background image

IM 422 / Page 12 of 28

Installation of Cooling Chassis

Correct installation of the cooling chassis is extremely important
to insure the proper operation of the unit. Install the chassis as
follows:

1. Remove outer carton and inspect for any shipping damage.

Report any found to the carrier.

2. Check nameplate data on chassis to insure that the correct

job site distribution has been made with respect to cooling
capacities. Generally, corner rooms require larger capaci-
ties.

3. Remove chassis from carton by pulling evenly on substan-

tial portion of unit. Caution: Do not pull on evaporator fan
housing, control box or compressor.

4. If wall sleeve has been previously installed, remove tempo-

rary weather panel.

5. Check all fasteners to make certain they have not come

loose during shipment. Do not loosen nuts holding down
compressor; they are set at the factory.

6. Do not lubricate motors before start-up. Motors are factory

lubricated. Consult “Scheduled Maintenance” section on
page 14 for lubrication instructions.

7.

Place Tinnerman clips from bag onto wall sleeve. Clips and
mounting screws are enclosed in a bag attached to the top
of the condenser coil cover.

8.

If louver has not been previously installed, connect to wall
sleeve as described above.

9.

If louver is supplied by others, as illustrated in Figure 4,
page 5, be sure to install foam type gaskets on all sides of
the condenser coil to prevent recirculation or bypass of
condenser air.

10. Slide chassis into wall sleeve until firmly seated against

weather seals of wall sleeve. Caution: Do not push on coil
surface or control box cover. Make sure the com

pres

sor

tubing does not catch when inserting chassis.

Installation of Louvers

1. Remove louver from its shipping carton which also contains

a hardware package for mounting the louver.

2. Remove outside weather plug and weather panel from wall

sleeve.

3. Make a temporary handle by looping a piece of flexible wire

or heavy cord through the louver. This enables the installer
to keep a firm grasp on the louver when installing from inside
the room.

4. Push the louver through the opening at the rear of the wall

box, then pull the louver back to the wall sleeve flange so that
the louver studs pass through the holes in the flange.

5. Attach washers and nuts and secure louver in place.

6. If the cooling chassis is not to be immediately installed,

replace the weather panel.

Factory
Supplied
Holes (2)

Cooling
Chassis

Damper Actuator

Hydronic Heat Sect.

Wall Sleeve

Figure 24. Installing the Cooling Chassis

11. Secure chassis  to wall sleeve with four (4) sheet metal

screws packaged with the Tinnerman  clips.

12. Plug electrical cord into receptacle. Excess cord should be

coiled up neatly and stored in the conditioner.

13. Set the manual damper operator in open or closed position

as desired. On units equipped with the optional electric
fresh air damper, set the “Auto-Off” switch in the desired
position. In “Auto,” the damper is open whenever the indoor
fan motor is running. The “Auto-Off” switch is located on the
bottom front face of the control box.

14. Set cycle switch (located on the bottom front face of the

control box) for constant or cycle indoor fan. With the switch
in “Cycle” position, the indoor fan will shut off when the
thermostat de-energizes cooling or heating.

15. Set the temperature limiting device to the desired range of

thermostat operation. (See page 13 for details on tem-
perature limiting device.)

Anchoring

Anchoring the wall sleeve in the opening is accomplished as
shown in Figure 23. It is recommended that rubber isolation
washers be used with the fasteners to minimize sound
transmission from the equipment to the wall, at the point of con-
tact.

5

16

" (8mm) hole is provided on each side, 2" (51mm) down

from  the top and 2" (51mm) in from the rear of the wall sleeve.
It may be necessary to drill additional holes in the wall sleeve to
firmly secure it. Caution: Do not drill holes in the base of the wall
sleeve. Use shims between the wall and the wall sleeve to pre-
vent sleeve distortion during anchoring.

Expansion

Anchor

Bolt

Molly or

Toggle Bolt

Cripple Stud

Main Stud

Wood

Screw

Figure 23. Anchoring Method

Содержание Incremental PDNC Series

Страница 1: ...Incremental Comfort Conditioners Model PDNS PDNC With Top Mounted Hydronic Heat Installation Maintenance Data Group PTAC Part No 106018563 Date August 2005 IM 422 6 2005 McQuay International...

Страница 2: ...authorities having jurisdiction and all applicable codes It is the responsibility of the installer to determine and follow the applicable codes Sheet metal parts self tapping screws clips and such it...

Страница 3: ...ckness B A 11 4 32mm 27 8 67mm 16 406mm D 91 8 232mm 51 2 140mm 7 8 22mm 15 8 41mm 15 16 33mm 3 76mm Min Kickplate Height Standard Size Wall Sleeve Wall Opening Requirements Before installing the unit...

Страница 4: ...can be metal wood or concrete 3 Level wall sleeve in all directions and anchor with appro priate fasteners Use holes provided see Figure 23 page 11 or drill additional holes as required to secure fir...

Страница 5: ...he finished wall surface This is to accommodate the heat section and room cabinet The center of gravity is 103 4 273mm from the rear face of the standard wall sleeve If no subbase is being employed ad...

Страница 6: ...nds into the room a minimum of 11 8 29mm beyond the finished interior wall surface This allows room to attach the heat section and room cabinet The wall sleeve should also be recessed enough to accomm...

Страница 7: ...uding air vents steam traps stop balance valves etc as specified by the design engIneer 5 For valve installed on right side of the unit make electrical connection to matching cap extending from the co...

Страница 8: ...entire week Select a warmer or cooler setting any time to temporarily over ride any program setting Vacation hold overrides programming Clear backlit display makes it easy to see time temperature and...

Страница 9: ...8 to 30 VAC 1 amp maximum per terminal 4 amp maximum total load 60 minute power backup for clock Temperature Control Ranges 45 o F to 90 o F Accuracy 1 o F System Configurations Single stage heat sing...

Страница 10: ...and allows user to select specific mode of operation using only one button Temp Buttons Functions same as buttons on touch pad allowing user to change the setpoint Fan Speed Buttons High Low Performs...

Страница 11: ...w Figure 21 Programmable Thermostat Wires From Control Slave Unit Figure 22 Master slave with Programmable Thermostat Wires From Control Factory Supplied Low Voltage Plug Receptacle Disconnect Wires F...

Страница 12: ...bles the installer to keep a firm grasp on the louver when installing from inside the room 4 Push the louver through the opening at the rear of the wall box then pull the louver back to the wall sleev...

Страница 13: ...its are supplied with an attachment cord and plug which exit from the bottom of the conditioner on the control side The cord for 115V 208V and 230V has a usable length of 72 1829mm from where it exits...

Страница 14: ...remental conditioners are built to last With proper care the unitshouldprovideuninterruptedserviceformanyyears Sched uled maintenance of this equipment as described below is the key to the equipment s...

Страница 15: ...Part Name 100 Units Cooling Chassis 1 Compressor Overload Device 1 Compressor Running Capacitor 1 Evaporator Fan Motor 1 Condenser Fan Motor 1 Pushbutton Switch 2 Damper Switch 2 Thermostat 2 Knob for...

Страница 16: ...on COOL 2 Blowers operate on COOL but compressor doesn t start 3 Blowers run on COOL and compressor starts but stops after a short interval 4 Blowers run on COOL and compressor starts and runs but co...

Страница 17: ...wer assembly and tighten nuts d Noise will disappear after equipment runs awhile e Make necessary adjustments to components f Check for proper adjustment Apply silicone oil or grease to gap between so...

Страница 18: ...IM 422 Page 18 of 28 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Open Valve Model PDNS PDNC Thermostat Unit Heat Water Changeover Manual...

Страница 19: ...IM 422 Page 19 of 28 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Closed Valve Model PDNS PDNC Thermostat Unit Heat Steam Changeover Manual...

Страница 20: ...IM 422 Page 20 of 28 PDNS PDNC Wiring Diagram Unit Mounted Digital Touch Pad Control First Release...

Страница 21: ...IM 422 Page 21 of 28 Wiring Diagram PDNS PDNC Control Remote Thermostat N O Valve 24V...

Страница 22: ...IM 422 Page 22 of 28 Wiring Diagram PDNS PDNC Control Unit Mounted N O Valve 24V...

Страница 23: ...IM 422 Page 23 of 28 Wiring Diagram PDNS PDNC Chassis Wiring...

Страница 24: ...IM 422 Page 24 of 28 Wiring Diagram PDNS PDNC Control Remote Thermostat N C Valve 24V...

Страница 25: ...IM 422 Page 25 of 28 Wiring Diagram PDNS PDNC Unit Mounted Thermostat Manual Changeover N C Valve...

Страница 26: ...IM 422 Page 26 of 28 Wiring Diagram PDNS PDNC Control Unit Mounted with HFLO Fan Cycle on Heat N C Valve 24V...

Страница 27: ...IM 422 Page 27 of 28 Wiring Diagram PDNS PDNC Unit Mounted Thermostat Manual Changeover N C Valve...

Страница 28: ...ational www mcquay com 800 432 1342 IM 422 6 Page 28 of 28 Rev 8 05 This document contains the most current product information as of this printing For the most up to date product information please g...

Отзывы: