IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS
28 www.DaikinApplied.com
o
peraTIon
TIMERS Setpoints
Figure 28: TIMERS Setpoint Screen
NOTE:
Grayed out setpoints do not apply to this model chiller.
Table 5: TIMERS Setpoint Settings
Description
No .
Default
Range
Password
Comments
Full Load Timer
6
300 sec
0 to 999 sec
M
Time compressor must load (without unloading) before vanes are
considered fully open. This setpoint does not apply to this model
chiller.
Interlock Timer
5
10 sec
10 to 240 sec
M
Maximum time allowed before interlock confirmation from compressor
Stop-Start Timer
3
3 min
3 to 20 min
M
Time from when compressor stops to when it can restart
Start-Start Timer
2
40 min
15 to 60 min
M
Time from when compressor starts to when it can start again
Evap Recirculate Timer
1
30 sec
0.2 to 5 min
M
Time that evaporator pump must run before compressor start
NOTE:
In
Table 5
and in the rest of the Setpoint tables on the following pages, the letters in the Password column refer to the
following:
• O = Operator Level (the password number for operator level is 100)
• M = Manager Level (the password number for manager level is 2001)
• T = Technician Level (the password number for technician level is only provided to McQuay International technicians)
Содержание Magnitude C Vintage
Страница 4: ......
Страница 14: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 12 www DaikinApplied com Installation Figure 12 Wiring Index ...
Страница 15: ...www DaikinApplied com 13 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation ...
Страница 16: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 14 www DaikinApplied com Installation Figure 13 Controller Box Wiring ...
Страница 19: ...www DaikinApplied com 17 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation ...
Страница 67: ......