15

 

Compressor Control 

Multiple Compressor Staging 

This section defines which compressor is the next one to start or stop.  The next section 
defines when the start, or stop, is to occur.  

Functions 

1.  Can start/stop compressors according to an operator-defined sequence. 

2.  Can start compressors based on the least number of starts (run hours if starts are equal) 

and stop on most run hours. 

The above two modes can be combined so that there are two or more groups where all 
compressors in the first group are started (based on number of starts/hours) before any in the 
second group, etc.  Conversely, all compressors in a group are stopped (based on run hours) 
before any in the preceding group, etc. 

Required Parameters 

1.  Sequence number setpoint for all compressors.  Possible settings = (1-3). Compressors 

will start in the specified order.  Default operation sequence is 1 for all compressors 
(meaning they will start based on number of starts).  That is, if all are 1s, the controller 
will look at number of starts and run-hours 

2.  Maximum Number of compressors ON setpoint.  Possible settings = (1-3).   

3.  Number of starts for all compressors. 

4.  Number of run hours for all compressors. 

5.  Status of all compressors (Available/Unavailable, Pumping down, Running, etc.). 

Multiple Compressor Start/Stop Timing 

This section defines when a compressor is to start, or stop, and the scenario for doing so. 

Starting 

Staging up, no compressors on the unit are running: 

The first compressor can start when the LWT is more than the sum of the active LWT 
setpoint and the Startup Delta-T.  For example, with default settings, the active setpoint 
would be 44

°

F and the startup delta would be 10 degrees F.  In this case, the LWT must be 

greater than 54

°

F.  This is a necessary, but may not be a sufficient, condition for starting the 

first compressor.   The Startup Delta-T is adjustable from 10 degrees down to 0 degrees F. 

Staging up, at least one compressor is already running: 

Additional compressors can start when the LWT is more than the sum of the active LWT 
setpoint and the Stage Delta-T.  With the default settings, the active setpoint is 44

°

F, and the 

Stage Delta would be 2 degrees F.  So, one necessary condition for staging an additional 
compressor on is that the LWT must be higher than 46

°

F.   

If in Cool Mode, an additional requirement is that all running compressors are running at 
their maximum capacity, or at least 75% slide position and the Stage Up Delay Timer (5 
minute default) has timed out.  Also, a compressor is considered to be at its maximum 
capacity if it is in an inhibit or unload situation due to low evaporator pressure, high 
condenser pressure, or low discharge superheat.  If a compressor is set for manual slide 
control, or the slide target has reached the maximum allowed by the Max Slide setpoint, it 
will also be flagged as being at maximum capacity. 

Содержание AGS 206A

Страница 1: ...5 Group Chiller Part Number 331373201 Date June 2005 Supersedes OM AGSB 4 GeneSys Air Cooled Screw Compressor Chiller AGS 230A B through AGS 475A B 60 Hertz AGS 206A B through AGS 411A B 50 Hertz Sof...

Страница 2: ...oller Menus 40 Screen Definitions 41 SET Screen Definitions 43 Circuit Controller Menus 47 Screen Definitions 47 SEQUENCE OF OPERATION 52 START UP AND SHUTDOWN 54 Expansion Valve Operation 55 Extended...

Страница 3: ...on of the equipment being controlled CAUTION Static sensitive components A static discharge while handling electronic circuit boards can cause damage to the components Discharge any static electrical...

Страница 4: ...iagnostics to inform operators of warning and fault conditions in plain language All events alarms and faults are time and date stamped for identification of when the fault condition occurred In addit...

Страница 5: ...are labeled CIRCUIT CONROL In addition to providing all normal operating controls the MicroTech II control system monitors equipment protection devices on the unit and will take corrective action if...

Страница 6: ...nimum and maximum setpoints These setpoints simply cut off the value to a working range and this range can be limited to a single value if the two setpoints are set to the same value CPU Error These a...

Страница 7: ...d Setpoint The psi evaporator pressure setting at which the controller will not allow further compressor loading Low High Superheat Error The difference between actual evaporator superheat and the sup...

Страница 8: ...p Stage On or Stage Up is the act of starting a compressor or fan when another is still operating The two phrases are interchangeable and either one can be used depending on the date of issue of the s...

Страница 9: ...FT RIGHT have three modes of use 1 Scroll between data screens in the direction indicated by the arrows default mode 2 Select a specific data screen in the menu matrix using dynamic labels on the righ...

Страница 10: ...12 F 7 Slide Load Indicator 4 to 20 mA 0 to 100 8 Open NOTE Value at the converter board input Value at the converter board output is 0 1 VDC 0 9 VDC These parameters are analog inputs to the circuit...

Страница 11: ...l Return Line Solenoid Closed Open 11 Open 12 Open 13 EXV Close Signal Contact EXV Follows 0 10 VDC EXV Closed Ignores 0 10 VDC 10 These parameters are digital outputs from this controller Their value...

Страница 12: ...0 20 0 o F M Stage 2 Up Deadband 8 0 1 0 20 0 o F M Stage 3 Up Deadband 10 0 1 0 20 0 o F M Stage 4 Up Deadband 12 0 1 0 20 0 o F M Stage 1 Down Deadband 8 0 1 0 20 0 o F M Stage 2 Down Deadband 7 0...

Страница 13: ...not restart in ICE mode The time delay is user adjustable The Ice Delay Timer may be manually cleared to force a restart in ICE mode A set point specifically for clearing the ICE mode delay is availab...

Страница 14: ...d on the right is for unload oil feed In Circuit Enable mode normal operation the controller makes decisions to move the Slide target the calculated value and pulses the proper solenoid in order to ke...

Страница 15: ...ompressor is to start or stop and the scenario for doing so Starting Staging up no compressors on the unit are running The first compressor can start when the LWT is more than the sum of the active LW...

Страница 16: ...of Operation The following conditions override the automatic slide control when the chiller is in COOL mode or ICE mode These overrides keep the circuit from entering a condition in which it is not de...

Страница 17: ...target will be adjusted down 2 every 5 seconds as long as the superheat remains below 20o F Maximum LWT Pulldown Rate The maximum rate at which the leaving water temperature can drop is limited by the...

Страница 18: ...ere the compressor needs to shut down normally a pumpdown will be performed The slide target will automatically go to 0 while pumping down and the compressor will run until the pumpdown pressure has b...

Страница 19: ...arget until it is equal to the saturated condenser temperature target setpoint This will allow the VFD to slowly bring the saturated condenser temperature back down Condenser Target This logic is only...

Страница 20: ...ambient temperature When the compressor starts a FanTrol stage is forced based on the following table Table 8 Forced Staging Outside Air Temperature FanTrol Stage At Start 75 o F Forced FanTrol 1 SP...

Страница 21: ...EXV 100 100 Max EXV 0 Min EXV 0 EXV Control Range 0 Slide Position EXV Steps Min EXV 100 1 Pre Open At the time of a start request the EXV will perform a pre open function This is to provide sufficien...

Страница 22: ...pressure unload occurs Starting with F code when suction pressure drops below the low evaporator pressure unload setpoint the controller will switch from subcool control to pressure control until suf...

Страница 23: ...peration in an off state see Unit Test Mode on page 28 Evaporator Oil Return Line Control The oil return solenoid shall be on any time the compressor is running and any of the following occurs Slide p...

Страница 24: ...Switch 0 VAC Stop 24 VAC On 2 Remote Switch 0 VAC Stop 24 VAC Start 3 Evaporator Water Flow Switch 0 VAC No Flow 24 VAC Flow 4 Mode Switch 0 VAC Cool 24 VAC Ice 5 Open 6 Open The following parameters...

Страница 25: ...English M BAS Protocol NONE NONE BACnet LonWorks CAREL MODBUS N2 M Ident number 1 0 200 M Baud Rate 19200 1200 2400 4800 9600 19200 M Compressors Sequence Cir 1 1 1 3 M Sequence Cir 2 1 1 3 M Sequence...

Страница 26: ...0 F Fan VFD Y 0 60 F Unit Enable Enabling and disabling the chiller is controlled by the Unit Enable Setpoint with options of OFF and ON The Unit OFF input unit On Off switch field installed Remote st...

Страница 27: ...N x ON ON NETWORK x x OFF OFF ON NETWORK OFF x x OFF ON NETWORK ON x ON ON All methods of disabling the chiller except for the unit switch will cause a normal shutdown of any running circuits Any time...

Страница 28: ...col COOL w Glycol KEYPAD x ICE w Glycol x COOL ICE w Glycol ICE w Glycol NETWORK x x COOL COOL ICE w Glycol COOL w Glycol NETWORK x x ICE COOL ICE w Glycol ICE w Glycol x x x x ICE w Glycol ICE w Glyc...

Страница 29: ...dicator You will see a selection to choose the slide pulse direction with the options of Load left coil or Unload right coil Then there is a selection to turn the pulse on or off Choose on for the Pul...

Страница 30: ...point 4 degrees F Leaving Water Temperature LWT Reset The Active Leaving Water setpoint is set to the current Leaving Water Temperature LWT setpoint unless the unit is in COOL mode and any of the rese...

Страница 31: ...4 20 mA Input Signal The Active Leaving Water setpoint is adjusted by the 4 to 20 mA reset analog input Parameters used 1 Cool LWT setpoint 2 Max Reset setpoint 3 LWT Reset signal Reset is 0 if the r...

Страница 32: ...Reset setpoint 3 OAT Reset is 0 if the outdoor ambient temperature is greater than 75 F From 75 down to 60 F the reset varies linearly from no reset to the max reset at 60 F At ambient temperatures l...

Страница 33: ...s below evap freeze protect setpoint Rapid Stop Leaving Evaporator Water Temperature Sensor Fault Sensor shorted or open Rapid Stop Outside Air Temperature Sensor Fault Sensor shorted or open Normal S...

Страница 34: ...elf clearing in the starter itself Alarms triggered by these faults will be allowed to self clear twice per day The third will trigger a manual reset in the controller requiring it to be cleared via t...

Страница 35: ...minutes Pumpdown and stop Comp state off Oil Level Low DI9 Open for Time greater than Low Oil Level Delay AND more than one hour since last occurrence Rapid stop Comp state off Failed Pumpdown Circui...

Страница 36: ...lide position and number of fans on are also stored To view alarms activate the manager password press Menu on the unit controller then select Alarm left arrow then select Active or Log Event Logging...

Страница 37: ...key 3 Change field values in edit mode according to the following table LEFT Default D RIGHT Cancel C UP Increment DOWN Decrement These four edit functions are indicated by one character abbreviation...

Страница 38: ...efault changes a value to the factory set default value RIGHT key Cancel cancels any change made to a value and returns to the original setting UP key Increment increases the value of the setting DOWN...

Страница 39: ...anager If the wrong password is entered a temporary message will appear so stating If no valid password is active the active password level displays none Entering an incorrect password while a passwor...

Страница 40: ...croll through all of them with the 4 arrow keys For this use the screens are arranged logically in a matrix as shown below Table 25 Unit Controller Menu Structure VIEW MENUS VIEW UNIT STATUS 1 VIEW UN...

Страница 41: ...gs are entered to these screens VIEW UNIT STATUS 1 Unit Status Unit Mode Evap Pump run Unit Status will display one of the following Auto Off Keypad Disable Off Test Mode Auto Wait for flow Off Ice Mo...

Страница 42: ...IEW CIR N STATUS 1 Off Ready Slide Position 000 0 Slide Target 000 0 Slide position and slide target are explained on page 18 VIEW CIR N STATUS 2 Hours XXXXX Starts XXXXX VIEW REFR CIR N 1 Evap Press...

Страница 43: ...rm or event could be shown The alarm log and event log can show up to the 25 most recent occurrences EVENT LOG 1 25 Event Description hh mm mm dd yy ALARM LOG 1 25 Alarm Description hh mm ss dd mmm yy...

Страница 44: ...able effect of increasing compressor cycling The StopDelta is the number of degrees below the chilled water setpoint the water temperature must fall for the last compressor to stop The StageDelta is t...

Страница 45: ...its F psi Lang ENGLISH Inch Pound units of measure and English language are the only options available in this software version SET UNIT SPs 12 Protocol Ident Number Baud Rate SET UNIT SPs 13 Enter Pa...

Страница 46: ...SPs 5 Stg Up Delay XXXsec SET ALARM LMTS 1 Low Evap Pressure Hold 59 0 psi Unload 58 0 psi SET ALARM LIMITS 2 LowOilDelay XXX sec HighOilDpDel XXX sec SET ALARM LIMITS 3 MinLiftDel XXX sec Low Subcool...

Страница 47: ...SET SCREENS TEST SCREENS VIEW UNIT 1 VIEW CIR 1 VIEW REFRG 1 VIEW FANS 1 SET COMP SPs SET EXV SPs 1 SET FANS 1 SET SENSOR OFFSETS 1 TEST COMP 1 VIEW UNIT 2 VIEW CIR 2 VIEW REFRG 2 VIEW FANS 2 SET COMP...

