82
WGS 130A to 190A
OM WGS-5
SET COMP SPs (3)
Pumpdown
Pressure= XX.X psi
Time Limit= XXX sec
SET COMP SPs (4)
Light Load Stage
Down Point=XX% slide
Stg Up Delay= XX min
SET COMP SPs (5)
Discharge Temp
Sensor Type=PT1000
Alarm Set Points
SET ALARM LIMITS (1)
Low Evap Pressure
Hold=XX.Xpsi
Unload=XX.Xpsi
The LowEvPrHold (Low Evaporator Pressure Hold) and LowEvPrUnld (Low Evaporator
Pressure Unload) have the same default value of 59 psi. If two compressors are running, the
LowEvPrUnld is in effect and the lag compressor will be shut off to unload the unit. If one
compressor is running, the LowEvPrHold is in effect and the lag compressor is prevented
from starting, thereby holding the unit capacity.
The last action to take place is the shutoff of all compressors running when the
LowEvPrStop setting is reached (default is 58 psi). Reducing these time intervals will
increase detrimental compressor cycling. It is recommended that these settings not be
changed.
SET ALARM LIMITS (2)
LowOilDelay= XXX sec
HighOilDpDel=XXX sec
Water-cooled:
Air-cooled
SET ALARM LIMITS (3) SET ALARM LIMITS (3
High Disc Temp=XXX
F High Disc Temp=XXX
F
HighLift Delay=XXsec HighLift Delay=XXsec
LowOATStartTmr=XXsec
:
SET ALARM LIMITS (4)
Evap Freeze= XX.X
F
Evap Flow Proof=XXXs
Recirc Timeout=xxmin
Evap Freeze (the unit freeze protection shutdown) is actually a stop alarm and shuts off the
unit when the LWT reaches 36
F. It is cleared by going to the CLEAR ALARM menu in
the ACTIVE ALARM hierarchy.