WFDNFT Vane-type Waterflow Detectors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

SPECIFICATIONS

Contact Ratings: 

Two sets of SPDT (Form C); 10 A @ 125/250 VAC 

; 2.5 A @ 12/24 VDC 

Triggering Threshold Bandwidth (Flow Rate): 

4 – 10 GPM

Static Pressure Rating: 

175 PSI (Max.)

Dimensions, Installed: 

WFDNFT – 4 in H x 3½

 

in W x 6¾ in D

Operating Temperature Range: 

32°F to 150°F (0°C to 66°C)

Enclosure Rating: 

WFDNFT – NEMA 4/IP54, as tested by Underwriters Laboratories, Inc. (UL)

The WFDNFT can be installed between 2×4 stud wall construction.

IMPORTANT

Please Read Carefully And Save
This instruction manual contains important information about the installation and 

operation of waterflow detectors. Purchasers who install waterflow detectors for use 

by others must leave this manual or a copy of it with the user. Read all instructions 

carefully before beginning.

CAUTION

The model WFDNFT is a vane-type waterflow detector for use in wet-pipe fire sprin-

kler systems only. Vane-type waterflow detectors shall not be used as the sole initiat-

ing device in both deluge and preaction systems; waterflow detectors used in these 

types of systems may result in an unintended discharge caused by a surge, trapped air 

or a short retard time.

WARNING

Installation must be performed by qualified personnel and in accordance with all na-

tional and local codes and ordinances.
Shock hazard: Disconnect power source before servicing. Serious injury or death 

could result.
Risk of explosion: Not for use in hazardous locations. Serious injury or death could 

result.

PRINCIPLES OF OPERATION

Vane-type waterflow detectors mount to water filled pipes in fire sprinkler systems. 

Waterflow in the pipe deflects a vane. Deflection of the vane produces a switched 

output, usually after a specified delay.
All WFDNFT detectors have a pneumatically controlled mechanical delay mecha-

nism. Delays do NOT accumulate; they reset if the flow of water stops or drops below 

minimum triggering flow rate before the entire delay has elapsed. All detectors will 

activate on a sustained flow of water of 10 gallons per minute (gpm) or greater down-

stream of the device.

COMPATIBLE PIPE TEES/RISERS

The WFDNFT is supplied with 12 paddles. One paddle is provided for each size of 

tee. See Figure 1 and approximate tee depth chart. Each paddle has an indication that 

shows the pipe size and type of tee to be used. 

INSTALLATION GUIDELINES

Before installing any waterflow alarm device, be thoroughly familiar with:

NFPA 72:  National Fire Alarm Code

NFPA 13:  Installation of Sprinkler Systems

NFPA 13D:  Standard for 1 and 2 Family Dwellings and Manufactured Homes

NFPA 13R:  Standard for Multi-family Dwellings
Also, follow other applicable NFPA standards, local codes and the requirements of the 

authority having jurisdiction. Failure to follow these directions may result in failure of 

I56-4263-B

FIGURE 1. MOUNTING DIMENSIONS AND APPROXIMATE TEE DEPTH 

REQUIREMENTS

3-1/2"

2-5/8"

TEE

DEPTH

4-3/32”

PLASTIC VANE

LOCKING

 COLLAR

TEE 

ADAPTER

.15”

TEE FITTING

GAUGE SUPPLIED ON 

PADDLE TREE MUST FIT 

BETWEEN TEE ADAPTER 

SHOULDER AND TEE 

 

W0400-00

APPROXIMATE TEE DEPTH REQUIREMENTS

TEE SIZE

Steel*/

Brass 

Threaded

Copper* 

Sweat

CPVC 

NIBCO

CPVC 

SPEARS 

w/Metal Band

CPVC  

SPEARS w/

Brass Insert

CPVC 
TYCO

1 X 1 X 1"

2

1

/

8

"

1

3

/

4

"

2

1

/

8

"

 (1)

2

3

/

32

(1)

2

1

/

2

(2)

2

3

/

4

(3)

1

1

/

4

 X 1

1

/

4

 x 1"

2

1

/

2

"

2

1

/

8

"

N/A

N/A

N/A

N/A

1

1

/

2

 X 1

1

/

2

 x 1"

2

3

/

4

"

2

1

/

4

"

N/A

3" 

(4)

N/A

N/A

2 X 2 X 1"

3

1

/

4

"

2

3

/

4

"

N/A

N/A

N/A

N/A

(1) Use paddle marked 1” CPVC; (2) Use paddle marked SPEARS 1” CPVC; 

(3) Use paddle marked TYCO 1” CPVC; (4) Use paddle marked 1

1

/

2

” CPVC

This waterflow detector has been evaluated for use with UL Listed CPVC fittings manu-

factured by the following companies: Tyco, Nibco and Spears Manufacturing Company. 

The Model WFDNFT is required to be installed in accordance with the Listing limitations 

specified by the manufacturer of the tee fitting. 
*See UL Listing Limitations on page 4. 

  

I56-4263-B 

 

 4/21

Содержание WFDNFT

Страница 1: ...elays do NOT accumulate they reset if the flow of water stops or drops below minimum triggering flow rate before the entire delay has elapsed All detectors will activate on a sustained flow of water of 10 gallons per minute gpm or greater down stream of the device COMPATIBLE PIPE TEES RISERS The WFDNFT is supplied with 12 paddles One paddle is provided for each size of tee See Figure 1 and approxi...

Страница 2: ...r and correct the problem before proceed ing CAUTION Avoidusingapipewrenchtotightenthelockingcollar Over torquingthelockingcollar may cause damage to the detector If additional tightening past hand tight is required on the collar use of a band wrench is recommended to protect collar surface not to exceed hand tight plus 1 notch on collar Be sure the direction of flow arrow and directional cover po...

Страница 3: ... applicable NFPA codes and standards and or the authority having jurisdiction for leaks and replace if leaks occur Test detectors at least quarterly as described under Operational Testing to insure proper operation Test more often if required by the authority having jurisdiction Under normal conditions Safe Signal waterflow detectors should provide years of trouble free service However if the dela...

Страница 4: ...e with the UL certification the model WFDNFT has additional critical installa tion limitations when installed in sprinkler systems constructed of metallic pipe and fittings The model WFDNFT must be installed in accordance with the limitations for BlazeMaster CPVC pipe and fittings which limits the installation of the product to systems in Light Hazard occupancies as defined in ANSI NFPA 13 Residen...

Отзывы: