WGS 130A to 190A
OM WGS-5
Screen Definitions – ALARM
ALARM LOG: XX
{Alarm Description}
hh:mm mm/dd/yy
{Parameters}
The most recent 25 alarms, either shutdown or limit, are shown in this menu and subsequent
menus located under it. The last alarm is shown first. ARROW DOWN from this menu
will go to the next-to-last alarm, ARROW DOWN again will go to the second from last, and
so on through the last 25 occurrences. The screens are numbered (1), (2), (3), etc.
Alarm Description will indicate which alarm occurred. If the alarm is a circuit alarm, then
the circuit for which the alarm occurred will also be indicated.
Parameters at the time of the alarm are shown on the bottom line of the screen one at a time.
These are scrolled through by pressing the edit key and using the up and down arrows to
scroll through the list. Parameters include:
Unit
State
Evap
LWT
Evap
EWT
Cond
EWT/OAT Circuit
State
Evaporator
Pressure
Condenser
Pressure
Suction
Temperature
Discharge
Temperature
Discharge
Superheat
EXV
Position
EXV
State
Slide
Position
Fans
On
Starter Fault Code (will show “00” when the alarm logged is not a starter fault)
EVENT LOG: XX
{Event Description}
hh:mm mm/dd/yy
*** ALARM ***
hh:mm mm/dd
{Alarm Description}
NO MORE ALARMS
Press ENTER to clear
If the unit is off on a shutdown alarm or running, but in a limit alarm condition, the cause
and date will appear in the above screen. If there is a simultaneous occurrence of more than
one alarm, the others will appear in additional screens below the first one, accessed by the
DOWN ARROW. Either type alarm will light a red light in back of the LEFT-ARROW
KEY. The light will go out when the fault is cleared. To clear the fault, scroll down to the
last screen and press ENTER. If other faults have appeared, they will all be cleared at the
same time.