background image

 IM 882 / Page 7 of 36

Wall Opening Requirements

When roughing in the opening for the wall sleeve, make 

certain there is sufficient clearance from the walls and 

floor. The wall sleeve should be positioned a minimum of 

5/8" in from the room side finished wall to accommodate 

the room cabinet. A minimum distance of 3" above the 

finished floor is required for return air.

The rough opening should measure 16¼" high x 42¼" 

wide. Before installing the unit, check the wall opening 

to be sure the wall sleeve will slide into the opening 

unobstructed. For masonry walls, a lintel must be used to 

provide support over each opening.

When using a louver frame, the opening must measure 

16

5

/

8

" x 42

5

/

8

". Louver frames should be used for 

panel wall and thin wall applications to assure positive 

anchoring to the wall (Figure 4). 

The opening must start 4" above the finished floor 

(including carpeting) to provide proper return air. 

Louver Frame Installation

When a louver frame is used, it must be installed prior 

to, or at the same time, as the wall sleeve, and it must be 

level and square.
1.  Apply caulking compound on the surfaces of the lou-

ver frame’s four flanges which will come in contact 

with the wall. Add caulking as required for weather 

tight seal.

2.  Insert the sleeve of the louver frame into the wall 

opening from the exterior of the building and apply 

firm pressure so that the caulked frame flanges are 

snug against the exterior of the building. Secure the 

louver frame to the wall if desired.

3.  Secure the louver frame to the wall through the sides 

and top. Never secure the frame through the bottom 

as it may cause leaks.

If the louver frame is to be installed in a panel wall, it 

should be installed at the same time as the wall sleeve.

   

WARNING

 

  Residential and institutional cleaning compounds can cause 

permanent damage to the packaged terminal unit. To avoid 

damage to unit controls and heat transfer surfaces, do not 

spray cleaning compounds onto the discharge grille, return 

air opening, or unit controls. Normal cleaning can be accom

-

plished by wiping the unit surface with a damp cloth. When 

using cleaning compounds on carpets, floors or walls, turn 

the unit off to avoid drawing potentially damaging vapors into 

the package terminal unit. 

Wall Sleeve Extension Installation

Wall sleeve extensions are shipped in a separate carton 

and tagged to match the proper unit. Be sure to check 

tagging of the extension against that of the unit. Install 

the wall sleeve extension as follows:

1.   Position the extension with standard wall sleeve  

 

 

so proper alignment with drain and mounting holes is  

 

achieved.

2.  Place a bead of caulk around the perimeter of the    

 

wall sleeve and another bead around the mating  

 

 

side of the wall sleeve extension so that the joint  

 

 

is watertight. Do not permit caulking to block the    

 

weep holes. Be sure to use a resilient caulking such    

 

as silicone.

3.  Assemble the wall sleeve extension to the wall  

 

 

sleeve. Clean out weep holes to assure proper  

 

 

drainage.

4.  Continue wall sleeve installation according to  

 

 

instructions on page 8.

Figure 5. Wall Sleeve Extension

Wall Sleeve Extension

6

7

/

8

"

11

1

/

8

"

2"

Room Side

Air Splitters

As Required

2" 

16

2" 

2

3

/

16

"

16

3

/

16

"

3

3

/

"

3

/

16

"

18

3

/

16

"

Figure 4. Louver Frame Dimensions

Note:

  Wall Sleeve rough opening when using a Louver Frame must 

be 16

5

/

8

" x 42

5

/

8

"

DO NOT drill holes in the bottom of the wall sleeve as it will 

cause leaks.

 

CAUTION

Содержание IM 938-1

Страница 1: ...Installation Maintenance Data Group PTAC Part No 668109501 Date January 2008 IM 882 2008 McQuay International Applied Packaged Terminal Air Conditioner 16 x 42 PDAC PDHP With Top Mounted Hydronic Heat...

Страница 2: ...at Section 13 Installation of Room Cabinet 14 Supply and Return Coil Arrangements 14 Controls PDAC PDHP Digital Touchpad Control 15 19 Inputs Outputs 15 Keys and Indicators Labels 15 Display Function...

Страница 3: ...be damaged in transit due to rough handling even though the carton may not show external damages When the damage is discovered upon unpacking make a written request for inspection by the carrier s ag...

Страница 4: ...lectric Heat H Hydronic A Hydronic w Intermediate Electric Y None PDHP only Electric Heat A 2 5 Kw B 3 5 Kw C 5 0 Kw Y None Hydronic Heat Type S Steam Top Mount Normally Closed T Steam Subbase Normall...

Страница 5: ...ew or existing buildings The Figure 1 Exploded View of the 16 x 42 PDAC PDHP with Top Mounted Hydronic Unit self contained refrigerant system delivers cooling to the desired space Heating can be accom...

Страница 6: ...4 273 143 4 375 133 4 143 4 349 375 103 4 273 153 4 400 143 4 153 4 375 400 103 4 273 163 4 425 153 4 163 4 400 425 103 4 273 173 4 451 163 4 173 4 425 451 Note Electrical rough in should be located b...

Страница 7: ...it may cause leaks If the louver frame is to be installed in a panel wall it should be installed at the same time as the wall sleeve WARNING Residential and institutional cleaning compounds can cause...

Страница 8: ...propriatefasteners Useholesprovided seeFigure15 page 12 or drill additional holes as required to secure firmly CAUTION Do not drill holes in the base of the wall sleeve Use shims between the wall and...

Страница 9: ...eat Coil Section 3 1 2 Thick Batt Insulation 1 5 8 Metal Stud 16 O C Window Stool Insulation Wet Panel 16 11 4 42 Outdoor Side of Sleeve X 63 8 Optional Leveling Leg 13 3 4 X D Figure 11 16 x 42 wall...

Страница 10: ...of all debris that may interfere with installation Figure 12 Wall sleeve installation using top angles and field supplied continuous louver 133 4 349mm 11 4 38mm Insulated Panel Optional Top Angle 16...

Страница 11: ...heat section and room cabinet The wall sleeve should also be recessed enough to accom modate the outside louver Level wall sleeve side to side and pitch to outside 1 8 ft to assure proper sleeve drai...

Страница 12: ...g the wall sleeve in the opening is accomplished asshowninFigure15 Itisrecommendedthatrubberisola tion washers be used with the fasteners to minimize sound transmission from the equipment to the wall...

Страница 13: ...uto mode it will cycle the indoor fan when there is a call for heating or cooling See page 28 for jumper placement details 15 Set the temperature limiting feature to the desired range of thermostat op...

Страница 14: ...omplete so as not to damage the room cabinet after it has been installed Attaching the room cabinet can be com pleted as follows 1 Firmly grasp the room cabinet and lift it over the heat section There...

Страница 15: ...tton Remote must be aimed in a line of sight of the window in upper right corner on the front panel at less than a 45o angle from center of the window The control board will beep when any button is pr...

Страница 16: ...compressor and condenser fan shall turn on when Y signal is high 3 Cold start feature see Modes of Operation Cold Start Cool dry mode see Cold Dry Mode and Sleep feature see Sleep Feature are not avai...

Страница 17: ...higher than the set point It will stop if the space temperature sensor is 2 F or lower than the set point subject to timing requirements In the Cool Mode the indoor fan will operate according to the...

Страница 18: ...room temperature and the set point is less than 2 F This will also occur after a Cold Start or a Mode change from Cool to Cool Dry During this time the fan will operate in the Mode and Speed selected...

Страница 19: ...ll not operate In single motor units the outdoor fan will run along with the indoor fan Control Board Configuration To enter the Configuration Mode simultaneously press the Up and Down buttons for 5 s...

Страница 20: ...reaches 30 F and stays there for at least five 5 minutes 3 The compressor has run for at least 90 seconds Sleep Timer is overridden during this operation Anti freeze Protection is active in all modes...

Страница 21: ...Found _ __________________________________________________________________ _______________________________________________________________________________________ _____________________________________...

Страница 22: ...s equipment After the equipment leaves the factory it may become damaged or maladjusted during transportation or on the job Sometimes wires are disconnected accidentally or fan motors move on their ba...

Страница 23: ...mode However the control pad LED display will indicate the mode of operation and the room temperature Controls Premium Programmable Digital Touchpad Control Operating Instructions LED with Program Set...

Страница 24: ...by pressing Mode button 2 1 Once in the configuration mode the default temperature scale will be displayed as shown below Toggle the temperature scale to degree Celsius by pressing either or button 2...

Страница 25: ...thermostat for each period of the day repeat steps 3 3 through 3 7 Further the thermostat can be programmed for each individual day of the week or use the SimplesetTM feature as described below 3 9 S...

Страница 26: ...le stage heat single stage cool or single stage electric heat pump Terminations RC RH C W Y O B G Controls Remote Wall Mounted Thermostats Wall mounted thermostats are available for the Applied PTAC u...

Страница 27: ...urns off Vacation hold overrides programming Lockout feature prevents unwanted tampering Clear backlit display makes it easy to see time temperature and setpoint even in the dark No batteries required...

Страница 28: ...emote mounted thermostats should be wired as shown in Figure 30 Other considerations for this arrangement are as follows 1 When wiring the low voltage plug and receptacle disconnect provide enough wir...

Страница 29: ...y the room temperature 3 Jumper Placement to Select Controller Type A Place jumper across LUI to select unit mounted touchpad Local User Interface B Place jumper across SEC Secondary to select Control...

Страница 30: ...otor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface REV Re...

Страница 31: ...ssor Motor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface...

Страница 32: ...removal system and assure proper operation Pour at least two 2 cups of water into evaporator drain pan and verify proper operation Clean condensate drain and clear weep holes located at the bottom re...

Страница 33: ...ion of the rest of the system A further advantage is that a failed part can be quickly and easily replaced thus minimizing the inoperative time of the equipment This is so however only if a replacemen...

Страница 34: ...rees below minimum setpoint limit LA Low Ambient Lockout Outdoor air temperature is below 35 F Fault and Protection Codes for Applied PTAC PTHP Control Board Fault code Description Cause for the fault...

Страница 35: ...tructed discharge grilles 5 Evaporator blower motor not running 6 Evaporator blower motor not up to speed 7 Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipment e...

Страница 36: ...e oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Occasionally equipment will have noise for no ap parent reason Inspection has revealed no loose components that might...

Отзывы: