OM WGS-5
WGS 130A to 190A
75
Unit Status will display one of the following:
Auto
Off:Ice
Mode
Timer
Off:All
Cir
Disabled
Off:Unit
Alarm
Off:Keypad
Disable
Off:Remote
Switch
Off:BAS
Disable Off:Unit
Switch
Off:Test
Mode
Auto:Wait for load
Auto:Cond Recirc
Auto:Evap Recirc
Auto:Wait Cond Flow
Auto:Wait Evap Flow
Auto:Pumpdown
Pump states include Off, Start, and Run. The condenser pump state is visible only for
water-cooled operation.
VIEW UNIT STATUS (2)
Softload Limit=XXX.X
Demand Limit= XXX.X
Network Limit= XXX.X
VIEW UNIT STATUS (3)
Unit Capacity=XXX.X%
Ice Delay= XXh XXm
Ice Delay will be visible only when unit mode is ice. It prevents the unit from undesirable
starts before the next day’s ice-making cycle.
VIEW UNIT STATUS (4)
1 2 3 4 5 6 8
D.O. X X X X X X X
D.I. X X X X X
The digital input and output status will show either a “0” or a “1” designating Off and On
states respectively.
View Unit Temperature
VIEW UNIT TEMP (1)
Evap LWT= XXX.X
o
F
Evap EWT= XXX.X
o
F
Active SP= XXX.X
o
F
VIEW UNIT TEMP (2)
LWT Pulldn= 0.0
o
F/m
Evap Delta T= XX.X
Water-cooled:
Air-cooled:
VIEW UNIT TEMP (3) VIEW UNIT TEMP (3)
Cond EWT= XXX.X
o
F
OAT= XXX.X
o
F
Cond LWT= XXX.X
o
F