IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS
36 www.DaikinApplied.com
o
peraTIon
MOTOR Setpoint Screen
Figure 43: MOTOR Setpoint Screen
Table 9: MOTOR Setpoint Settings
Description
No .
Default
Range
Password
Comments
Nominal Capacity
10
100
0 to 9999 Tons
T
Determines when to shut off a compressor. ONLY applies to multi-chiller
setup.
Maximum LWT Rate
9
0.5 °F/min
0.1 to 5.0 °F/min
M
Inhibits loading if LWT change exceeds the setpoint value
Minimum LWT Rate
8
0.1 °F/min
0.1 to 5.0 °F/min
M
Additional compressor can start if LWT change is below setpoint
Soft Load Ramp Time
7
5 min
1 to 60 min
M
Time period to go from initial load point (% RLA) set in SP 5 to 100% RLA
Initial Soft Load Limit
6
40%
10 to 100%
M
Initial amps as % of RLA, Uses SP4 & 6
Soft Load Enable
5
OFF
OFF, ON
M
Soft load on or off, Uses SP6 & 7
Nameplate RLA *
4
Dependent on dataplate
T
RLA value from compressor nameplate
Maximum Amps
3
100%
10 to 100%
T
% RLA above which loading is inhibited (Load Limit) SP + 5% unloads
compressor
Minimum Amps
2
40%
5 to 80%
T
% RLA below which unloading is inhibited
Demand Limit Enable
1
OFF
OFF, ON
O
ON sets %RLA at 0% for 4 mA external signal and at 100% RLA for 20 mA
signal OFF – signal is ignored
NOTE:
Setpoints that have a technician level password (T) should only be changed by a McQuay International technician.
Contact a McQuay International service representative for more information.
CAUTION
* Chiller Nameplate RLA
MUST
match chiller dataplate per compressor.
Содержание Magnitude C Vintage
Страница 4: ......
Страница 14: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 12 www DaikinApplied com Installation Figure 12 Wiring Index ...
Страница 15: ...www DaikinApplied com 13 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation ...
Страница 16: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 14 www DaikinApplied com Installation Figure 13 Controller Box Wiring ...
Страница 19: ...www DaikinApplied com 17 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation ...
Страница 67: ......