A heavy-gauge, corrosion resistant wall sleeve is provided

for each unit. The wall sleeve is either shipped in a separate
carton or shipped in a multi-pack of 15.

Typical installation for masonry walls is shown in Figure 5.

The recommended installation procedure for this type of con-
struction is as follows:

1. Clean the opening of all debris that may interfere with

installation.

2. Be sure the unit’s center of gravity falls within the load

bearing surface of the wall. The center of gravity for the unit
is approximately 10

3

4

" (273mm) from the rear edge of the

wall sleeve. If the center of gravity is not within the load
bearing surface, then additional support such as wood, metal
or concrete must be provided in the field.

3. Place a thin pad of soft mortar on the bottom of the open-ing.

Important: Make certain the wall sleeve protrudes into the
room a minimum of 1

1

8

" (29mm) beyond the finished wall

surface to accommodate the heat section and room cabinet.
Be sure to recess the wall sleeve enough to accommodate
outside louver. This recess is 

3

8

" (9.5mm) for stamped

louvers and 1

1

4

" (32mm) for architectural louvers. The louver

should be flush to exterior surface when completed.

Wall Sleeve Installation — Thick Wall Construction

Figure 5. Wall sleeve installation using brickstops

4. If a brickstop is employed (as shown in Figure 5), slide the

wall sleeve into the wall until the brickstop contacts the
exterior bricks, as illustrated below. If a brickstop is not used,
slide the wall sleeve in the wall so that it extends into the room
a minimum of 1

1

8

" (29mm) beyond the finished interior wall

surface. This allows room to attach the heat section and
room cabinet. The wall sleeve should also be recessed
enough to accommodate the outside louver.

5. After the mortar has dried, remove the masonry support from

the wall sleeve. Note:  The wall sleeve is not intended to
replace the lintel.

6. Level wall sleeve in all directions and anchor with appropri-

ate fasteners (as shown in Figure 23, page 11). A 

5

16

" (8mm)

hole is provided on each side, 2" (51mm) down from the top
and 2" (51mm) in from the rear of the wall sleeve. It may
necessary to drill additional holes in the wall sleeve to firmly
secure it . Caution: Do not drill holes in the base of the wall
sleeve. Use shims between the wall and the wall sleeve to
prevent wall sleeve distortion during anchoring.

7. Caulk the wall sleeve to the wall opening on both the

in-side and outside perimeter using a resilient, nonhardening
caulk such as silicone. Be careful not to plug the weep holes.

Notes:
1. For dimensions B and D, see table on page 3.
2. Dimension “X” is  “as required” and is usually sent to the factory to be

welded during wall sleeve fabrication.

3. Caulk entire perimeter of wall sleeve after installation.
4.

Wall sleeve to extend a minimum of 1-1/4" past finished sheetrock.

5.

Wall sleeve should be installed recessed 1-1/4" from face of brick so
that when louver is installed it is flush with face of building.

D

Outside

Louver

B

1"

Finished Floor

Wall Sleeve

A

Wood Stool

Casement Window with
Insulating Clear Glass

2'-6

1

2

"

Exposed Projection
Concrete Slab

7-

1

4

"

Brick

1'-4"

4"

2'-4"

Brick

Room Cabinet

Optional

Continuous

Flange

Outside Edge

of Sleeve

Wall

Sleeve

D

X

Optional
Brickstops

42" (1067mm)

1

1

4

"

(32mm)

16"

(406mm)

Содержание Incremental PDNC Series

Страница 1: ...Incremental Comfort Conditioners Model PDNS PDNC With Top Mounted Hydronic Heat Installation Maintenance Data Group PTAC Part No 106018563 Date August 2005 IM 422 6 2005 McQuay International...

Страница 2: ...authorities having jurisdiction and all applicable codes It is the responsibility of the installer to determine and follow the applicable codes Sheet metal parts self tapping screws clips and such it...

Страница 3: ...ckness B A 11 4 32mm 27 8 67mm 16 406mm D 91 8 232mm 51 2 140mm 7 8 22mm 15 8 41mm 15 16 33mm 3 76mm Min Kickplate Height Standard Size Wall Sleeve Wall Opening Requirements Before installing the unit...

Страница 4: ...can be metal wood or concrete 3 Level wall sleeve in all directions and anchor with appro priate fasteners Use holes provided see Figure 23 page 11 or drill additional holes as required to secure fir...

Страница 5: ...he finished wall surface This is to accommodate the heat section and room cabinet The center of gravity is 103 4 273mm from the rear face of the standard wall sleeve If no subbase is being employed ad...

Страница 6: ...nds into the room a minimum of 11 8 29mm beyond the finished interior wall surface This allows room to attach the heat section and room cabinet The wall sleeve should also be recessed enough to accomm...

Страница 7: ...uding air vents steam traps stop balance valves etc as specified by the design engIneer 5 For valve installed on right side of the unit make electrical connection to matching cap extending from the co...

Страница 8: ...entire week Select a warmer or cooler setting any time to temporarily over ride any program setting Vacation hold overrides programming Clear backlit display makes it easy to see time temperature and...

Страница 9: ...8 to 30 VAC 1 amp maximum per terminal 4 amp maximum total load 60 minute power backup for clock Temperature Control Ranges 45 o F to 90 o F Accuracy 1 o F System Configurations Single stage heat sing...

Страница 10: ...and allows user to select specific mode of operation using only one button Temp Buttons Functions same as buttons on touch pad allowing user to change the setpoint Fan Speed Buttons High Low Performs...

Страница 11: ...w Figure 21 Programmable Thermostat Wires From Control Slave Unit Figure 22 Master slave with Programmable Thermostat Wires From Control Factory Supplied Low Voltage Plug Receptacle Disconnect Wires F...

Страница 12: ...bles the installer to keep a firm grasp on the louver when installing from inside the room 4 Push the louver through the opening at the rear of the wall box then pull the louver back to the wall sleev...

Страница 13: ...its are supplied with an attachment cord and plug which exit from the bottom of the conditioner on the control side The cord for 115V 208V and 230V has a usable length of 72 1829mm from where it exits...

Страница 14: ...remental conditioners are built to last With proper care the unitshouldprovideuninterruptedserviceformanyyears Sched uled maintenance of this equipment as described below is the key to the equipment s...

Страница 15: ...Part Name 100 Units Cooling Chassis 1 Compressor Overload Device 1 Compressor Running Capacitor 1 Evaporator Fan Motor 1 Condenser Fan Motor 1 Pushbutton Switch 2 Damper Switch 2 Thermostat 2 Knob for...

Страница 16: ...on COOL 2 Blowers operate on COOL but compressor doesn t start 3 Blowers run on COOL and compressor starts but stops after a short interval 4 Blowers run on COOL and compressor starts and runs but co...

Страница 17: ...wer assembly and tighten nuts d Noise will disappear after equipment runs awhile e Make necessary adjustments to components f Check for proper adjustment Apply silicone oil or grease to gap between so...

Страница 18: ...IM 422 Page 18 of 28 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Open Valve Model PDNS PDNC Thermostat Unit Heat Water Changeover Manual...

Страница 19: ...IM 422 Page 19 of 28 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Closed Valve Model PDNS PDNC Thermostat Unit Heat Steam Changeover Manual...

Страница 20: ...IM 422 Page 20 of 28 PDNS PDNC Wiring Diagram Unit Mounted Digital Touch Pad Control First Release...

Страница 21: ...IM 422 Page 21 of 28 Wiring Diagram PDNS PDNC Control Remote Thermostat N O Valve 24V...

Страница 22: ...IM 422 Page 22 of 28 Wiring Diagram PDNS PDNC Control Unit Mounted N O Valve 24V...

Страница 23: ...IM 422 Page 23 of 28 Wiring Diagram PDNS PDNC Chassis Wiring...

Страница 24: ...IM 422 Page 24 of 28 Wiring Diagram PDNS PDNC Control Remote Thermostat N C Valve 24V...

Страница 25: ...IM 422 Page 25 of 28 Wiring Diagram PDNS PDNC Unit Mounted Thermostat Manual Changeover N C Valve...

Страница 26: ...IM 422 Page 26 of 28 Wiring Diagram PDNS PDNC Control Unit Mounted with HFLO Fan Cycle on Heat N C Valve 24V...

Страница 27: ...IM 422 Page 27 of 28 Wiring Diagram PDNS PDNC Unit Mounted Thermostat Manual Changeover N C Valve...

Страница 28: ...ational www mcquay com 800 432 1342 IM 422 6 Page 28 of 28 Rev 8 05 This document contains the most current product information as of this printing For the most up to date product information please g...

Отзывы: