background image

IM 812 / Page 15 of 24

Equipment Start-up

5.

If the control pad is being remote mounted, unsnap the
control from its mounting bracket on the unit, unplug it
and mount it on the wall. Be sure to plug in the 6 wire
cable that connects it to the unit mounted control box.
Snap on the decorative cover that replaces the control
pad at the unit. See pages 5 and 8 for more information.
Dip switch #2 of 4 on front of control box, should be ON.

Note: If upon initial power up, the digital temperature dis-
play reads between 16

o

 and 30

o

 (Celsius), unplug the power

cord and plug it back in again to reset for Fahrenheit (60-
85

o

).

6.

Test HEAT by selecting the heat mode and increasing the
temperature setting until the unit is discharging heated air.
Note: Initial electric heater activation may result in
slight burning odor. It is recommended  to run heater
at time of installation several minutes until any odor
dissipates. To activate electric heaters on heat pump
models, select a unit temperature several degrees
above room temperature.

7.

Test COOL by selecting the cooling mode and decreasing
the temperature setting until the discharge air is cold.

8.

Test FAN by selecting the fan mode and increasing the
temperature setting to 85

o

F.  There should be no heat.

Lower the setting to 60

o

F. There should be no cooling.

9.

Test COOL/DRY by selecting the COOL mode. With indi-
cator light in COOL, press and hold the Mode key for 15
seconds until light switches to COOL/DRY. Then decrease
the temperature setting until the discharge air is cold.
Switch back to COOL by again pressing the Mode key for
15 seconds.

10. Test fan AUTO/HIGH/LOW as follows: With the unit in ei-

ther HEAT, or COOL mode, switch back and forth between
AUTO, HIGH and LOW speed, using the FAN key on the
control pad. The sound level between HIGH and LOW will
be noticeable and shown by indicator light. AUTO gives
Low fan if temperature setting is within 2

o

F of room tem-

perature and High fan if more than 2

o

F from room tem-

perature.

11. Test the CONTINUOUS/CYCLE fan by selecting HEAT or

COOL  mode and raising or lowering the temperature set
point. With dip switch #5 OFF, the indoor fan will continue
to run regardless of whether the unit is calling for heating/
cooling or not. With dip switch #8 ON, the indoor fan will
only run during “heat demand” and will run continuous
while unit calls for heat/cool and be OFF 7 minutes and
ON 2 minutes if unit is not heating/cooling. We recom-
mend leaving dip switch #8 ON to conserve energy.

12. ROOM FREEZE PROTECTION – If the owner wants this

feature (40

o

-50

o

F minimum room temperature), leave dip

switch #4 of 4 OFF. To test, place the room temperature
sensor in ice water and the heat will come on regardless of
the control mode or temperature settings.

13. WIRED REMOTE ON/OFF – If this feature is being used,

connect the two low voltage wires, coming from the re-
mote dry contacts, to the CN3 receptacle inside of the 2˝
x 3˝ electrical cover on front of the control box. Use the
small plug and wire assembly provided.

Table 2. Power Cord / Heater Kw Selection

Heater

Unit

Vendor

Plug Size

Unit Fuse

Kw

Voltage

Number

(3)

(amps)

Size (amps)

0

(1)

208

105575502

15

15

0

(1)

230

105575502

15

15

0

(1)

265

105575804

20

15

1.5

208

105575501

15

15

1.9

230

105575501

15

15

1.9

265

105575802

20

15

2.3

208

105575601

20

15

2.8

230

105575601

20

20

2.8

265

105575801

20

15

3.8

(2)

208

105575703

30

25

4.7

(2)

230

105575703

30

30

4.7

(2)

265

105575803

20

25

(1)

 Cooling Only  

     (2)

 Unit Size 12 and 15 only 

      (3)