Страница 48: ...outputs in menu 5 are defined in Table 2 and Table 4 beginning on page 10 0 Off 1 ON VIEW CIR STATUS 4 Digital Outputs 11 12 13 0 0 0 VIEW CIR STATUS 5 Analog Outputs volts X 100 1 XXXX 3 XXXX VIEW C...

Страница 49: ...VIEW REFRIGERANT 7 EXV Steps XXXX EXV ctrl range XXXX XXXX steps VIEW FANS 1 VFD Speed XXX X Fans Running X VFD Target XXX X F VIEW FANS 2 Target Sat T XXX X F Stage Up Err XXX Stage Dn Err XXX SET Sc...

Страница 50: ...NNNN amps EXV Setpoints SET EXV SPs 1 EXV Control auto Manual EXV Pos XXXX Pre open time XXX sec SET EXV SPs 2 Min EXV XXX steps Service pumpdown No Fan Setpoints SET FAN SPs 1 Fan VFD no Number of f...

Страница 51: ...Press XX X psi Liq Press XX X psi SET SENSOR OFFSET 2 Suct Temp X X F Disch Temp X X F Liq Temp X X F SET SENSOR OFFSET 3 Slide min pos XX Slide max pos XX Slide Pos XXX X Test TEST CIRCUIT 1 Fans 1 O...

Страница 52: ...cating panel such a BAS protocol interface The display will show OFF RemoteComm if this operating mode is in effect If an alarm condition exists which prevents normal operation of both refrigerant cir...

Страница 53: ...activate the remaining condenser fans as needed to maintain proper condenser pressure The MicroTech II controller continuously monitors the condenser minus evaporator lift pressure and will adjust th...

Страница 54: ...cy must perform initial start up in order to activate warranty CAUTION Most relays and terminals in the unit control center are powered when S1 is closed and the control circuit disconnect is on There...

Страница 55: ...ressure target The base pressure target is calculated using the following formula Base target 2 3LWT 8 The base target is limited to a range from the low pressure inhibit set point plus 2 psi up to 52...

Страница 56: ...ompressors have pumped down turn off the chilled water pump CAUTION Do not turn the unit off using the S1 switch without first moving PS1 and PS2 to the Stop position unless it is an emergency as this...

Страница 57: ...glycol is not used in the system drain all water from the unit evaporator and chilled water piping if the unit is to be shutdown during winter Do not leave the vessels or piping open to the atmosphere...

Страница 58: ...rcuit The control power can be rewired to a separate 115V supply do not wire directly to the heater If this is done the disconnect switch should be clearly marked to avoid accidental deactivation of t...

Страница 59: ...ese figures are examples only and cannot be appropriate to every situation Generally for an extended margin of protection select a temperature at least 10 F lower than the expected lowest ambient temp...

Страница 60: ...DSH drops below 20 then it will unload Excessive refrigerant charge excessive oil a large amount of oil in circulation and a leaking or over feeding evaporator solenoid valve will all cause low discha...

Страница 61: ...tween 20 and 22 DSH the compressor will not load up and will be in an low discharge superheat inhibit event The higher the refrigerant flow the more liquid carry over we will get from the flooded evap...

Страница 62: ...rry over will result in higher discharge superheats More liquid carry over will occur when 1 The refrigerant circuit is overcharged 2 Excessive oil is in the evaporator 3 Mass flow rate of compressor...

Страница 63: ...ACnet When selected the ident number and baud rate setpoints are not available Baud rate is locked at 19200 The factory installed kits on the MicroTech II controller are as follows BACnet Kit P N 3501...

Страница 64: ...MAX N 120 VAC 85 2 CHW PUMP RELAY 2 BY OTHERS 120 VAC 1 0 AMP MAX N 120 VAC 81 75 24 VAC ALARM BELL RELAY FACTORY SUPPLIED ALARM FIELD WIRED ALARM BELL OPTION TB1 24 VAC OR 30 VDC 71 72 69 60 67 NOR...

Страница 65: ......

Страница 66: ...y International 800 432 1342 www mcquay com OM AGSB 5 6 05 This document contains the most current product information as of this printing For the most up to date product information please go to www...

Отзывы: