background image

IM 1068 / Page 29 of 32

 

Trouble 

Cause 

Cure

d.  Refer to original load calculations; recalculate heat load.
e.  Close them.
f.  * Ship cooling chassis prepaid to nearest McQuay authorized 
  warranty station.

g.  * Ship cooling chassis prepaid to nearest McQuay authorized war-

ranty station.

a.  Adjust.
b.  Replace.

a.  Remove obstructions to water flow.
b.  Adjust or replace.
c.  Check for correct voltage. Oil motor if necessary.
d.  Adjust.

a.  Correct as in #1.
b.   Open heat valve or turn on heating system.
c.  Replace.
d.  Tighten.
e.  Adjust – rotate control knob to “Warmer”.

a.  Adjust fan position on motor shaft to reposition fan motor bracket
  assembly.
b.  Lubricate with SAE #19 oil or replace motor.
c.  Align blower assembly and tighten nuts.
d.  Noise will disappear after equipment runs awhile.
e.  Make necessary adjustments to components.
f.  Check for proper adjustment. Apply silicone oil or grease to gap 
  between solenoid and armature.
g.  Tighten.
h.  Fasten securely.
I.  Adjust by bending or applying tape.
j.  Occasionally equipment will have noisy operation for no apparent  

reason. Inspect ion has revealed no loose components that might 
be the source of the noise. Due to the action of the compressor, it 
is possible to have internal noise develop if the refrigerant tubing 
has become bent even slightly. To distinguish this condition from 
the simple rattle producing vibration caused by loose screws, nuts, 
and other components, grasp the refrigerant tubing at various points 
throughout the system until a point is found where the noise is 
eliminated or reduced. Bend the copper tubing very gently until the 
noise disappears.

k.  Tighten.

a.  Contact building management.
b.  Check power supply line fuses, circuit breakers. Blow fuses would 

indicate circuit overloading, a short circuit, or a grounded condition in 
the circuit.

c.  Replace.
d.  Replace wire or tighten.
e.  Adjust – rotate knob to “Warm”.
f.  Replace.
g.  Replace.
h.
  1) Temporarily lock valve open; replace.
  2) Replace.

8.  Insufficient cooling capacity
 

(continued).

9. Too much cooling.

10. “Sweating”

11. Blowers won't operate
  on Heat.

12. **Equipment is noisy.

13. Insufficient or no heat

d.  Heat load in room exceeds capacity of equipment.
e.  Windows and doors in room are open.
f.  Compressor not pumping, indicated by:
  1) Low wattage.
  2) Condenser not warm, evaporator only partially cool, or not at all.
g.  Restricted capillary tube or strainer, indicated by:
  1) Frost on capillary tube or strainer.
  2) Low wattage.
  3) Condenser not warm.
  4) Evaporator partially frosted, only partially cool, or not at all.

a.  Thermostat set too low.
b.  Defective thermostat.

a.  Condensate drain from evaporator to condenser plugged.
b.  Insulating seals on equipment damaged.
c.  Evaporator blower motor not up to speed.
d.  Evaporator blower incorrectly positioned.

a.  No power.
b.  Heat is off (equipment with heat fan lockout).
c.  Faulty push-button switch.
d.  Loose connections at push-button switch.
e.  Thermostat set too low.

a.  Blower rubbing against enclosure.

b.  Blower motor bearings are dry.
c.  Loose blower hold-down nuts on motor-bracket assembly.
d.  Refrigerant absorbed in compressor oil after extended shutdown.
e.  Equipment improperly installed.
f.  Damper solenoid hums.

g.  Loose terminal box cover on side of compressor.
h.  Loose electrical components.
i.  Copper tubing vibrating.
j.  Harmonics.

k.  Loose sheet metal parts.

a.  No steam or hot water being applied.
b.  No Power.

c.  Faulty push-button switch.
d.  Loose connection at push-button switch.
e.  Thermostat set too high.
f.  Thermostat faulty.
g.  No power output on transformer secondary.
h.  In-operative valve.
  1) Steam valve normally closed.
  2) Hot water valve normally closed. 

Troubleshooting Chart

These items should be checked by a qualified service technician only.

Содержание Incremental Packaged Terminal

Страница 1: ...Incremental Packaged Terminal Air Conditioner Incremental Room Conditioner with R 410A Refrigerant Group PTAC Part No 669729001 Date March 2010 Installation Maintenance Data IM 1068 2010 McQuay Intern...

Страница 2: ...thisequipmentshallbeinaccordancewiththe regulations of authorities having jurisdiction and all applicable codes It is the responsibility of the installer to determine and follow the applicable codes S...

Страница 3: ...9000 Voltage A 115 60 1 C 208 60 1 G 230 60 1 J 277 265 60 1 S 208 115 60 1 R 265 115 60 1 Coil Options Z None Heating Options 35 2 5 kW nominal 41 3 5 kW nominal 44 4 0 kW nominal 48 5 0 kW nominal 5...

Страница 4: ...floor line to clear obstructions Without cabinet modifications the wall box can be placed up to 1 25mm abovethefloor Thestandardadjustablekickplatecan be telescoped to hide the space below the wall b...

Страница 5: ...nstructions will vary by depth of wall but not by wall material Do not remove the weather panel at any time during the installation of the wall box Premature removal of this panel could result in impr...

Страница 6: ...e Type K cooling chassis but packaged and shipped separately Check the heat section carton label and the unit s nameplate to ensure it is correct for the cooling chassis and the space The following st...

Страница 7: ...exposed water or steam lines that are located within the room cabinet Failure to do this may cause erratic operation of the thermostat 10 Protect the heat section from damage during construction Do n...

Страница 8: ...turn piping for steam or hot water is supplied from right hand side only Hot water must be supplied to the bottom of the coil and steam to the top of the coil 2 To simplify the steam or hot water conn...

Страница 9: ...e condenser fan wheel to be sure that there is no interference or looseness If it is loose tighten the setscrew located over the center of the flat on the motor shaft Do not lubricate condenser fan mo...

Страница 10: ...e the equipment is connected to the proper power supply and that proper fusing is used 2 In cases where a number of conditioners are to be installed single circuits should be provided for each machine...

Страница 11: ...H Edge of Wall Box Long Control Box Cool Chassis Power Cord Heat Section Power Cord Wall Box End View w o Cabinet B A H D F G 91 4 203 mm Figure 13 Electric Heat Section Size 019 Notes Guest room con...

Страница 12: ...Sizes 007 012 The hydronic heat section can be supplied with a short 4 high control box or a long 13 high control box depending on the number of options selected Observe the control box to determine w...

Страница 13: ...ion B The long control box is used with optional special controls such as Guest Room Control GRC Night Setback NSB and remote thermostats Note Left hand piping must be used with the long control box d...

Страница 14: ...at section and cool chassis and push the cabinet firmly against the wall The discharge grille seals should rest on the discharge opening of the heat section For unit size 019 Position the room cabinet...

Страница 15: ...Start up Initial start up of the McQuay equipment by an experienced person is usually the responsibility of the installing contractor This consists of inspecting and operating the equipment for all f...

Страница 16: ...slave unit as shown in Figure 22 The master unit is furnished with a 50 VA transformer that is capable of handling up to 7 slave units If additional slave units are to be added a larger field supplie...

Страница 17: ...Setback NSB R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transform...

Страница 18: ...P4 Plug on Master Wire Harness P5 Plug on Master Wire Harness R1 Relay Run R2 Relay Outdoor Fan Motor R3 Relay Cooling R4 Relay Indoor Fan Motor R5 Relay Heating 1st Stage R6 Relay Heating 2nd Stage...

Страница 19: ...R4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Term...

Страница 20: ...Master Wire Harness R1 Relay Run R2 Relay Outdoor Fan Motor R3 Relay Cooling R4 Relay Indoor Fan Motor R5 Relay Heating 1st Stage R6 Relay Heating 2nd Stage R7 Relay Night Setback NSB R9 Relay Hot Wa...

Страница 21: ...4 Relay Guest Room Control GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Termin...

Страница 22: ...n Master Wire Harness R1 Relay Run R2 Relay Outdoor Fan Motor R3 Relay Cooling R4 Relay Indoor Fan Motor R5 Relay Heating 1st Stage R6 Relay Heating 2nd Stage R7 Relay Night Setback NSB R9 Relay Hot W...

Страница 23: ...ol GRC R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal Board 24...

Страница 24: ...Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Terminal...

Страница 25: ...R5 Relay Hot Water Valve R6 Relay Control R7 Relay Night Setback NSB S1 Control Switch S2 Fan Speed Switch S3 Fan Cycle Switch S4 Damper Switch T1 Transformer TB1 Terminal Block Control Box TB2 Termin...

Страница 26: ...oil lightly to enhance dust collecting ability The Type K is also available with a carbon filter a zeolite filter or electrostatic filter The electrostatic filter is renewable by rinsing with hot wate...

Страница 27: ...fective part can then be returned to McQuay International or one of its authorized service stations So long as it is still in warranty it is repaired or replaced and returned to the owner without cost...

Страница 28: ...a short interval 4 Blowers run on Cool and compressor starts and runs but compressor occasionally stops on overload device 5 Compressor starts and runs on Cool but blowers do not run 6 Compressor star...

Страница 29: ...a short circuit or a grounded condition in the circuit c Replace d Replace wire or tighten e Adjust rotate knob to Warm f Replace g Replace h 1 Temporarily lock valve open replace 2 Replace 8 Insuffic...

Страница 30: ...Control Size 007 65 lbs Size 009 65 lbs Size 012 65 lbs Size 019 77 lbs Electric Heat Section With Control Size 007 60 lbs Size 009 60 lbs Size 012 60 lbs Size 019 70 lbs Wall Box With Rear Extension...

Страница 31: ...IM 1068 Page 31 of 32...

Страница 32: ...ranty details Refer to Form 933 43285Y To find your local McQuay Representative go to www mcquay com This document contains the most current product information as of this printing For the most up to...

Отзывы: