![McQuay RoofPak RAH 047C Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/mcquay/roofpak-rah-047c/roofpak-rah-047c_installation-and-maintenance-manual_1756079054.webp)
McQuay IM 487-4
51
Preparing Unit for Operation
Preparing Unit for Operation
Figure 61. RAH spring mount hold down fasteners
Spring Isolated Fans
Releasing Spring Mounts
The optional spring-mounted supply and return fans are locked
down for shipment. Hold-down fasteners are located at each
spring mount. Remove these fasteners before operating the
fans. Figure 62 shows a typical spring mount. Note that the
3/8" hold-down bolt securing the fan base to the unit cross
channel must be removed.
After removing the hold-down fasteners, rock the fan assembly
by hand to check for freedom of movement.
Figure 62. Spring mounted hold-down fasteners, all units
Figure 63. Fan spring mount adjustment
* Grossly out-of-adjustment thrust restraints can affect this
dimension. Recheck after thrust restrains are adjusted.74
Adjusting Spring Mounts
During operation, all fans should ride level, with the bottom of
the fan base approximately 3/8" (10mm) above the top of the
unit’s cross channel. Unhoused single-width “plug” fans will
also ride at this level when at rest.
•
When not operating, housed double-width fans ride lower at
the discharge end of the fan base than at the motor end.
When the fan is operating against a static pressure, it should
run level. If not, level the assembly as follows (see
Figure 63):
1
Loosen the 1 5/16" jam nut above the fan base.
2
Using a large, straight blade screwdriver, turn the 5/8"
leveling screw clockwise to lower the fan base,
counterclockwise to raise the fan base.
3
When properly adjusted, retighten the jam nut.
Relief Damper Tie-Down
Economizer sections with a 30" or 40" return fan have a relief
damper that is tied down for shipping. Remove the two
brackets and two screws before operation to allow free
movement of dampers. Access is from inside the economizer
section.
WARNING
Moving machinery hazard. Can cause severe injury or death.
Before servicing equipment, disconnect power and lock off.
More than one disconnect may be required to de-energize unit.
Hold-down
fasteners
Hold-down
fasteners
This bracket is added,
and these 3/8" tie downs
are used for RDS 800C.
This bracket is added,
and these 3/8" tie downs
are used for RDS 800C.
WARNING
Moving machinery hazard. Can cause severe injury or death.
Start the fans for the first time according to the “Check, Test,
and Start Procedures” on page 94. If this is not done, equipment
damage, severe personal injury, or death can occur.
3 /8 " ± 1 /4 "
with fan running
Leveling
screw
Spring
mount
assembly
Cross
channel
Jam nut
Fan base
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание RoofPak RAH 047C
Страница 118: ...McQuay IM 487 4 115 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 119: ...116 McQuay IM 487 4 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 120: ...McQuay IM 487 4 117 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...