 Molded on power cord receptacle

Initial start-up of the unit by trained, experienced personnel, is
usually the responsibility of the installing contractor. This start-
up consists of inspecting and operating the equipment for all
functions at the time of initial installation, and making neces-
sary adjustments. It also includes demonstrating its proper
operation to the owner or the owners’ agent. Note that, unless
otherwise specifically agreed to in writing, the manufacturer
includes no field labor, start-up service or the like in the price
of its equipment. After the equipment leaves the factory, it
may become damaged or maladjusted during transportation
or on the job. Sometimes wires are disconnected acciden-
tally, or fan motors move on their bases due to rough han-
dling, causing fans to strike. Correcting such conditions is part
of start-up. Dip switch settings from factory are all OFF ex-
cept #8 of 8 and #3 of 4. Any switch changes must be acti-
vated by unplugging and plugging in the power cord.

Note: There are various time delays built into the system
when using the unit or wall mounted control pad. Most of
these delays are only for a few seconds, but they can be
up to four minutes. The compressor will delay for two min-
utes before it can be restarted on both the control pad
and remote thermostat. The compressor will run for 90
seconds minimum unless mode is changed. The fan runs
for 15 seconds after the electric heater turns off. The unit
will always start up with random time delay.

1.

Chassis with separate power cord has a universal electric
heater. The power cord selected determines the Kw out-
put. Make sure you have the right cord for the heater Kw
required by the owner. See Table 2 below.

208/230V chassis with factory installed power cord, has a
2.9/3.5 Kw heater and must connect to a 20 amp circuit.

2.

Make certain the chassis power cord is plugged into a
receptacle with the correct voltage and fuse protection
required by the unit data plate. See IM 714 (ships with the
power cord) for more detail about the power cord and re-
ceptacle. Coil up any excess cord length and stow it un-
der the control box.

3.

Open or close the ventilation damper door as required by
the owner. The actuator is located at the lower left end of
the chassis. See Figure 15.

Note: Remove shipping screw from door if it needs to be
opened.

4.

If the conditioner will use the standard control pad
that ships with the unit, continue to step 5. If a remote
thermostat will be used rather than the control pad, skip
over steps 5 through 17 and continue with step 18.

Содержание Remington PTAC B+

Страница 1: ...ntenance Data IM 812 Group PTAC PTHP Part Number TBD Date July 2004 McQuay Remington Packaged Terminal Air Conditioners and Heat Pumps B Model 2004 McQuay Remington Air Conditioning For Parts Support Call 800 411 7822 ...

Страница 2: ... units but manda tory for all 265V 5 Separate plug in power cord selects heater size NOTE PTAC HP 09 012 208 230 V 2 9 3 5 Kw heaters are also available with factory installed power cords 6 Electrical receptacle Optional for 208V and 230V units but mandatory for all 265V 7 Plug cord cover Optional for 208V and 230V units but mandatory for all 265V WARNING This product was carefully packed and thor...

Страница 3: ...65v B B Control C C Control KX 208 230v MX 265v A Universal Heater B Fixed Heater Fixed heater is 2 9 3 5 Kw 208 230V only with factory installed 20 amp power cord available on unit size 09 and 012 only Universal heater is nominal 2 3 or 5 Kw or no heat for cooling only applications determined by power cord selection See Table 2 page 15 Now that you have made an investment in modern efficient McQu...

Страница 4: ...n HEAT or COOL mode AUTO gives high fan if unit set ting is more than 2o F from room temperature and low fan if less than 2o F from room temperature Continuous Cycle Fan When dip switch 8 located on the front of the control box is OFF the indoor fan will operate continuously When dip switch 8 is ON the indoor fan will cycle on and off with the compressor or heater In cycle fan the fan will start e...

Страница 5: ...ACO MCO ACO or programmable With the exception of wired Remote ON OFF the control fea tures listed for the standard control pad will not be available with the wall thermostat unless the wall stat chosen includes them Low fan speed is standard for stats without speed selection Dip SWI 1 8 1 4 Temperature Limiting see chart page 4 5 6 Outdoor coil temperature when unit will change from reverse cycle...

