www.mcohome.com User Manual
MCOHome Technology Co., Ltd
6
Note: Follow the same steps to exclude
the device from the network.
After inclusion, turn off the device and
then turn it on. Now the device is ready to be
operated by controller/ gateway in Z-Wave
network.
Association Group
Thermostat supports 1 association group. A gateway is suggested to associate with this
group. Then if any changes happen, such as: temperature, working mode, etc., the thermostat
will report to this associated device (gateway).
Command Class supported by the device:
COMMAND_CLASS_BASIC;
COMMAND_CLASS_THERMOSTAT_SETPOINT;
COMMAND_CLASS_THERMOSTAT_MODE;
COMMAND_CLASS_THERMOSTAT_OPERATING_STATE;
COMMAND_CLASS_SENSOR_MULTILEVEL;
COMMAND_CLASS_ASSOCIATION;
COMMAND_CLASS_VERSION;
COMMAND_CLASS_MANUFACTURER_SPECIFI
COMMAND_CLASS_TIME,
COMMAND_CLASS_TIME_PARAMETERS
Note:
This device supports 4 kinds of modes in Z-Wave:
Off
mode;
Heating
mode (Manual);
Energy Saving heating
mode (Auto) ;
Away heating
mode (Vacation).
Users can set these 4 modes via COMMAND_CLASS_THERMOSTAT_MODE. And
COMMAND_CLASS_BASIC can switch among Heating mode & Energy saving heating mode.
COMMAND_CLASS_THERMOSTAT_SETPOINT can be used to set the heating
temperature threshold value in Heating mode or Energy saving heating mode.
Parameters Settings:
Add
Function
Byte
Options
Default
Remark
1
Upload temperature
format automatically
1
0x00Celsius 0x01Fahrenheit
0x02Follow the main display
0x02
2
Upload temperature
value automatically
1
0x00 OFF
0x01 Upload the difference
value only
0x02 Timing upload mode
only
0x03 Upload the
diftiming upload
mode
0x03
3
Upload temperature
difference
2
Base on 0.1
℃
unit, 0x0005
by default, 5*0.1
℃
=0.5
℃
,
0x0003~0x03E8
0x0005
0.5
℃