background image

 IM 422 / Page 13 of 28

Installing Room Cabinet

The room cabinet is the last piece to install. The following
instructions assume all components (wall sleeve, heat section,
louver and chassis) have been installed, piped and anchored.
All major room construction should also be complete so as not
to damage the room cabinet after it has been installed. Attach-
ing the room cabinet can be completed as follows:

1. Firmly grasp the room cabinet and lift it over the heat section.

There are notches in the back flanges of the room cabinet
that rest on the wall sleeve to assure it is centered.

2. Align the notches of the room cabinet on the wall sleeve and

firmly push the cabinet downward until it seats on the wall
sleeve (see Figure 25).

3. Screw the cabinet to the wall using the screws provided.

There are two (2) screw holes provided on each side located
on the inner flanges of the room cabinet.

4. Loosen the four (4) wing nuts on the kickplate and adjust the

kickplate the required distance to the floor.

5. Tighten the wing nuts firmly.

6. Wipe any smudges or dirt off the room cabinet using a mild

cleaner and a soft cloth.

All wiring should be in accordance with all local and National
Electrical Code requirements.

Units are supplied with an attachment cord and plug which

exit from the bottom of the conditioner on the control side. The
cord for 115V, 208V and 230V has a usable length of 72"
(1829mm) from where it exits the conditioner. The use of
extension cords to increase the length of the plug/cord set is not
recommended. Units to  operate on 265V are supplied with a

Electrical Service

14" (356mm) cord for connection to a subbase.

The attachment plug size should be used to determine the

circuit ampacity and overcurrent protection. Time delay,
overcurrent protection devices are recommended to prevent
unit damage and to avoid nuisance tripping.

Outlets are generally located beneath the conditioner, on

or recessed in the wall so it is concealed by the conditioner
overhang and kickplate.

Optional Adjusting Temperature Limiting Device

As an option, a temperature limiting device can be furnished to
allow the owner to set the minimum and/or maximum tempera-
ture selections. Adjust this device as follows:

1. Remove temperature knob and metal cover plate.

2. Loosen the hold-down screw with Phillips screwdriver.

3. Adjust cams to attain desired rotation limit.

4. Tighten hold-down screw.

5. Replace metal cover and temperature knob.

Once unit is in operation, rotate knob to maximum heat

and/or maximum cool to check temperature limits. Repeat
procedure listed above until desired temperature limitations
are achieved.

Figure 25.

Содержание Incremental PDNC Series

Страница 1: ...Incremental Comfort Conditioners Model PDNS PDNC With Top Mounted Hydronic Heat Installation Maintenance Data Group PTAC Part No 106018563 Date August 2005 IM 422 6 2005 McQuay International...

Страница 2: ...authorities having jurisdiction and all applicable codes It is the responsibility of the installer to determine and follow the applicable codes Sheet metal parts self tapping screws clips and such it...

Страница 3: ...ckness B A 11 4 32mm 27 8 67mm 16 406mm D 91 8 232mm 51 2 140mm 7 8 22mm 15 8 41mm 15 16 33mm 3 76mm Min Kickplate Height Standard Size Wall Sleeve Wall Opening Requirements Before installing the unit...

Страница 4: ...can be metal wood or concrete 3 Level wall sleeve in all directions and anchor with appro priate fasteners Use holes provided see Figure 23 page 11 or drill additional holes as required to secure fir...

Страница 5: ...he finished wall surface This is to accommodate the heat section and room cabinet The center of gravity is 103 4 273mm from the rear face of the standard wall sleeve If no subbase is being employed ad...

Страница 6: ...nds into the room a minimum of 11 8 29mm beyond the finished interior wall surface This allows room to attach the heat section and room cabinet The wall sleeve should also be recessed enough to accomm...

Страница 7: ...uding air vents steam traps stop balance valves etc as specified by the design engIneer 5 For valve installed on right side of the unit make electrical connection to matching cap extending from the co...

Страница 8: ...entire week Select a warmer or cooler setting any time to temporarily over ride any program setting Vacation hold overrides programming Clear backlit display makes it easy to see time temperature and...

Страница 9: ...8 to 30 VAC 1 amp maximum per terminal 4 amp maximum total load 60 minute power backup for clock Temperature Control Ranges 45 o F to 90 o F Accuracy 1 o F System Configurations Single stage heat sing...

Страница 10: ...and allows user to select specific mode of operation using only one button Temp Buttons Functions same as buttons on touch pad allowing user to change the setpoint Fan Speed Buttons High Low Performs...

Страница 11: ...w Figure 21 Programmable Thermostat Wires From Control Slave Unit Figure 22 Master slave with Programmable Thermostat Wires From Control Factory Supplied Low Voltage Plug Receptacle Disconnect Wires F...

Страница 12: ...bles the installer to keep a firm grasp on the louver when installing from inside the room 4 Push the louver through the opening at the rear of the wall box then pull the louver back to the wall sleev...

Страница 13: ...its are supplied with an attachment cord and plug which exit from the bottom of the conditioner on the control side The cord for 115V 208V and 230V has a usable length of 72 1829mm from where it exits...

Страница 14: ...remental conditioners are built to last With proper care the unitshouldprovideuninterruptedserviceformanyyears Sched uled maintenance of this equipment as described below is the key to the equipment s...

Страница 15: ...Part Name 100 Units Cooling Chassis 1 Compressor Overload Device 1 Compressor Running Capacitor 1 Evaporator Fan Motor 1 Condenser Fan Motor 1 Pushbutton Switch 2 Damper Switch 2 Thermostat 2 Knob for...

Страница 16: ...on COOL 2 Blowers operate on COOL but compressor doesn t start 3 Blowers run on COOL and compressor starts but stops after a short interval 4 Blowers run on COOL and compressor starts and runs but co...

Страница 17: ...wer assembly and tighten nuts d Noise will disappear after equipment runs awhile e Make necessary adjustments to components f Check for proper adjustment Apply silicone oil or grease to gap between so...

Страница 18: ...IM 422 Page 18 of 28 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Open Valve Model PDNS PDNC Thermostat Unit Heat Water Changeover Manual...

Страница 19: ...IM 422 Page 19 of 28 Wiring Diagram Standard Manual Changeover Control Hydronic Heat With Normally Closed Valve Model PDNS PDNC Thermostat Unit Heat Steam Changeover Manual...

Страница 20: ...IM 422 Page 20 of 28 PDNS PDNC Wiring Diagram Unit Mounted Digital Touch Pad Control First Release...

Страница 21: ...IM 422 Page 21 of 28 Wiring Diagram PDNS PDNC Control Remote Thermostat N O Valve 24V...

Страница 22: ...IM 422 Page 22 of 28 Wiring Diagram PDNS PDNC Control Unit Mounted N O Valve 24V...

Страница 23: ...IM 422 Page 23 of 28 Wiring Diagram PDNS PDNC Chassis Wiring...

Страница 24: ...IM 422 Page 24 of 28 Wiring Diagram PDNS PDNC Control Remote Thermostat N C Valve 24V...

Страница 25: ...IM 422 Page 25 of 28 Wiring Diagram PDNS PDNC Unit Mounted Thermostat Manual Changeover N C Valve...

Страница 26: ...IM 422 Page 26 of 28 Wiring Diagram PDNS PDNC Control Unit Mounted with HFLO Fan Cycle on Heat N C Valve 24V...

Страница 27: ...IM 422 Page 27 of 28 Wiring Diagram PDNS PDNC Unit Mounted Thermostat Manual Changeover N C Valve...

Страница 28: ...ational www mcquay com 800 432 1342 IM 422 6 Page 28 of 28 Rev 8 05 This document contains the most current product information as of this printing For the most up to date product information please g...

Отзывы: