background image

 IM 882 / Page 13 of 36

Factory

Supplied

Holes (2)

Cooling

Chassis

Damper 

Actuator

Hydronic Heat Section

Wall Sleeve

Figure 16. Installing the Cooling Chassis and Hydronic 

Heat Section

6.  Do not lubricate motors before start-up. Motors are 

factory lubricated. Consult “Scheduled Maintenance” 

section on page 31 for lubrication instructions.

7.  Place Tinnerman clips from bag onto wall sleeve. 

Clips and mounting screws are enclosed in a bag 

attached to the top of the condenser coil cover.

8.  If louver has not been previously installed, connect 

to wall sleeve as described above.

9.  If louver is supplied by others, as illustrated in 

Figure 12, page 10, be sure to install foam type 

gaskets on all sides of the condenser coil to prevent 

recirculation or bypass of condenser air.

10.  Slide chassis into wall sleeve until firmly seated 

against weather seals of wall sleeve. 

Caution:

 Do 

not push on coil surface or control box cover. Make 

sure the compressor tubing does not catch when 

inserting chassis.

11.  Secure chassis to wall sleeve with four (4) sheet 

metal screws packaged with the Tinnerman clips.

12.  Plug electrical cord into receptacle. Excess cord 

should be coiled up neatly and stored in the 

conditioner.

13.  Set the manual damper operator in open or closed 

position as desired. On units equipped with the 

optional electric fresh air damper, set for “AU” 

or "CL" in the Configuration Mode. In “AU,” the 

damper is open whenever the indoor fan motor is 

running (AU is Auto and CL is Closed).

14.  Set the indoor fan mode for off cycle on the PC 

board for the off cycle selection of 10, 20, 30 

minutes or 1 hour off cycle time. The fan will operate 

for 2 minutes and shut down for the selected off 

cycle period. For continuous fan operation, the fan 

mode selection on the touchpad or remote thermostat 

must be set to continuous or on. When the room 

thermostat is in the cycle or auto mode, it will cycle 

the indoor fan when there is a call for heating or 

cooling. See page 28 for jumper placement details.

15.  Set the temperature limiting feature to the desired  

range of thermostat operations. As shipped, the  

range is 60°F to 85°F.

16.  Replace the air filter and front panel.

17.  Connect the low voltage valve wires with the 

 

Molex connection to the valve.

Heat Section Installation

The heat section is designed to be “snapped” into the top 

of the wall sleeve (Figure 16). There are four square holes 

provided in the wall sleeve, two on each side, for coil at-

tachment. Assembly the heat section to the wall sleeve as 

follows:

1.  Unpack the heat section and inspect for any shipping 

 

damage. Report any damage found to the carrier.

2.  Check the heat section against the plans to make certain 

the coil supplied has the connections match the specifica-

tions.

3.  Firmly attach the heat section to the wall sleeve by lining 

up the heat section hooks with the square holes supplied 

in the wall sleeve. Snap the heat section in place by 

exerting pressure downward.

4.  The valve is always connected to the supply side of 

the coil. There are seven possible coil arrangements 

available. Each is shown on the next page. Select the 

illustration below that matches the coil supplied and pipe 

it according to the illustration. Install valve and other 

accessories including air vents, steam traps, stop balance 

valves, etc., as specified by the design engineer.

5.  For valve installed on right side of the unit, make elec-

trical connection to matching cap extending from the 

control box. For left side valve, make electrical connec-

tion to cap mounted to left side of chassis.

Note:

 When the heating medium is steam, the supply 

 

  connection should be attached to the uppermost tube    

  and  the return to the lower tube. The coil is pitched in the 

 

  casing to allow drainage of condensate. 

When  the  heating  medium  is  hot  water,  the  supply 

 

  connection should be made to the lowermost tube and  

  the return to the uppermost tube. Hot water coils  

 

  should be “flooded” to minimize air entrapment.

Содержание IM 938-1

Страница 1: ...Installation Maintenance Data Group PTAC Part No 668109501 Date January 2008 IM 882 2008 McQuay International Applied Packaged Terminal Air Conditioner 16 x 42 PDAC PDHP With Top Mounted Hydronic Heat...

Страница 2: ...at Section 13 Installation of Room Cabinet 14 Supply and Return Coil Arrangements 14 Controls PDAC PDHP Digital Touchpad Control 15 19 Inputs Outputs 15 Keys and Indicators Labels 15 Display Function...

Страница 3: ...be damaged in transit due to rough handling even though the carton may not show external damages When the damage is discovered upon unpacking make a written request for inspection by the carrier s ag...

Страница 4: ...lectric Heat H Hydronic A Hydronic w Intermediate Electric Y None PDHP only Electric Heat A 2 5 Kw B 3 5 Kw C 5 0 Kw Y None Hydronic Heat Type S Steam Top Mount Normally Closed T Steam Subbase Normall...

Страница 5: ...ew or existing buildings The Figure 1 Exploded View of the 16 x 42 PDAC PDHP with Top Mounted Hydronic Unit self contained refrigerant system delivers cooling to the desired space Heating can be accom...

Страница 6: ...4 273 143 4 375 133 4 143 4 349 375 103 4 273 153 4 400 143 4 153 4 375 400 103 4 273 163 4 425 153 4 163 4 400 425 103 4 273 173 4 451 163 4 173 4 425 451 Note Electrical rough in should be located b...

Страница 7: ...it may cause leaks If the louver frame is to be installed in a panel wall it should be installed at the same time as the wall sleeve WARNING Residential and institutional cleaning compounds can cause...

Страница 8: ...propriatefasteners Useholesprovided seeFigure15 page 12 or drill additional holes as required to secure firmly CAUTION Do not drill holes in the base of the wall sleeve Use shims between the wall and...

Страница 9: ...eat Coil Section 3 1 2 Thick Batt Insulation 1 5 8 Metal Stud 16 O C Window Stool Insulation Wet Panel 16 11 4 42 Outdoor Side of Sleeve X 63 8 Optional Leveling Leg 13 3 4 X D Figure 11 16 x 42 wall...

Страница 10: ...of all debris that may interfere with installation Figure 12 Wall sleeve installation using top angles and field supplied continuous louver 133 4 349mm 11 4 38mm Insulated Panel Optional Top Angle 16...

Страница 11: ...heat section and room cabinet The wall sleeve should also be recessed enough to accom modate the outside louver Level wall sleeve side to side and pitch to outside 1 8 ft to assure proper sleeve drai...

Страница 12: ...g the wall sleeve in the opening is accomplished asshowninFigure15 Itisrecommendedthatrubberisola tion washers be used with the fasteners to minimize sound transmission from the equipment to the wall...

Страница 13: ...uto mode it will cycle the indoor fan when there is a call for heating or cooling See page 28 for jumper placement details 15 Set the temperature limiting feature to the desired range of thermostat op...

Страница 14: ...omplete so as not to damage the room cabinet after it has been installed Attaching the room cabinet can be com pleted as follows 1 Firmly grasp the room cabinet and lift it over the heat section There...

Страница 15: ...tton Remote must be aimed in a line of sight of the window in upper right corner on the front panel at less than a 45o angle from center of the window The control board will beep when any button is pr...

Страница 16: ...compressor and condenser fan shall turn on when Y signal is high 3 Cold start feature see Modes of Operation Cold Start Cool dry mode see Cold Dry Mode and Sleep feature see Sleep Feature are not avai...

Страница 17: ...higher than the set point It will stop if the space temperature sensor is 2 F or lower than the set point subject to timing requirements In the Cool Mode the indoor fan will operate according to the...

Страница 18: ...room temperature and the set point is less than 2 F This will also occur after a Cold Start or a Mode change from Cool to Cool Dry During this time the fan will operate in the Mode and Speed selected...

Страница 19: ...ll not operate In single motor units the outdoor fan will run along with the indoor fan Control Board Configuration To enter the Configuration Mode simultaneously press the Up and Down buttons for 5 s...

Страница 20: ...reaches 30 F and stays there for at least five 5 minutes 3 The compressor has run for at least 90 seconds Sleep Timer is overridden during this operation Anti freeze Protection is active in all modes...

Страница 21: ...Found _ __________________________________________________________________ _______________________________________________________________________________________ _____________________________________...

Страница 22: ...s equipment After the equipment leaves the factory it may become damaged or maladjusted during transportation or on the job Sometimes wires are disconnected accidentally or fan motors move on their ba...

Страница 23: ...mode However the control pad LED display will indicate the mode of operation and the room temperature Controls Premium Programmable Digital Touchpad Control Operating Instructions LED with Program Set...

Страница 24: ...by pressing Mode button 2 1 Once in the configuration mode the default temperature scale will be displayed as shown below Toggle the temperature scale to degree Celsius by pressing either or button 2...

Страница 25: ...thermostat for each period of the day repeat steps 3 3 through 3 7 Further the thermostat can be programmed for each individual day of the week or use the SimplesetTM feature as described below 3 9 S...

Страница 26: ...le stage heat single stage cool or single stage electric heat pump Terminations RC RH C W Y O B G Controls Remote Wall Mounted Thermostats Wall mounted thermostats are available for the Applied PTAC u...

Страница 27: ...urns off Vacation hold overrides programming Lockout feature prevents unwanted tampering Clear backlit display makes it easy to see time temperature and setpoint even in the dark No batteries required...

Страница 28: ...emote mounted thermostats should be wired as shown in Figure 30 Other considerations for this arrangement are as follows 1 When wiring the low voltage plug and receptacle disconnect provide enough wir...

Страница 29: ...y the room temperature 3 Jumper Placement to Select Controller Type A Place jumper across LUI to select unit mounted touchpad Local User Interface B Place jumper across SEC Secondary to select Control...

Страница 30: ...otor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface REV Re...

Страница 31: ...ssor Motor IFM Indoor Fan Motor OFM Outdoor Fan Motor HFLO Heat Fan Lockout Sensor OCS Outdoor Coil Sensor OAS Outdoor Air Sensor ICS Indoor Coil Sensor IAS Indoor Air Sensor LUI Local User Interface...

Страница 32: ...removal system and assure proper operation Pour at least two 2 cups of water into evaporator drain pan and verify proper operation Clean condensate drain and clear weep holes located at the bottom re...

Страница 33: ...ion of the rest of the system A further advantage is that a failed part can be quickly and easily replaced thus minimizing the inoperative time of the equipment This is so however only if a replacemen...

Страница 34: ...rees below minimum setpoint limit LA Low Ambient Lockout Outdoor air temperature is below 35 F Fault and Protection Codes for Applied PTAC PTHP Control Board Fault code Description Cause for the fault...

Страница 35: ...tructed discharge grilles 5 Evaporator blower motor not running 6 Evaporator blower motor not up to speed 7 Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipment e...

Страница 36: ...e oil or grease to gap between solenoid and armature g Tighten h Fasten securely i Occasionally equipment will have noise for no ap parent reason Inspection has revealed no loose components that might...

Отзывы: