www.DaikinApplied.com 39
IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS
o
peraTIon
WATER Setpoints
Figure 45: WATER Setpoint Screen
NOTE:
Grayed out setpoints do not apply to this model chiller.
Table 11: WATER Setpoint Settings
Description
No .
Default
Range
Password
Comments
Maximum Reset Delta T
9
0.0°F
0.0 to 20.0 °F
M
Set the maximum reset that can occur, in degrees F if LWT reset is
selected or max reset at 20 mA input if 4-20 mA is selected in SP7
Start Reset Delta T
8
10.0°F
0.0 to 20.0 °F
M
Sets the evap delta-T above which Return reset begins
LWT Reset Type
7
NONE
NONE, RETURN,
4-20mA
M
Select reset type, NONE for none, RETURN for resetting chilled water
based on the entering water, or 4-20 mA for external analog signal
Stage Delta T
6
1.0
0.5 to 5°F
M
Sets the temperature the leaving water must be above setpoint for next
compressor to start
Startup Delta T
5
3.0°F
0.0 to 10.0 °F
M
Degrees above setpoint for chiller to start
Shutdown Delta T
4
3.0°F
0.0 to 3.0 °F
M
Degrees below setpoint for chiller to stop
Leaving Water Temp - Cool
1
44.0°F
40.0 to 80.0 °F
M
Evaporator LWT setpoint in COOL mode
Содержание Magnitude C Vintage
Страница 4: ......
Страница 14: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 12 www DaikinApplied com Installation Figure 12 Wiring Index ...
Страница 15: ...www DaikinApplied com 13 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation ...
Страница 16: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 14 www DaikinApplied com Installation Figure 13 Controller Box Wiring ...
Страница 19: ...www DaikinApplied com 17 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation ...
Страница 67: ......