Technical Manual Presence Detector SCN-P360XX.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
10
3
Communication
objects
3.1
Overview
The
communication
objects
are
divided
into
the
categories
of
the
submenus.
The
objects
0
‐
12
are
reserved
for
the
lightgroups.
The
displayed
objects
and
the
length
of
the
objects
change
in
accordance
of
the
adjusted
settings.
The
object
14
is
for
the
day/night
switchover
and
can
be
activated
via
the
general
settings.
Also
the
object
15
–
“Presence”
can
be
activated
in
the
general
settings.
The
objects
16
and
17
refer
to
the
menu
brightness
in
which
the
specific
settings
for
this
object
can
be
done.
They
contain
the
current
measured
brightness
value
and
the
threshold
value.
After
these
objects,
the
objects
for
the
Teach
‐
In
function
follows.
The
Teach
‐
In
function
is
for
the
internal
brightness
compensation,
especially
for
the
constant
light
function.
Then
the
objects
20
‐
28
follows,
which
are
responsible
for
the
constant
light
function.
The
object
29
‐
“Output
Heartbeat”
can
be
parametrized
in
the
general
settings.
3.2
Default
‐
settings
oft
he
communication
objects
The
following
table
shows
the
default
settings
of
the
communication
objects:
Default
settings
Nr.
Name
Function
Length
Priority
C
R W T
U
0
Output
–
Lightgroup
1
Switch
1
Bit
Low
X
X
X
0
Output
–
Lightgroup
1
Dimming
absolute
1
Byte
Low
0
Output
–
Lightgroup
1
Scene
1
Byte
Low
1
Output
–
Lightgroup
1
night
mode
Switch
1
Bit
Low
X
X
X
2
External
Input
–
Lightgoup
1
Switch
1
Bit
Low
X
X
3
Input
external
Movement
–
Lightgoup
1
Switch
1
Bit
Low
X
X
4
Input
–
Lightgroup
1
Force
control
2
Bit
Low
X
X
5
Input
–
Lightgroup
1
Lock
1
Bit
Low
X
X
6
Input
–
Lightgroup
1
Lock
object
On
1
Bit
Low
X
X
+7
Light
group
2