐
32
[3]
Definition
how
much
motions
must
be
detected
before
the
presence
detecor
switches
on
Length
of
monitoring
time
slot
(only
at
HCV)
0
‐
3000s
[30s]
Adjustment
oft
he
length
of
the
monitoring
time
slot
Force
or
lock
object
Force
control
object
Lock
object
universal
Lock
object
universal
and
force
object
ON
Adjustment
if
a
force
control
object
or
a
lock
object
shall
be
used
Table
5:
Setting
detector
The
parameters
are
described
in
detail
as
follows:
Operating
mode
The
operating
mode
is
divided
into
fully
automatic
and
semi
automatic.
So
the
presence
detector
can
be
configured
for
greater
rooms
as
Maser/Slave.
The
Master/Slvae
mode
is
described
in
detail
in
an
extra
chapter.
fully
automatic
If
the
presence
detector
is
configured
as
fully
automatic,
every
detected
presence
causes
power
‐
on
of
the
output.
semi
automatic
At
the
semi
automatic
mode,
the
output
is
only
switched
on
if
the
detector
detects
a
presence
and
the
object
External
Input
–
light
group
1/2
/HCV
receives
an
on
‐
signal
at
the
same
time.