IOM 1210-1 • MAGNITUDE
®
MODEL WMC CHILLERS
44 www.DaikinApplied.com
Possible Alarms and Events
There are three types of alarms: faults, problems, and warnings. In addition to these three alarms, there are also "events." See
the following tables for examples of faults, problems, warnings, and events that can occur. Separate tables are shown based on
whether the alarm source is the unit or the compressor.
NOTE:
In the "Alarm Reset" column of the following tables, itallics indicate special alarm conditions or severity. If the "Alarm
Reset" says "Auto-clears," it indicates that the alarm will auto-clear after the condition is resolved and the normal
condition returns.
Fault Alarms
Equipment protection faults cause rapid compressor shutdown. The compressor is stopped immediately (if the compressor was
running).
Table 12: Unit Fault Alarms
Description
OITS Alarm Message
Alarm Reset
Low Motor Current Comp 1
COMPR STOP - Motor Current Low
Auto-clears
Low Motor Current Comp 2
COMPR STOP - Motor Current Low
Auto-clears
No Condenser Water Flow
COMPR STOP - Condenser Water Flow Loss
Auto-clears
No Compressor Stop Comp 1
COMPR STOP - Current High with Compr OFF
Auto-clears
No Compressor Stop Comp 2
COMPR STOP - Current High with Compr OFF
Auto-clears
No Evaporator Water Flow
COMPR STOP - Evaporator Water Flow Loss
Auto-clears
Low Evaporator Pressure Circuit 1
COMPR STOP - Evaporator Pressure Low
Auto-clears
Low Evaporator Pressure Circuit 2
COMPR STOP - Evaporator Pressure Low
Auto-clears
Leaving Evaporator Water Temperature Sensor Fault Comp 1
COMPR STOP - Evap LWT Sensor Out of Range
Auto-clears
Surge High Suct SH-Running Comp 1
COMPR STOP - Surge Temperature
Auto-clears
Surge High Suct SH-Running Comp 2
COMPR STOP - Surge Temperature
Auto-clears
Expansion Alarm – FAULT (external alarm)
COMPR STOP - Control Fault (External Input)
Auto-clears
Check Valve Fault 1
CHILLER STOP - Check Valve Failure
Locked off (requires local reset)
Check Valve Fault 2
CHILLER STOP - Check Valve Failure
Locked off (requires local reset)
Содержание Magnitude C Vintage
Страница 4: ......
Страница 14: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 12 www DaikinApplied com Installation Figure 12 Wiring Index ...
Страница 15: ...www DaikinApplied com 13 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation ...
Страница 16: ...IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS 14 www DaikinApplied com Installation Figure 13 Controller Box Wiring ...
Страница 19: ...www DaikinApplied com 17 IOM 1210 1 MAGNITUDE MODEL WMC CHILLERS Installation ...
Страница 67: ......