![McQuay RoofPak RAH 047C Скачать руководство пользователя страница 114](http://html1.mh-extra.com/html/mcquay/roofpak-rah-047c/roofpak-rah-047c_installation-and-maintenance-manual_1756079114.webp)
McQuay IM 487-4
111
Maintenance
Terminals
The terminals are spring clamp type. They only require
inserting (see
in
Figure 124
) and clamping the wire to be
stripped, which offers several advantages over screw
terminals. The clamping is done by inserting a flat-bladed
screw driver (up to 9/64" wide). See
in
Figure 124
.
•
Spring connection does not require torquing and resists
vibration
•
Easily identifiable terminal markers
•
Built-in test ports on each terminal, up to 2.3 mm diameter
See
in
Figure 124
.
Figure 124. Terminal connectors
Phase Voltage Monitor (PVM) (see page 84)
The phase voltage monitor is designed to protect three-phase
loads from damaging power conditions. A microprocessor-
based voltage and phase sensing circuit constantly monitors
the three-phase voltages to detect harmful power line
conditions. When a harmful condition is detected, its output
relay is deactivated after a specified trip delay (Trip Delay).
The output relay reactivates after power line conditions return
to an acceptable level for a specified amount of time (Restart
Delay). The trip and restart delays prevent nuisance tripping
due to rapidly fluctuating power line conditions.
Other features:
•
LED display to indicate status (see
in Figure 125)
– Loss of phase
– High or low voltage
– Voltage unbalance
– Phase reversal
– Rapid cycling
– Standard 1 to 500 second variable restart delay (see
in
Figure 125)
•
Standard 2% to 8% variable voltage unbalance (see
in
Figure 125)
•
Standard 1 to 30 second trip delay (see
in Figure 125)
Figure 125. Phase voltage monitor
1
Standard
1–500 second
variable
restart delay
LED display
Standard 2%–8%
variable voltage
unbalance
4
Standard
1–30 second
trip delay
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание RoofPak RAH 047C
Страница 118: ...McQuay IM 487 4 115 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 119: ...116 McQuay IM 487 4 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...
Страница 120: ...McQuay IM 487 4 117 Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...