Страница 6: ...2 1067mm Top View 133 4 349mm 203 4 527mm 16 406mm 133 4 349mm 16 406mm 1 2 13mm 3 8 Stamped Louver 11 8 Architectural Louver Front View Side View See Note 1 411 2 1054mm See Note 1 Subbase 7 178mm 7 178mm Wall Opening Requirements Before installing the unit check the wall opening to be sure the wall sleeve will slide into the opening unobstructed For masonry walls a lintel must be used to provide...

Страница 7: ...ust be flush or beyond the outside finished wall do not recess Install the outdoor drain kit as follows 1 Assemble the drain kit as shown in Figure 4 2 Choose the side of the wall sleeve to which the drain kit is to be installed 3 There are drain holes and pilot holes provided in the wall sleeve from factory Place the drain kit against the cho sen drain hole and fasten securely with screws provide...

Страница 8: ...he control R H side The cord has a usable length of 60 from where it exits the conditioner Do not use extension cords When a subbase is not used the receptacle is generally mounted beneath the conditioner or on the wall beside it An electrical subbase is available and contains a junction box for a field mounted receptacle All electrical connections are made within the subbase thus eliminating the ...

Страница 9: ...oors Outdoor Louver Louver Frame Front Panel 7 Wall Sleeve Min 2 Supports Field Supplied Receptacle by Others 133 4 16 16 Outdoor Louver Louver Frame Front Panel 7 Wall Sleeve 133 4 Subbase Side Extension Piece Caulk Perimeter Both Indoors Outdoors Power Supply Conduit Alternate Entry Electrical Subbase Floor Conduit 4 Recess the wall sleeve so that the louver is flush with the outside of the buil...

Страница 10: ...Place a thin pad of mastic on bottom of the opening and slide in the wall sleeve Be sure to recess the wall sleeve enough to accommodate outside louvers This recess is 3 8 for stamped louvers and 11 8 for architectural lou vers Louver should be flush to exterior surface when complete Note Wall sleeve must be flush with the exterior wall if using the outdoor drain kit see page 7 5 Level wall sleeve...

Страница 11: ...ction without subbase 208 230V only Note a Subbase is available in either 3 or 4 height Leveling legs provide adjustment of up to 1 additional height b Wall sleeve extension is available in various depths as required 5 Level wall sleeve left to right pitch it 1 4 bubble to the outdoors and secure in wall with fasteners as shown in Figure C page 12 A 5 16 hole is provided on each side 2 down from t...

Страница 12: ...he caulking does not block the weep holes 3 Attach indoor drain kit if used according to the instruc tions on page 7 Outdoor drain kits are not designed to be used with sleeve extensions Louver Frame Louver frames should be used for panel wall and thin wall applications for positive anchoring to the wall Recess the wall sleeve so that the louver is flush with the outside of the build ing if outdoo...

Страница 13: ... design that will not cause recir culation of condenser air Free area is defined by ASHRAE as the minimum area of the openings in an air inlet or outlet through which air can pass Refer application of special louvers or building facade treatments that may affect normal operation of the unit or re strict free air discharge of condenser airflow to your local McQuay Remington representative for facto...

Страница 14: ...e the room The chassis weighs approximately 150 lbs Use blocking and lifting devices Do not raise over any body parts 1 Remove the shipping carton and inspect for any shipping damage Report any found to the carrier 2 Save the shipping carton to cover installed conditioner until construction is complete 3 Remove the two screws attaching the front panel to the chassis and unlatch the front panel fro...

Страница 15: ...3 electrical cover on front of the control box Use the small plug and wire assembly provided Table 2 Power Cord Heater Kw Selection Heater Unit Vendor Plug Size Unit Fuse Kw Voltage Number 3 amps Size amps 0 1 208 105575502 15 15 0 1 230 105575502 15 15 0 1 265 105575804 20 15 1 5 208 105575501 15 15 1 9 230 105575501 15 15 1 9 265 105575802 20 15 2 3 208 105575601 20 15 2 8 230 105575601 20 20 2 ...

Страница 16: ...15 minute and 14 hour time delays Failure to remove short for long term operation will dam age the equipment and void the warranty 18 WIRELESS REMOTE CONTROLLER If this optional ac cessory will be used check it out at this time It will only work with the control pad either unit or wall mounted You should be able to control the unit from anywhere in the room by pointing the remote controller at the...

Страница 17: ...mall hole may be drilled and grommeted in the subbase front to allow passage of the low voltage wires 3 When using a programmable or electronic wall thermostat that requires 24V power include the BK common wire to the thermostat HP wall stats with 2 stage heat and mul tiple fan speed controls require that all 7 low voltage wires to be connected The stat must be programmed to power both WH and BR w...

Страница 18: ...BK BK RD CAP SC OM CM IM N Hi Lo N Hi C R S BU RD N T1 L BK RD RD RD WH WH BW BW WH WH BW BW PC1 NEUTRAL 2 HIGH FAN LOW FAN NEUTRAL 3 OTFAN HI 4WV NEUTRAL 1 RL6 L C C NO NO RL8 RL7 L COMP P3 P2 RD RD H1 H2 Electric Heater Transformer Control Pad Wireless Remote Control Room ID Coil OD Coil OutCoil InCoil Room CN8 PRI SEC CN11 CN5 CN2 CN10 CN6 CN7 CN4 CN3 PC2 BK BK BK BK GY GY THERMISTOR HL 1 1 2 2...

Страница 19: ... conditions Unit malfunction will occur if air filters are not kept clean To remove the air filters grasp the top of the filters and pull straight up Vacuum the filters from the dirty side or wash with hot water and a mild detergent Allow the filters to dry thoroughly before replacing them See Figure 19 B Every year the chassis should be removed for a thorough checkup This should be completed as f...

Страница 20: ... and the temperature of the conditioned space is 80o F Figure 20 Refrigeration Cycle 80o F Room Air to Evaporator 45o F R22 Liquid and Gas to Evaporator Capillary Restrictor 120o F Condenser Air to Outdoors Condenser Evaporator 60o F Conditioned Air to Room Hermetic Compressor 70 PSIG and 55o F to Compressor Gas 270 PSIG R22 to Condenser 95o F Outdoor Air to Condenser 120o F Liquid R22 Heating Coo...

Страница 21: ...gh condenser due to 1 Dirty condenser 2 Obstructed outdoor louver 3 Condenser fan not running 4 Condenser fan not up to speed 5 Condenser fan slipping on motor shaft 6 Recirculation of condenser air a Check supply line fusses circuit breakers and be sure the power is on Blown fuses would indicate circuit overloading a short circuit or a grounded condition in the circuit Voltage supply to the equip...

Страница 22: ... air flow 3 Clean or replace 4 Remove obstructions 5 Check motor 6 Check for correct voltage 7 Adjust blower wheel position and tighten set screw d Refer to original load calculations recalculate heat load e Close them f Replace g Replace a Adjust b Replace a Remove obstructions to water flow b Repair or replace c Check for correct voltage Replace motor or capacitor d Adjust a See No 1 b Raise the...

Страница 23: ...coil temperature sensor H P only a Replace b Replace c Replace Trouble Possible Causes Treatment Troubleshooting Chart Continued Troubleshooting can present hazards of electricity rotating parts sharp edges and weight Troubleshooting must be done by trained experienced technicians only Improper troubleshooting can result in equipment damage severe personal injury or death WARNING ...

Страница 24: ...the general appearance of McQuay Remington products at the time of publication and the manufacturer reserves the right to make changes in design and construction at anytime without notice 13600 Industrial Park Boulevard Minneapolis MN 55441 USA phone 763 553 5009 For replacement parts call 1 800 377 2787 2004 McQuay Remington Air Conditioning IM 812 Page 24 of 24 Rev 7 04 ...

Отзывы: