background image

NOTE: Set the delay to the minimum required to prevent false alarms due to flow 

surges.
After extended service, parts of the detector may become worn reducing the time de-

lay and causing false alarms. If this happens, increase the delay. If the delay is already 

at maximum, replace the mechanical delay assembly. Refer to Maintenance section 

for ordering replacement parts.

OPERATIONAL TESTING

Always notify a central station monitoring waterflow alarms before repairing, main-

taining or testing waterflow alarm devices.
1.   Replace the cover and tighten the security screws with the tamper proof wrench. 

Store the wrench in a secure place.

2.   Open the inspector’s test valve and time how long it takes for the detector to 

indicate a flow condition. The detector should remain activated until the inspec-

tor’s test valve is closed. Air pockets in the sprinkler system may increase the 

apparent time delay.

FIGURE 4. DELAY ADJUSTMENT DIAL

NOTE: RETARD TIME MAY EXCEED 90 SECONDS. ADJUST

AND VERIFY THAT TIME DOES NOT EXCEED 90 SECONDS.

NUMBER ON DIAL IS APPROXIMATE TIME DELAY IN SECONDS

DELAY

ADJUSTMENT

DIAL

W0385-00

MAINTENANCE

To prevent accidental water damage, control valves should be shut tightly and the 

system completely drained before waterflow detectors are removed or replaced.
Inspect detectors in accordance with applicable NFPA codes and standards and/or 

the authority having jurisdiction for leaks and replace if leaks occur. Test detectors 

at least quarterly as described under Operational Testing to insure proper operation. 

Test more often if required by the authority having jurisdiction.
Under normal conditions Safe Signal waterflow detectors should provide years of 

trouble-free service. However, if the delay mechanism becomes faulty, a replacement 

kit is available. To replace the delay mechanisms, request Part No. FS-RT. Complete 

instructions are enclosed with replacement parts. The delay mechanism can be easily 

replaced without removing the detector from the pipe or draining the pipe. Refer to 

procedure below for removal of detector on pipe. Do not repair or replace any other 

waterflow detector components in the field. If any other part of the detector does not 

perform properly, replace the entire detector. Failure to follow this instruction may 

result in failure of the detector to report a waterflow condition.
Proceed as follows to remove a detector.
1.  Drain the pipe.
2.  Turn off electrical power to the detector
3.  Remove the cover and disconnect the wiring.
3.  Unscrew the locking collar.
4.  Lift the detector clear of the pipe.

CAUTION

If a vane breaks off in a pipe, find and remove it. Failure to do so may restrict the 

proper flow of water to part of the sprinkler system.

FIGURE 5. DIRECTIONAL COVER

NOTCHED COVER INDICATES FLOW DIRECTION AT A

DISTANCE FROM MULTIPLE VIEWING ANGLES

W0382-00

  

I56-4263-B 

 

 4/21

Содержание WFDNFT

Страница 1: ...elays do NOT accumulate they reset if the flow of water stops or drops below minimum triggering flow rate before the entire delay has elapsed All detectors will activate on a sustained flow of water of 10 gallons per minute gpm or greater down stream of the device COMPATIBLE PIPE TEES RISERS The WFDNFT is supplied with 12 paddles One paddle is provided for each size of tee See Figure 1 and approxi...

Страница 2: ...r and correct the problem before proceed ing CAUTION Avoidusingapipewrenchtotightenthelockingcollar Over torquingthelockingcollar may cause damage to the detector If additional tightening past hand tight is required on the collar use of a band wrench is recommended to protect collar surface not to exceed hand tight plus 1 notch on collar Be sure the direction of flow arrow and directional cover po...

Страница 3: ... applicable NFPA codes and standards and or the authority having jurisdiction for leaks and replace if leaks occur Test detectors at least quarterly as described under Operational Testing to insure proper operation Test more often if required by the authority having jurisdiction Under normal conditions Safe Signal waterflow detectors should provide years of trouble free service However if the dela...

Страница 4: ...e with the UL certification the model WFDNFT has additional critical installa tion limitations when installed in sprinkler systems constructed of metallic pipe and fittings The model WFDNFT must be installed in accordance with the limitations for BlazeMaster CPVC pipe and fittings which limits the installation of the product to systems in Light Hazard occupancies as defined in ANSI NFPA 13 Residen...

Отзывы: