background image

IM 882 / Page 32 of 36

Maintenance (Scheduled)

Incremental conditioners are built to last. With proper 

care, the unit should provide uninterrupted service for 

many years. Scheduled maintenance of this equipment as 

described below is the key to the equipment’s longevity.
A.  Air filters must be cleaned at regular intervals.  

 

 

Twice annually may be adequate in some areas  

 

 

while twice monthly may be required in others.  

 

 

Areas with high dirt and lint content or heavy  

 

 

usage of units require more frequent filter    

 

 

maintenance than those areas of relatively clean  

 

 

operating or low usage conditions. Unit  

 

  

 

malfunction will occur if air filters are not kept  

 

 

clean. Rinse filter with hot water and a mild   

 

 

detergent.

B.   McQuay recommends that every year the chassis    

 

be removed for a thorough checkup. This should  

 

 

be completed as follows:

1.   Unplug unit from power source.

2.   Remove front panel.

3.   Remove chassis from cabinet and move it to the  

 

 

maintenance department. Replace with spare  

 

 

chassis or weather plate.

4.   Check all seals and insulation and repair as    

 

 

required.

5.  Check all wiring and controls for hazardous   

 

 

conditions.

6.   Thoroughly clean discharge grilles.

7.   Cover motors and control module with water tight    

 

material and wash evaporator coil, condenser coil    

 

and base pan using hot water and a mild soap.

CAUTION

Residential and institutional cleaning compounds can cause 

permanent damage to the packaged terminal unit. To avoid 

damage to unit controls and heat transfer surfaces, do 

not spray cleaning compounds onto the discharge grille, 

return air opening, or unit controls. Normal cleaning can 

be accomplished by wiping the unit surface with a damp 

cloth. When using cleaning compounds on carpets, floors or 

walls, turn the unit off to avoid drawing potentially damaging 

vapors into the package terminal unit.

8.   Check condensate removal system and assure  

 

 

proper operation. Pour at least two (2) cups of  

 

 

water into evaporator drain pan and verify proper    

 

operation. Clean condensate drain and clear weep    

 

holes located at the bottom rear of wall sleeve.

9.   Dry equipment thoroughly, especially electric  

 

 

parts and installation. 

10. Clean any rust spots with steel wool and paint with    

 

rust inhibiting paint.

11.  Clean insulation or replace if necessary.

12.  Check insulation on refrigeration piping and  

 

 

replace if necessary.

13.  Check all fasteners and tighten as required.

14.  Clean and oil damper door and linkage.

15.  Test run chassis before reinstalling.

Equipment Protection From The

Environment

The metal parts of this unit may be subject to rust or 

deterioration in adverse environmental conditions. This 

oxidation could shorten the equipment’s useful life. Salt 

spray, fog or mist in seacoast areas, sulphur or chlorine 

from lawn watering systems, and various chemical 

contaminants from industries such as paper mills and 

petroleum refineries are especially corrosive.

If the unit is to be installed in an area where 

contaminants are likely to be a problem, special 

attention should be given to the equipment location 

and exposure.

1   Avoid having lawn sprinkler heads spray directly in 

or on the outdoor louver.

2   In coastal areas, the units must have the corrosion 

protection package to maintain the warranty 

coverage.

Regular maintenance will reduce the buildup of 

contaminants and help to protect the outdoor section 

of the unit.

1   Frequent washing of the outdoor section,    

 

 

condenser fan blade and condenser coil with  

 

 

fresh water will remove most of the salt or other  

 

 

contaminants that build up in the outdoor section    

 

of the unit

2   Regular cleaning of the cabinet with a good non- 

 

 

abrasive polish will provide protection and keep it    

 

in good condition.

3   A mild liquid cleaner may be used several times a 

year to remove matter that will not wash off with 

water.

The best protection is frequent cleaning, maintenance 

and minimal exposure to contaminant.

Содержание IM 938-1

Страница 1: ...Installation Maintenance Data Group PTAC Part No 668109501 Date January 2008 IM 882 2008 McQuay International Applied Packaged Terminal Air Conditioner 16 x 42 PDAC PDHP With Top Mounted Hydronic Heat...

Страница 2: ...at Section 13 Installation of Room Cabinet 14 Supply and Return Coil Arrangements 14 Controls PDAC PDHP Digital Touchpad Control 15 19 Inputs Outputs 15 Keys and Indicators Labels 15 Display Function...

Страница 3: ...be damaged in transit due to rough handling even though the carton may not show external damages When the damage is discovered upon unpacking make a written request for inspection by the carrier s ag...

Страница 4: ...lectric Heat H Hydronic A Hydronic w Intermediate Electric Y None PDHP only Electric Heat A 2 5 Kw B 3 5 Kw C 5 0 Kw Y None Hydronic Heat Type S Steam Top Mount Normally Closed T Steam Subbase Normall...

Страница 5: ...ew or existing buildings The Figure 1 Exploded View of the 16 x 42 PDAC PDHP with Top Mounted Hydronic Unit self contained refrigerant system delivers cooling to the desired space Heating can be accom...

Страница 6: ...4 273 143 4 375 133 4 143 4 349 375 103 4 273 153 4 400 143 4 153 4 375 400 103 4 273 163 4 425 153 4 163 4 400 425 103 4 273 173 4 451 163 4 173 4 425 451 Note Electrical rough in should be located b...

Страница 7: ...it may cause leaks If the louver frame is to be installed in a panel wall it should be installed at the same time as the wall sleeve WARNING Residential and institutional cleaning compounds can cause...

Страница 8: ...propriatefasteners Useholesprovided seeFigure15 page 12 or drill additional holes as required to secure firmly CAUTION Do not drill holes in the base of the wall sleeve Use shims between the wall and...

Страница 9: ...eat Coil Section 3 1 2 Thick Batt Insulation 1 5 8 Metal Stud 16 O C Window Stool Insulation Wet Panel 16 11 4 42 Outdoor Side of Sleeve X 63 8 Optional Leveling Leg 13 3 4 X D Figure 11 16 x 42 wall...

Страница 10: ...of all debris that may interfere with installation Figure 12 Wall sleeve installation using top angles and field supplied continuous louver 133 4 349mm 11 4 38mm Insulated Panel Optional Top Angle 16...

Страница 11: ...heat section and room cabinet The wall sleeve should also be recessed enough to accom modate the outside louver Level wall sleeve side to side and pitch to outside 1 8 ft to assure proper sleeve drai...

Страница 12: ...g the wall sleeve in the opening is accomplished asshowninFigure15 Itisrecommendedthatrubberisola tion washers be used with the fasteners to minimize sound transmission from the equipment to the wall...

Страница 13: ...uto mode it will cycle the indoor fan when there is a call for heating or cooling See page 28 for jumper placement details 15 Set the temperature limiting feature to the desired range of thermostat op...

Страница 14: ...omplete so as not to damage the room cabinet after it has been installed Attaching the room cabinet can be com pleted as follows 1 Firmly grasp the room cabinet and lift it over the heat section There...

Страница 15: ...tton Remote must be aimed in a line of sight of the window in upper right corner on the front panel at less than a 45o angle from center of the window The control board will beep when any button is pr...

Страница 16: ...compressor and condenser fan shall turn on when Y signal is high 3 Cold start feature see Modes of Operation Cold Start Cool dry mode see Cold Dry Mode and Sleep feature see Sleep Feature are not avai...

Страница 17: ...higher than the set point It will stop if the space temperature sensor is 2 F or lower than the set point subject to timing requirements In the Cool Mode the indoor fan will operate according to the...

Страница 18: ...room temperature and the set point is less than 2 F This will also occur after a Cold Start or a Mode change from Cool to Cool Dry During this time the fan will operate in the Mode and Speed selected...

Страница 19: ...ll not operate In single motor units the outdoor fan will run along with the indoor fan Control Board Configuration To enter the Configuration Mode simultaneously press the Up and Down buttons for 5 s...

Страница 20: ...reaches 30 F and stays there for at least five 5 minutes 3 The compressor has run for at least 90 seconds Sleep Timer is overridden during this operation Anti freeze Protection is active in all modes...

Страница 21: ...Found _ __________________________________________________________________ _______________________________________________________________________________________ _____________________________________...

Страница 22: ...s equipment After the equipment leaves the factory it may become damaged or maladjusted during transportation or on the job Sometimes wires are disconnected accidentally or fan motors move on their ba...

Страница 23: ...mode However the control pad LED display will indicate the mode of operation and the room temperature Controls Premium Programmable Digital Touchpad Control Operating Instructions LED with Program Set...

Страница 24: ...by pressing Mode button 2 1 Once in the configuration mode the default temperature scale will be displayed as shown below Toggle the temperature scale to degree Celsius by pressing either or button 2...

Страница 25: ...thermostat for each period of the day repeat steps 3 3 through 3 7 Further the thermostat can be programmed for each individual day of the week or use the SimplesetTM feature as described below 3 9 S...

Страница 26: ...le stage heat single stage cool or single stage electric heat pump Terminations RC RH C W Y O B G Controls Remote Wall Mounted Thermostats Wall mounted thermostats are available for the Applied PTAC u...

Страница 27: ...urns off Vacation hold overrides programming Lockout feature prevents unwanted tampering Clear backlit display makes it easy to see time temperature and setpoint even in the dark No batteries required...

Страница 28: ...emote mounted thermostats should be wired as shown in Figure 30 Other considerations for this arrangement are as follows 1 When wiring the low voltage plug and receptacle disconnect provide enough wir...

Страница 29: ...y the room temperature 3 Jumper Placement to Select Controller Type A Place jumper across LUI to select unit mounted touchpad Local User Interface B Place jumper across SEC Secondary to select Control...

Страница 30: ...otor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface REV Re...

Страница 31: ...ssor Motor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface...

Страница 32: ...removal system and assure proper operation Pour at least two 2 cups of water into evaporator drain pan and verify proper operation Clean condensate drain and clear weep holes located at the bottom re...

Страница 33: ...ion of the rest of the system A further advantage is that a failed part can be quickly and easily replaced thus minimizing the inoperative time of the equipment This is so however only if a replacemen...

Страница 34: ...rees below minimum setpoint limit LA Low Ambient Lockout Outdoor air temperature is below 35 F Fault and Protection Codes for Applied PTAC PTHP Control Board Fault code Description Cause for the fault...

Страница 35: ...tructed discharge grilles 5 Evaporator blower motor not running 6 Evaporator blower motor not up to speed 7 Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipment e...

Страница 36: ...e oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Occasionally equipment will have noise for no ap parent reason Inspection has revealed no loose components that might...

Отзывы: