Technical Manual Presence Detector SCN-P360XX.01
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
18
Follow
‐
up
time
The
follow
‐
up
time
defines
the
power
‐
on
time.
The
detector
switches
on
at
detected
presence
until
the
adjusted
follow
‐
up
time
runs
out.
Sensor
activation/
‐
deactivation
The
sensor
activation/deactivation
is
only
available
at
light
groups.
By
using
this
setting,
the
detector
can
get
a
determined
working
zone.
The
parameter
“Lower
active
brightness
threshold”
defines
the
brightness
threshold
below
the
detector
works
as
normal
presence
detector.
If
the
brightness
is
higher
than
this
threshold,
no
motion
will
be
detected.
The
sensor
is
not
switched
off
upper
this
brightness
threshold.
This
behavior
can
be
achieved
by
using
the
parameter
“Upper
disable
brightness
treshold”.
This
value
should
not
be
adjusted
to
low,
because
this
could
effect
a
steady
switching
of
the
output.
Monitoring
time
slots
The
Monitoring
time
slots
are
only
available
fort
he
HCV
channel.
This
setting
causes
that
a
longer
detzection
is
necessary
for
switching
the
detector
on.
For
switching
the
channel
on,
in
every
time
slot
a
at
least
one
motion
must
be
detected.
Force
control
/Lock
object
The
object
can
be
used
as
well
as
force
conbtrol
object
or
as
lock
object.
The
force
control
object
has
3
different
states:
Force
control
ON
(control
=
1,
value
=
1)
At
this
mode
an
on
‐
command
is
sent
to
the
output.
The
evaluation
is
stopped
and
the
follow
‐
up
time
starts.
If
no
command
is
received
at
the
force
control
object
after
the
follow
‐
up
time,
the
detector
switches
back
into
the
normal
mode.
Force
control
OFF
(control
=
1,
value
=
0)
At
this
command
an
off
‐
command
is
sent
to
the
output.
The
evaluation
is
stopped
and
the
follow
‐
up
time
starts.
If
no
command
is
received
at
the
force
control
object
after
the
follow
‐
up
time,
the
detector
switches
back
into
the
normal
mode.
Force
control
AUTO
(control
=
0
value
=
0)
After
sending
this
command,
the
normal
mode
of
the
detector
starts.
The
lock
object
can
be
used
with
the
following
settings
for
the
activation
and
deactivation:
Force
control
ON
Same
functionality
as
described
at
Force
Control
ON.
Force
control
OFF
Same
functionality
as
described
at
Force
Control
OFF.
Automatic
mode
The
detector
switches
again
tot
he
automatic
mode.
Lock
(actual
state)
The
detector
is
locked
in
the
current
state.
Additional
a
second
lock
object
can
be
shown
fort
he
lock
object,
the
lock
object
ON.
This
object
switches
the
output
continuous