background image

IM 812 / Page 8 of 24

Electric Subbase
An electrical subbase is optional for 208V and 230V units, but
is standard for 265V units. It is available in two sizes: 3˝ or 4˝.
The subbase contains leveling legs for adjustment of up to 1˝
additional height. Install the wall sleeve and subbase at the
same time.

Note: A minimum of 4

3

8

˝ of the wall sleeve must project

into the room when using a subbase.

Installation
1.

If the minimum depth subbase is required (4

3

8

˝ ), discard

the side extension pieces. The subbase mounts flush with
the front of the wall sleeve.

2.

If more than the minimum depth subbase is required, de-
termine the depth of the side extension pieces desired
and break at the proper score-line. Insert the side exten-
sion pieces into the front assembly and secure with two
short black screws at each side.

3.

Insert leveling legs into subbase bottom flanges. Four (4)
legs will be needed if side extensions are used. Only two
(2) will be required if side extensions are not used.

4.

Place the subbase on the floor and align its center line
with the center line of the wall opening. Do not fasten the
subbases to the floor. After the wall sleeve has been in-
stalled, attach the subbase to it using the two clips
provided.

5.

The wiring should be roughed in and the conduit connected
to the electrical junction box. Complete the installation by
wiring the receptacle to the incoming power supply.

Subbase Installation

Figure 5. Electric Subbase

Electrical
Junction
Box for Main
Power Connection

Receptacle
Mounting Location

Plug/Cord Cover
(Required on 265V Units Only)

Knockouts for

Optional Fuse &

Disconnect Switch

Electrical Knockouts

3" or 4"

0" to 1"

41

1

2

"

Leveling Leg

17"

12"

5"

2

1

2

"

0" to 9

3

8

"

4

3

8

"

1

1

2

"

7

8

"

5

8

"

3"

Plan

Front Elevation (Three Front Panels in Place)

3

" x 5"

Opening for
Electrical and/or
Drain Rough-In

Side
Extension
Piece

3

1

2

"

All wiring must be done in accordance with local and National
Electrical Code requirements. Some units have a multitap
heater, so the Kw is determined by the field-installed power
cord, and some have factory installed cords with fixed heat-
ers. Refer to the data plate for proper overcurrent protection.
Time delay fuses or HACR circuit breakers are required to avoid
nuisance tripping.
Power Supply Wiring
208V and 230V units use a power cord that exits from beneath
the conditioner on the control (R.H.) side. The cord has a usable
length of 60˝ from where it exits the conditioner. (Do not use
extension cords.) When a subbase is not used, the receptacle
is generally mounted beneath the conditioner or on the wall
beside it. An electrical subbase is available and contains
a junction box for a field-mounted receptacle. All electrical
connections are made within the subbase, thus eliminating
the need for a wall-mounted receptacle (see Figure 5). The
subbase is available in 3˝ or 4˝ height and can be furnished
with a factory-mounted fused disconnect and receptacle as
an option. The subbase is optional for 208V and 230V, but
mandatory for 265V. The 265V chassis uses a “short cord,”
which is just long enough to plug into the subbase. A plug/
cord cover is also required on 265V to make the power cord
inaccessible (see Figure 5).

Power Supply and Control Wiring

Control Wiring
If the unit control pad will be wall mounted, rough in the 20´,
35´ or 50´ low-voltage wire harness at this time. The end of the
harness, with exposed terminals, will plug into the control box
at the unit. The other end, with concealed terminals, will con-
nect to the control pad on the wall. At the unit, exit the wall
with enough wire harness to reach the connector on the con-
trol box front. At the control pad mounting location on the
wall, exit with only a few inches of wire harness. Line up the
notch in the control pad mounting plate with the wire harness
exiting the wall and secure the plate to the wall. Unplug the
short cord from the PC board in the control pad, plug in the
new wire harness from the wall and snap the control pad onto
the mounting plate. The harness should all be concealed be-
hind the control pad when finished. If an optional 24V wall stat
will be used rather than the control pad, rough in the 4 to 7
low voltage wires as required by the stat. If remote ON/OFF
control will be used, rough in 2 low voltage wires (22 ga. min.)
to a maximum of 325´ from the unit, (see page 4.) If unit will be
connected to motion detector and door switch by others, rough
in the wiring as required by the manufacturer. Leave enough
wire at the unit to reach receptacles CN4 & CN7 on front of
control box.

WARNING

!

All electrical work must be done by trained, experienced
electricians in accordance with applicable codes and stan-
dards. Kinked, bent or chaffed cords; improper ground-
ing or fusing; improper current or voltage; or improper
installation can cause fire or electric hazards that can re-
sult in property damage or personal injury or death.

Содержание Remington PTAC B+

Страница 1: ...ntenance Data IM 812 Group PTAC PTHP Part Number TBD Date July 2004 McQuay Remington Packaged Terminal Air Conditioners and Heat Pumps B Model 2004 McQuay Remington Air Conditioning For Parts Support Call 800 411 7822 ...

Страница 2: ... units but manda tory for all 265V 5 Separate plug in power cord selects heater size NOTE PTAC HP 09 012 208 230 V 2 9 3 5 Kw heaters are also available with factory installed power cords 6 Electrical receptacle Optional for 208V and 230V units but mandatory for all 265V 7 Plug cord cover Optional for 208V and 230V units but mandatory for all 265V WARNING This product was carefully packed and thor...

Страница 3: ...65v B B Control C C Control KX 208 230v MX 265v A Universal Heater B Fixed Heater Fixed heater is 2 9 3 5 Kw 208 230V only with factory installed 20 amp power cord available on unit size 09 and 012 only Universal heater is nominal 2 3 or 5 Kw or no heat for cooling only applications determined by power cord selection See Table 2 page 15 Now that you have made an investment in modern efficient McQu...

Страница 4: ...n HEAT or COOL mode AUTO gives high fan if unit set ting is more than 2o F from room temperature and low fan if less than 2o F from room temperature Continuous Cycle Fan When dip switch 8 located on the front of the control box is OFF the indoor fan will operate continuously When dip switch 8 is ON the indoor fan will cycle on and off with the compressor or heater In cycle fan the fan will start e...

Страница 5: ...ACO MCO ACO or programmable With the exception of wired Remote ON OFF the control fea tures listed for the standard control pad will not be available with the wall thermostat unless the wall stat chosen includes them Low fan speed is standard for stats without speed selection Dip SWI 1 8 1 4 Temperature Limiting see chart page 4 5 6 Outdoor coil temperature when unit will change from reverse cycle...

Страница 6: ...2 1067mm Top View 133 4 349mm 203 4 527mm 16 406mm 133 4 349mm 16 406mm 1 2 13mm 3 8 Stamped Louver 11 8 Architectural Louver Front View Side View See Note 1 411 2 1054mm See Note 1 Subbase 7 178mm 7 178mm Wall Opening Requirements Before installing the unit check the wall opening to be sure the wall sleeve will slide into the opening unobstructed For masonry walls a lintel must be used to provide...

Страница 7: ...ust be flush or beyond the outside finished wall do not recess Install the outdoor drain kit as follows 1 Assemble the drain kit as shown in Figure 4 2 Choose the side of the wall sleeve to which the drain kit is to be installed 3 There are drain holes and pilot holes provided in the wall sleeve from factory Place the drain kit against the cho sen drain hole and fasten securely with screws provide...

Страница 8: ...he control R H side The cord has a usable length of 60 from where it exits the conditioner Do not use extension cords When a subbase is not used the receptacle is generally mounted beneath the conditioner or on the wall beside it An electrical subbase is available and contains a junction box for a field mounted receptacle All electrical connections are made within the subbase thus eliminating the ...

Страница 9: ...oors Outdoor Louver Louver Frame Front Panel 7 Wall Sleeve Min 2 Supports Field Supplied Receptacle by Others 133 4 16 16 Outdoor Louver Louver Frame Front Panel 7 Wall Sleeve 133 4 Subbase Side Extension Piece Caulk Perimeter Both Indoors Outdoors Power Supply Conduit Alternate Entry Electrical Subbase Floor Conduit 4 Recess the wall sleeve so that the louver is flush with the outside of the buil...

Страница 10: ...Place a thin pad of mastic on bottom of the opening and slide in the wall sleeve Be sure to recess the wall sleeve enough to accommodate outside louvers This recess is 3 8 for stamped louvers and 11 8 for architectural lou vers Louver should be flush to exterior surface when complete Note Wall sleeve must be flush with the exterior wall if using the outdoor drain kit see page 7 5 Level wall sleeve...

Страница 11: ...ction without subbase 208 230V only Note a Subbase is available in either 3 or 4 height Leveling legs provide adjustment of up to 1 additional height b Wall sleeve extension is available in various depths as required 5 Level wall sleeve left to right pitch it 1 4 bubble to the outdoors and secure in wall with fasteners as shown in Figure C page 12 A 5 16 hole is provided on each side 2 down from t...

Страница 12: ...he caulking does not block the weep holes 3 Attach indoor drain kit if used according to the instruc tions on page 7 Outdoor drain kits are not designed to be used with sleeve extensions Louver Frame Louver frames should be used for panel wall and thin wall applications for positive anchoring to the wall Recess the wall sleeve so that the louver is flush with the outside of the build ing if outdoo...

Страница 13: ... design that will not cause recir culation of condenser air Free area is defined by ASHRAE as the minimum area of the openings in an air inlet or outlet through which air can pass Refer application of special louvers or building facade treatments that may affect normal operation of the unit or re strict free air discharge of condenser airflow to your local McQuay Remington representative for facto...

Страница 14: ...e the room The chassis weighs approximately 150 lbs Use blocking and lifting devices Do not raise over any body parts 1 Remove the shipping carton and inspect for any shipping damage Report any found to the carrier 2 Save the shipping carton to cover installed conditioner until construction is complete 3 Remove the two screws attaching the front panel to the chassis and unlatch the front panel fro...

Страница 15: ...3 electrical cover on front of the control box Use the small plug and wire assembly provided Table 2 Power Cord Heater Kw Selection Heater Unit Vendor Plug Size Unit Fuse Kw Voltage Number 3 amps Size amps 0 1 208 105575502 15 15 0 1 230 105575502 15 15 0 1 265 105575804 20 15 1 5 208 105575501 15 15 1 9 230 105575501 15 15 1 9 265 105575802 20 15 2 3 208 105575601 20 15 2 8 230 105575601 20 20 2 ...

Страница 16: ...15 minute and 14 hour time delays Failure to remove short for long term operation will dam age the equipment and void the warranty 18 WIRELESS REMOTE CONTROLLER If this optional ac cessory will be used check it out at this time It will only work with the control pad either unit or wall mounted You should be able to control the unit from anywhere in the room by pointing the remote controller at the...

Страница 17: ...mall hole may be drilled and grommeted in the subbase front to allow passage of the low voltage wires 3 When using a programmable or electronic wall thermostat that requires 24V power include the BK common wire to the thermostat HP wall stats with 2 stage heat and mul tiple fan speed controls require that all 7 low voltage wires to be connected The stat must be programmed to power both WH and BR w...

Страница 18: ...BK BK RD CAP SC OM CM IM N Hi Lo N Hi C R S BU RD N T1 L BK RD RD RD WH WH BW BW WH WH BW BW PC1 NEUTRAL 2 HIGH FAN LOW FAN NEUTRAL 3 OTFAN HI 4WV NEUTRAL 1 RL6 L C C NO NO RL8 RL7 L COMP P3 P2 RD RD H1 H2 Electric Heater Transformer Control Pad Wireless Remote Control Room ID Coil OD Coil OutCoil InCoil Room CN8 PRI SEC CN11 CN5 CN2 CN10 CN6 CN7 CN4 CN3 PC2 BK BK BK BK GY GY THERMISTOR HL 1 1 2 2...

Страница 19: ... conditions Unit malfunction will occur if air filters are not kept clean To remove the air filters grasp the top of the filters and pull straight up Vacuum the filters from the dirty side or wash with hot water and a mild detergent Allow the filters to dry thoroughly before replacing them See Figure 19 B Every year the chassis should be removed for a thorough checkup This should be completed as f...

Страница 20: ... and the temperature of the conditioned space is 80o F Figure 20 Refrigeration Cycle 80o F Room Air to Evaporator 45o F R22 Liquid and Gas to Evaporator Capillary Restrictor 120o F Condenser Air to Outdoors Condenser Evaporator 60o F Conditioned Air to Room Hermetic Compressor 70 PSIG and 55o F to Compressor Gas 270 PSIG R22 to Condenser 95o F Outdoor Air to Condenser 120o F Liquid R22 Heating Coo...

Страница 21: ...gh condenser due to 1 Dirty condenser 2 Obstructed outdoor louver 3 Condenser fan not running 4 Condenser fan not up to speed 5 Condenser fan slipping on motor shaft 6 Recirculation of condenser air a Check supply line fusses circuit breakers and be sure the power is on Blown fuses would indicate circuit overloading a short circuit or a grounded condition in the circuit Voltage supply to the equip...

Страница 22: ... air flow 3 Clean or replace 4 Remove obstructions 5 Check motor 6 Check for correct voltage 7 Adjust blower wheel position and tighten set screw d Refer to original load calculations recalculate heat load e Close them f Replace g Replace a Adjust b Replace a Remove obstructions to water flow b Repair or replace c Check for correct voltage Replace motor or capacitor d Adjust a See No 1 b Raise the...

Страница 23: ...coil temperature sensor H P only a Replace b Replace c Replace Trouble Possible Causes Treatment Troubleshooting Chart Continued Troubleshooting can present hazards of electricity rotating parts sharp edges and weight Troubleshooting must be done by trained experienced technicians only Improper troubleshooting can result in equipment damage severe personal injury or death WARNING ...

Страница 24: ...the general appearance of McQuay Remington products at the time of publication and the manufacturer reserves the right to make changes in design and construction at anytime without notice 13600 Industrial Park Boulevard Minneapolis MN 55441 USA phone 763 553 5009 For replacement parts call 1 800 377 2787 2004 McQuay Remington Air Conditioning IM 812 Page 24 of 24 Rev 7 04 ...

Отзывы: